AS Details:E2.7.11 (Counter-flashing - Diverter Flashing)

Jump to: navigation, search

AS Details:E2.7.11 (Counter-flashing - Diverter Flashing)


7.1.5.9.jpg



WORK INCLUDED

(1) Trim: and the kick-out must be approximately 20-degree angle to the vertical slope.

(2) Fold Layout: Formed from a minimum 26 guage galvanized steel diverters shall extend a minimum 125 mm (5") up vertical surfaces 100 mm (4") to the roof.

(3) Breadpanned Corner Fold: Fold up must be equal in height to to the upstand of the flashing.

(4) Hidden Seam: Breadpan fold to be turned behind the upstand.

(5) Angle Trim: Kick-out can be angle trimmed and a drip edge formed at the outlet. Outlet is to extend a minimum of 25mm (1") lower than the edge of the roof material and lead water into the gutter where existing.

NOTE
  • Refer to RGC Guarantee Standards for additional requirements
  • Proprietary soldered or welded diverter flashing may be used provided they conform to RGC Guarantee Standards.


Back to Asphalt Shingle Application

Back to Asphalt Shingles Construction Details