Difference between revisions of "EPDM Details:D2.7.6-4 Curbs & Sleepers (Mechanical Opening)"
Difference between revisions of "EPDM Details:D2.7.6-4 Curbs & Sleepers (Mechanical Opening)"
(One intermediate revision by the same user not shown) | |||
Line 13: | Line 13: | ||
<div class="col-md-6"> | <div class="col-md-6"> | ||
=== WORK INCLUDED === | === WORK INCLUDED === | ||
− | ;1) [[RoofStar Guarantee Standards for EPDM Roof | + | ;1) [[RoofStar Guarantee Standards for EPDM Roof Assemblies#EPDMSUBSTRATES|'''Gypsum Deck Overlay''']]: May be required depending on insulation thickness or when required as a thermal barrier by design authority. |
− | ;(2) [[RoofStar Guarantee Standards for EPDM Roof | + | ;(2) [[RoofStar Guarantee Standards for EPDM Roof Assemblies#EPDMVAPOUR|'''Vapour Retarder''']]: If required by design authority. |
− | ;(3) [[RoofStar Guarantee Standards for EPDM Roof | + | ;(3) [[RoofStar Guarantee Standards for EPDM Roof Assemblies#EPDMINSULATION|'''Insulation''']]: Mechanically attached. Installed according to ''RoofStar Guarantee Standards''. See available insulation products in the [[Roof Deck Insulation|'''Accepted Materials''']] section of this Manual. |
− | ;(4) [[RoofStar Guarantee Standards for EPDM Roof | + | ;(4) [[RoofStar Guarantee Standards for EPDM Roof Assemblies#EPDMMEMBRANE|'''Single-ply Membrane''']]: Installed according to manufacturer's instructions and ''RoofStar Guarantee Standards''. |
− | ;(5) [[RoofStar Guarantee Standards for EPDM Roof | + | ;(5) [[RoofStar Guarantee Standards for EPDM Roof Assemblies#EPDMSTRIPPING|'''Membrane Flashing''']]: Adhered according to manufacturer's printed specifications using proprietary adhesive. Thermoset membrane may be joined using uncured tape or proprietary adhesive. |
− | ;(6) [[RoofStar Guarantee Standards for EPDM Roof | + | ;(6) [[RoofStar Guarantee Standards for EPDM Roof Assemblies#METALCAP-EPDM|'''Metal Base Flashing''']]: Mechanically fasten, standing seam at corners. Full width base flashing optional on flexible membranes. Partial skirt flashing minimum 75 mm (3") required on mechanical curbs that require flashing under metal flange. |
<hr> | <hr> | ||
=== RELATED WORK BY OTHERS === | === RELATED WORK BY OTHERS === | ||
− | ;(A) [[RoofStar Guarantee Standards for EPDM Roof | + | ;(A) [[RoofStar Guarantee Standards for EPDM Roof Assemblies#EPDMDECKS|'''Acceptable Deck''']] |
− | ;(B) [[RoofStar Guarantee Standards for EPDM Roof | + | ;(B) [[RoofStar Guarantee Standards for EPDM Roof Assemblies#EPDMVAPOUR|'''Vapour Retarder''']] |
− | ;(C) [[RoofStar Guarantee Standards for EPDM Roof | + | ;(C) [[RoofStar Guarantee Standards for EPDM Roof Assemblies#EPDMCURB|'''Mechanical Curb''']]: Minimum 200 mm (8") and maximum 300 mm (12") above finished roof surface. |
;(D) '''Rigid Insulation''' | ;(D) '''Rigid Insulation''' | ||
</div><!-- COL-6-MD --> | </div><!-- COL-6-MD --> | ||
Line 32: | Line 32: | ||
'''NOTE''': Refer to '''''RoofStar Guarantee Standards''''' for additional requirements. | '''NOTE''': Refer to '''''RoofStar Guarantee Standards''''' for additional requirements. | ||
− | |||
<hr> | <hr> | ||
− | + | [[RoofStar Guarantee Standards for EPDM Roof Assemblies|<i class="fa fa-chevron-circle-left fa" ></i> RoofStar Guarantee Standards for EPDM Roof Assemblies]] | |
− | [[ | ||
[[EPDM (Thermoset Membranes) Construction Details|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''EPDM Construction Details'']] | [[EPDM (Thermoset Membranes) Construction Details|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''EPDM Construction Details'']] | ||
[[Construction Details|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''Construction Details'']] | [[Construction Details|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''Construction Details'']] |
Latest revision as of 16:48, 23 October 2017
RoofStar Guarantee Standards are blue-linked |
EPDM Details
1 WORK INCLUDED
- 1) Gypsum Deck Overlay
- May be required depending on insulation thickness or when required as a thermal barrier by design authority.
- (2) Vapour Retarder
- If required by design authority.
- (3) Insulation
- Mechanically attached. Installed according to RoofStar Guarantee Standards. See available insulation products in the Accepted Materials section of this Manual.
- (4) Single-ply Membrane
- Installed according to manufacturer's instructions and RoofStar Guarantee Standards.
- (5) Membrane Flashing
- Adhered according to manufacturer's printed specifications using proprietary adhesive. Thermoset membrane may be joined using uncured tape or proprietary adhesive.
- (6) Metal Base Flashing
- Mechanically fasten, standing seam at corners. Full width base flashing optional on flexible membranes. Partial skirt flashing minimum 75 mm (3") required on mechanical curbs that require flashing under metal flange.
2 RELATED WORK BY OTHERS
- (A) Acceptable Deck
- (B) Vapour Retarder
- (C) Mechanical Curb
- Minimum 200 mm (8") and maximum 300 mm (12") above finished roof surface.
- (D) Rigid Insulation
NOTE: Refer to RoofStar Guarantee Standards for additional requirements.
RoofStar Guarantee Standards for EPDM Roof Assemblies