(Created page with "File:6.3.2.1.jpg === WORK INCLUDED === (1) <b>Vapour Retardant:</b> If required by design authority. (2) <b>Insulation: </b>Mechanically attached where deck type permit...")
 
 
(28 intermediate revisions by the same user not shown)
Line 1: Line 1:
[[File:6.3.2.1.jpg]]
+
{{Template:RPM Info}}
  
 +
{{DISPLAYTITLE:<span style="position: absolute; clip: rect(1px 1px 1px 1px); clip: rect(1px, 1px, 1px, 1px);">{{FULLPAGENAME}}</span>}}
 +
__NOTOC__
  
 +
<big><big>Division D - Construction Details</big></big>
 +
<hr>
 +
<big><big><big><big><big>EPDM | Conventionally Insulated System (Alternate) ([[EPDM_Roof_Systems_Standard#1.1.3.1._Permitted_Roof_Systems | Article 1.1.3.1.]])</big></big></big></big></big>
 +
{{Template:Construction Details Header}}
 +
<div class="panel panel-success">
 +
<div class="panel-heading"><big>'''EPDM Details'''</big></div>
 +
<div class="panel-body">
 +
<div class="col-md-6">
 +
<div style="text-align:center; vertical-align:center">
 +
[[File:6.3.2.1.jpg|class=img-responsive]]
 +
</div>
 +
</div><!-- COL-MD-6 -->
 +
 +
<div class="col-md-6">
 
=== WORK INCLUDED ===
 
=== WORK INCLUDED ===
(1) <b>Vapour Retardant:</b> If required by design authority.
+
;(1) [[EPDM Roof Systems Standard#PART_6|'''Vapour Retarder''']]: If required by design authority.
 
+
;(2) [[EPDM Roof Systems Standard#PART_7|'''Insulation''']]: Mechanically attached where deck type permits. Installed according to ''RoofStar Guarantee Standards''. See available insulation products in the [[Division C | Division C]] of this Manual.
(2) <b>Insulation: </b>Mechanically attached where deck type permits. Installed according to <i>RGC</i> <i>Guarantee Standard </i>A4.3.<i> </i>See Section 2.2 for accepted materials
+
;(3) [[EPDM Roof Systems Standard#PART_9|'''Adhesive''']]: Proprietary, installed according to manufacturer's instructions, usually brushed, rolled or sprayed.
 
+
;(4) [[EPDM Roof Systems Standard#PART_9|'''Single-ply Membrane''']]: Installed according to manufacturer's instructions and ''RoofStar Guarantee Standards''.
(3) <b>Adhesive: </b>Proprietary, installed according to manufacturer&#8217;s instructions, usually brushed, rolled or sprayed.
+
;(5) '''Membrane Lap''': Thermoset membrane may be joined using uncured tape or proprietary adhesive.
 
+
;(6) '''Edge Flashing''': Proprietary.
(4) <b>Single Ply Membrane:</b> Installed according to manufacturer&#8217;s instructions and <i>RGC</i> <i>Guarantee Standards </i>Section<i> </i>2.1.1 and Section 2.1.3.
+
;(7) [[EPDM Roof Systems Standard#PART_10|'''Membrane Flashing''']]: Installed according to manufacturer's instructions.
 
 
(5) <b>Membrane Lap: </b>Thermoplastic membrane may be welded or chemically bonded (See Section 6.2) Thermoset membrane may be joined using uncured tape or proprietary adhesive (See Section 6.1).
 
 
 
(6) <b>Edge Flashing:</b> Proprietary.
 
 
 
(7) <b>Membrane Flashing:</b> Installed according to manufacturer&#8217;s instructions.
 
  
 +
<hr>
  
 
=== RELATED WORK BY OTHERS ===
 
=== RELATED WORK BY OTHERS ===
(A) <b>Acceptable Deck</b>
+
;(A) [[EPDM Roof Systems Standard#PART_2|'''Acceptable Deck''']]
 
+
;(B) Fascia: Optional.
(B) <b>Fascia:</b> Optional.
+
;(C) Wood Blocking
 
+
</div><!-- COL-6-MD -->
(C) <b>Wood Blocking:</b> Equal to height of insulation.
+
</div><!-- PANEL BODY -->
 
+
</div><!-- PANEL -->
NOTE: Refer to <i>RGC Guarantee Standards</i> for additional requirements.
 
  
 +
'''NOTE''': See the [[EPDM Roof Systems Standard | '''Standard''']] for additional requirements.
  
 +
<hr>
  
[[Section:D. Application: Low Slope Roofs|<i class="fa fa-chevron-circle-left fa-2x" ></i> Back to ''EPDM Application'']]
+
[[EPDM (Thermoset Membranes) Construction Details|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''EPDM Construction Details'']]
  
[[EPDM (Thermoset Membranes) Construction Details|<i class="fa fa-chevron-circle-left fa-2x" ></i> Back to ''EPDM Construction Details'']]
+
[[Main Page | <i class="fa fa-home fa"></i> Home]]
  
[[Section:G. Construction Details|<i class="fa fa-chevron-circle-left fa-2x" ></i> Back to ''Construction Details'']]
+
{{Tempate:RPM Page Footer with Copyright and Current Date}}

Latest revision as of 21:53, 27 June 2022



Division D - Construction Details


EPDM | Conventionally Insulated System (Alternate) ( Article 1.1.3.1.)

Notice to Reader
Images used in a Construction Detail are representative and not prescriptive, and are not necessarily drawn to scale. They are intended to support the related Standard (Ref. Division A, Article 2.2.1.2.).

The reader may link to the related Article in the detail title, or link to the Standard as it relates to a specific element in the detail. All hyperlinks are displayed blue text.

EPDM Details

6.3.2.1.jpg

1 WORK INCLUDED

(1) Vapour Retarder
If required by design authority.
(2) Insulation
Mechanically attached where deck type permits. Installed according to RoofStar Guarantee Standards. See available insulation products in the Division C of this Manual.
(3) Adhesive
Proprietary, installed according to manufacturer's instructions, usually brushed, rolled or sprayed.
(4) Single-ply Membrane
Installed according to manufacturer's instructions and RoofStar Guarantee Standards.
(5) Membrane Lap
Thermoset membrane may be joined using uncured tape or proprietary adhesive.
(6) Edge Flashing
Proprietary.
(7) Membrane Flashing
Installed according to manufacturer's instructions.

2 RELATED WORK BY OTHERS

(A) Acceptable Deck
(B) Fascia
Optional.
(C) Wood Blocking

NOTE: See the Standard for additional requirements.