EPDM Control Joint (Roof Divider)

Jump to: navigation, search

EPDM Control Joint (Roof Divider)

Revision as of 19:24, 12 November 2025 by James Klassen (talk | contribs)



Division D - Construction Details


EPDM | Control Joint (Roof Divider) ( Article 10.3.2.3.; Article 10.3.4.1.)

Notice to Reader
Images used in a Construction Detail are representative and not prescriptive, and are not necessarily drawn to scale. They are intended to support the related Standard (Ref. Division A, Article 2.2.1.2.).

The reader may link to the related Article in the detail title, or link to the Standard as it relates to a specific element in the detail. All hyperlinks are displayed blue text.

EPDM Details


Drawing A
Drawing B

1 WORK INCLUDED

(1) Control Joint (Roof Divider)
Typically framed with dimensional lumber and plywood on site by the Contractor, or by others (as specified). Insulated control joint shown in Drawing (A). See Article 10.1.6.2. concerning permissible design heights for control joints.
(2) Roof membrane
Carried up and over the top of the control joint as stated above. Single-ply membranes may be run up and over the control joint (secured at the base on either side with proprietary securement strips), or the control joint may be flashed (again, using the manufacturer’s securement strips).
(2a) Roof Membrane Securement Strip
Proprietary to a single-ply membrane manufacturer and installed to secure the field membrane at the base of a wall, parapet, expansion joint, or control joint. Not required for SBS-modified bituminous membrane systems.
(3) Metal Cap Flashing
Required only when the low control joint (less than 203.2 mm (8”) in height) is not fully enveloped with at least two plies of sheet membrane flashing. Cap flashing must be designed and installed as required in Part 13.
Note that the cap flashing is sloped at least 2% (mono slope illustrated) when the width of the flashing exceeds 101.6 mm (4”) (Ref. Article 13.1.3.6., “Cap Flashing, Counter-flashing, and Reglet Flashing”).

2 RELATED WORK BY OTHERS

(A) Acceptable deck

NOTE: See the Standard for additional requirements.


Back to EPDM Roof System Details