Asphalt Shingles - Intersection with Waterproofing Roof (Lower)

Jump to: navigation, search

Asphalt Shingles - Intersection with Waterproofing Roof (Lower)



Division D - Construction Details


Asphalt Shingles | Intersection with Waterproofing Roof (Lower) ( Article 10.3.7.2.)

Notice to Reader
Images used in a Construction Detail are representative and not prescriptive, and are not necessarily drawn to scale. They are intended to support the related Standard (Ref. Division A, Article 2.2.1.2.).

The reader may link to the related Article in the detail title, or link to the Standard as it relates to a specific element in the detail. All hyperlinks are displayed blue text.

Asphalt Shingle Details
Click on any image to expand it
ASh Figure 10.3.7.-B.jpg
ASh Intersection with Waterproofing Roof (Lower) 2.jpg

1 WORK INCLUDED

(1) Underlayment
Required, and installed to overlap the Valley Protection Membrane and the Valley Metal Flashing. Install ‘shingle-style’, following the requirements for side and end laps; use acceptable fasteners, or adhere (if a self-adhering membrane) in keeping with the manufacturer’s published requirements.
(2) Field Shingles
Fasteners used to secure shingles must be at least 300 mm (12") above the finished surface of the roof waterproofing system.
(3) Waterproofing roof system
Secure membrane to water-shedding roof deck at least 300 mm (12") above the finished surface of the roof waterproofing (refer to the related Membrane Standards, Part 9 FIELD MEMBRANE and Part 10 PERIMETERS and WALLS).

2 RELATED WORK BY OTHERS

(A) Acceptable Deck

NOTE: See the Standard for additional requirements.


Back to Asphalt Shingle System Details

Home

© RCABC 2024
No reproduction of this material, in whole or in part, is lawful without the expressed permission of the RCABC Guarantee Corp.