LMF Metal Cap Flashing (inside corner)

Jump to: navigation, search

LMF Metal Cap Flashing (inside corner)



Division D - Construction Details


LMF | Metal Cap Flashing (inside corner)

Notice to Reader
Images used in a Construction Detail are representative and not prescriptive. Nor are they necessarily drawn to scale. Rather, they are provided to visually convey the requirements of the Standard they represent. Unless otherwise required by the Standard, dimensions, the selection of materials and their application remains the responsibility of the Design Authority.

The full text of the referenced requirements can be read in any Standard and may be read by using the blue hyperlinks
Metal Flashing Details

10.2.1.1.jpg

1 WORK INCLUDED

(1) Metal Cant Flashing
Standing seam required at corners of cant. Refer to Part 13 in the related Standard.
(2) Metal Base Flashing
Vertical runs over 100 mm (4") require standing seam or S-lock corners. Refer to Part 13 in the related Standard. Cross-breaks and cladding-type fasteners are optional.
(3) Double S-Lock Corner
Fastened through concealed flanges.
(4) Metal Cap Flashing – Interior Face
Fastened with continuous clips or cladding screws evenly spaced between seams. Over 100 mm (4") width requires standing seam.
(5) Seam
Lap seam at an inside corner is acceptable if vertical distance is not more than 100 mm (4").
(6) Metal Cap Flashing – Top Face
Over 100 mm (4") width must provide positive slope to roof area.
(7) Standing Seam
(8) Metal Cap Flashing – Outside Face
Corner standing seams may be folded flat on outside face only. Fasten with continuous concealed clip-type fasteners or cladding screws evenly spaced between seams.

2 RELATED WORK BY OTHERS

(A) Acceptable Parapet
(B) Sloped Blocking
Required over minimum 100 mm (4") parapet width.

NOTE: See the related Standard for additional requirements.