;(2) '''Flashing Flange''': minimum 100 mm (4") flange set in coating of compatible sealant.
 
;(2) '''Flashing Flange''': minimum 100 mm (4") flange set in coating of compatible sealant.
 
;(3) [[RoofStar Guarantee Standards for SBS Roof Systems#SBSBASE|'''Primary Membrane''']] and [[RoofStar Guarantee Standards for SBS Roof Systems#SBSSTRIPFLASH|'''Membrane Flashing''']].
 
;(3) [[RoofStar Guarantee Standards for SBS Roof Systems#SBSBASE|'''Primary Membrane''']] and [[RoofStar Guarantee Standards for SBS Roof Systems#SBSSTRIPFLASH|'''Membrane Flashing''']].
;(4) [[RoofStar Guarantee St.andards for SBS Roof Systems#SBSPMRA|'''Protected Membrane Roof Assembly''']]: Flashing to extend a minimum 200 mm (8") above finished roof surface (pavers, ballast, or walkways)
+
;(4) [[RoofStar Guarantee Standards for SBS Roof Systems#SBSPMRA|'''Protected Membrane Roof Assembly''']]: Flashing to extend a minimum 200 mm (8") above finished roof surface (pavers, ballast, or walkways)
 
;(5) [[RoofStar Guarantee Standards for SBS Roof Systems#SBS-STRIPPING|'''Conventional Roof Assembly''']]: Flashing to extend a minimum 200 mm (8") above finished roof surface.
 
;(5) [[RoofStar Guarantee Standards for SBS Roof Systems#SBS-STRIPPING|'''Conventional Roof Assembly''']]: Flashing to extend a minimum 200 mm (8") above finished roof surface.
 
;(6) [[RoofStar Guarantee Standards for SBS Roof Systems#SBSINSULATION|'''Insulation''']]: See available insulation products in the [[Roof Deck Insulation|'''Accepted Materials''']] section of this Manual.
 
;(6) [[RoofStar Guarantee Standards for SBS Roof Systems#SBSINSULATION|'''Insulation''']]: See available insulation products in the [[Roof Deck Insulation|'''Accepted Materials''']] section of this Manual.

Revision as of 21:40, 5 August 2016

10.3.7.1.jpg

1 WORK INCLUDED

(1) Flashing
0.08 mm (0.032", 20 gauge) Aluminum or 0.56 mm (16 oz) copper to CSA B272-93 flashing supplied by anchor manufacturer with flanges sealed by roofer.
(2) Flashing Flange
minimum 100 mm (4") flange set in coating of compatible sealant.
(3) Primary Membrane and Membrane Flashing.
(4) Protected Membrane Roof Assembly
Flashing to extend a minimum 200 mm (8") above finished roof surface (pavers, ballast, or walkways)
(5) Conventional Roof Assembly
Flashing to extend a minimum 200 mm (8") above finished roof surface.
(6) Insulation
See available insulation products in the Accepted Materials section of this Manual.

2 WORK BY OTHERS

(A) Acceptable Deck
Concrete slab shown, see anchor manufacturer's attachment details for other deck types.
(B) Roof Anchor
to CSA Z91-M90
(C) Anchor Eye
to CSA Z91-M90
(D) Water Tight Cap


NOTE: Refer to RoofStar Guarantee Standards for additional requirements.