WP Details:F1.7.6 (Walls - Planter Pre-Curb Wall)

Jump to: navigation, search

WP Details:F1.7.6 (Walls - Planter Pre-Curb Wall)

Revision as of 20:08, 25 October 2016 by James Klassen (talk | contribs)
RoofStar Guarantee Standards are blue-linked
SBS Details

D1.7.6-5 (1).jpg

D1.7.6-5 (2).jpg

1 WORK INCLUDED

(1) Primary Waterproofing Membrane: Fully adhered to acceptable substrates (concrete slab depicted), installed as per RoofStar Guarantee Standards and Membrane Manufacturer's installation specifications.

(2) Membrane Primer or Adhesive: proprietary primer or adhesive, application and quantities as directed by membrane manufacturers published application specifications.

(3) Pre-Curb (Start-Up Curb) Membrane Flashing: Two ply of membrane flashing (elastomeric, plastomeric, or modified bituminous) completely enclosing pre-curb and installed as per membrane manufacturer's published application specifications. Install membrane reinforcement gussets at all corner detail transitions.

(4) Proprietary liquid membrane flashing System: RoofStar-accepted Liquid Membrane Flashing System(s) (NOTE: Refer to Liquid Membrane Flashing Systems in the Accepted Materials section of this Manual). Install as per Manufacturer's published instructions.

(5) Inside Planter Wall Membrane Flashing: Adhered according to manufacturer's specifications. Carry membrane flashing plies to reglet termination near top of planter wall (stagger membrane seal minimum 300mm (6").

(6) Reglet Metal Counter Flashing

(7) Plaza Deck Assembly: Extruded polystyrene insulation and filter mat (optional) over primary waterproofing membrane. Concrete pavers placed above pre-curb membrane flashing height on proprietary pedestals. Note: membrane and metal wall counter flashing is not required above pre-curb membrane flashing on plaza deck side of planter walls.

2 RELATED WORK BY OTHERS

(A) Acceptable Deck: Concrete slab shown

(B) Pre-Curb: Minimum of 100mm (4") in height above concrete deck, smooth dry and clean.

(C) Pre-Curb: Form on top of membrane sealed Pre-curbs or Start-up curbs.

(D) Re-Bar: Placed at centre of Pre-curb.

(E) Reglet: Pre-manufactured purpose-made reglet cast in concrete wall or saw-cut.

(F) Alternate Termination: Horizontal Reglet alternative to premanufactured purpose-made reglet cast in concrete wall or saw-cut on vertical surface of inside planter walls.

NOTE: Refer to RoofStar Guarantee Standards for additional requirements.



RoofStar Guarantee Standards for Waterproofing Plazas, Promenades & Terraces

Back to Waterproofing Construction Details