=== WORK INCLUDED ===
 
=== WORK INCLUDED ===
;(1) '''Membranes''': Membranes must be installed to '''''RoofStar Guarantee Standards''''' and the manufacturer's printed instructions ({{hilite | NOTE: Fasteners shall be installed 4” or more above the maximum water line, and gutters must include a scupper overflow drain. || 2017-April-22 }}).  Also refer to [[RoofStar Guarantee Standards for ASM Roof Systems#ASMGUT|'''9 Built-in Gutters''']] in the '''''RoofStar Guarantee Standards for ASM Roof Systems'''''.  
+
;(1) '''Membranes''': Membranes must be installed to '''''RoofStar Guarantee Standards''''' and the manufacturer's printed instructions ({{hilite | NOTE: Fasteners shall be installed 4” or more above the maximum water line, and gutters must include a scupper overflow drain. || 2017-April-22 }}).  Also refer to [[RoofStar Guarantee Standards for ASM Roof Assemblies#ASMGUT|'''9 Built-in Gutters''']] in the '''''RoofStar Guarantee Standards for ASM Roof Systems'''''.  
 
;(2) '''Adhesion''': Membranes must be fully adhered, where exposed, and mechanically fastened at terminations 300 mm (12") o/c
 
;(2) '''Adhesion''': Membranes must be fully adhered, where exposed, and mechanically fastened at terminations 300 mm (12") o/c
 
;(3) '''Height''': The minimum vertical sealed height above the maximum water level is 150 mm (6"). The membrane run up the slope will vary with roof pitch. Increase height in heavy snow regions.
 
;(3) '''Height''': The minimum vertical sealed height above the maximum water level is 150 mm (6"). The membrane run up the slope will vary with roof pitch. Increase height in heavy snow regions.
;(4) [[RoofStar Guarantee Standards for Asphalt Shingles Roof Systems#ASEave|'''Eave Protection and Underlay''']]: Built-in gutter membranes can be extended to act as an eave protection membrane. Underlay or eave protection membrane must overlap built-in gutter membrane by a minimum of 200 mm (8") and be installed in shingle fashion (not shown for clarity).
+
;(4) [[RoofStar Guarantee Standards for Asphalt Shingles Roof Assemblies#ASEave|'''Eave Protection and Underlay''']]: Built-in gutter membranes can be extended to act as an eave protection membrane. Underlay or eave protection membrane must overlap built-in gutter membrane by a minimum of 200 mm (8") and be installed in shingle fashion (not shown for clarity).
  
 
<hr>
 
<hr>
Line 22: Line 22:
 
=== RELATED WORK BY OTHERS ===
 
=== RELATED WORK BY OTHERS ===
 
;(A) '''Dimension''': Dimensions of parapets, cants and water loading of gutters are variable and should be determined by design authority  
 
;(A) '''Dimension''': Dimensions of parapets, cants and water loading of gutters are variable and should be determined by design authority  
;(B) [[RoofStar Guarantee Standards for Asphalt Shingles Roof Systems#ASDECK|'''Acceptable Deck''']]
+
;(B) [[RoofStar Guarantee Standards for Asphalt Shingles Roof Assemblies#ASDECK|'''Acceptable Deck''']]
 
</div><!-- COL-6-MD -->
 
</div><!-- COL-6-MD -->
 
</div><!-- PANEL BODY -->
 
</div><!-- PANEL BODY -->
Line 32: Line 32:
  
  
 
+
[[RoofStar Guarantee Standards for Asphalt Shingles Roof Assemblies|<i class="fa fa-chevron-circle-left fa" ></i> RoofStar Guarantee Standards for Asphalt Shingles Roof Assemblies]]
[[RoofStar Guarantee Standards for Asphalt Shingles Roof Systems|<i class="fa fa-chevron-circle-left fa" ></i> RoofStar Guarantee Standards for Asphalt Shingles Roof Systems]]
 
  
 
[[Asphalt Shingles Construction Details|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''Asphalt Shingles Construction Details'']]
 
[[Asphalt Shingles Construction Details|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''Asphalt Shingles Construction Details'']]
  
[[Section:G. Construction Details|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''Construction Details'']]
+
[[Construction Details|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''Construction Details'']]

Revision as of 18:00, 23 October 2017

RoofStar Guarantee Standards are blue-linked
ASM Details

8.3.1.jpg

1 WORK INCLUDED

(1) Membranes
Membranes must be installed to RoofStar Guarantee Standards and the manufacturer's printed instructions (NOTE: Fasteners shall be installed 4” or more above the maximum water line, and gutters must include a scupper overflow drain.). Also refer to 9 Built-in Gutters in the RoofStar Guarantee Standards for ASM Roof Systems.
(2) Adhesion
Membranes must be fully adhered, where exposed, and mechanically fastened at terminations 300 mm (12") o/c
(3) Height
The minimum vertical sealed height above the maximum water level is 150 mm (6"). The membrane run up the slope will vary with roof pitch. Increase height in heavy snow regions.
(4) Eave Protection and Underlay
Built-in gutter membranes can be extended to act as an eave protection membrane. Underlay or eave protection membrane must overlap built-in gutter membrane by a minimum of 200 mm (8") and be installed in shingle fashion (not shown for clarity).

2 RELATED WORK BY OTHERS

(A) Dimension
Dimensions of parapets, cants and water loading of gutters are variable and should be determined by design authority
(B) Acceptable Deck

NOTE: Refer to RoofStar Guarantee Standards for additional requirements.