<big><big>Division D - Construction Details</big></big>
 
<hr>
 
<hr>
{| class="wikitable" | style="color: black; background-color: orange; width: 100%;text-align:center"
+
<big><big><big><big><big>SBS | Parapet-Wall Connection ([[SBS_Roof_Systems_Standard#10.3.4.1._Parapets | Article 10.3.4.1.]])</big></big></big></big></big>
| colspan="2"  | <big>'''''Notice to Reader'''''</big>
+
{{Template:Construction Details Header}}
|-
 
| style="color: black; background-color: #ffffcc; width: 100%;text-align:center" | Images used in a Construction Detail are representative and not prescriptive. Nor are they necessarily drawn to scale. Rather, they are provided to visually convey the requirements of the Standard they represent. Unless otherwise required by the Standard, dimensions, the selection of materials and their application remains the responsibility of the ''Design Authority''.<br><br>The full text of the referenced requirements in the [[SBS Roof Systems Standard | '''Standard''']] may be read by using the <span style="color:#6495ed">'''blue hyperlinks'''</span>
 
|}
 
 
<div class="panel panel-success">
 
<div class="panel panel-success">
 
<div class="panel-heading"><big>'''SBS Details'''</big></div>
 
<div class="panel-heading"><big>'''SBS Details'''</big></div>
Line 24: Line 26:
 
=== WORK INCLUDED ===
 
=== WORK INCLUDED ===
  
;(1) [[SBS Roof Systems Standard#SBSSUBSTRATES|'''Supporting Deck Overlay''']]: If required by design authority.
+
;(1) [[SBS Roof Systems Standard#PART_5|'''Supporting Deck Overlay''']]: If required by design authority.
;(2) [[SBS Roof Systems Standard#SBSAIRVAPOUR|'''Air or Vapour Control Layers''']]:If required by design authority.
+
;(2) [[SBS Roof Systems Standard#PART_6|'''Air or Vapour Control Layers''']]:If required by design authority.
;(3) [[SBS Roof Systems Standard#SBSINSULATION|'''Insulation''']]:
+
;(3) [[SBS Roof Systems Standard#PART_7|'''Insulation''']]:
 
:See list of '''[[Division C: Accepted Materials|Accepted Materials]]'''.
 
:See list of '''[[Division C: Accepted Materials|Accepted Materials]]'''.
;(4) [[SBS Roof Systems Standard#SBSINSULATIONOVERLAY|'''Insulation Overlay''']]:
+
;(4) [[SBS Roof Systems Standard#PART_8|'''Insulation Overlay''']]:
 
:As required.
 
:As required.
;(5) [[SBS Roof Systems Standard#SBSBASE|'''Primary Membrane''']] and [[RoofStar Guarantee Standards for SBS Modified Bitumen Roof Assemblies#SBSPROTECTION| '''Membrane Protection''']]:
+
;(5) [[SBS Roof Systems Standard#PART_9|'''Primary Membrane''']] and [[RoofStar Guarantee Standards for SBS Modified Bitumen Roof Assemblies#SBSPROTECTION| '''Membrane Protection''']]:
;(6) [[SBS Roof Systems Standard#SBS-STRIPPING|'''Membrane Flashing (attachment & termination)''']]: Mechanically fasten at terminations.  At least one ply must extend over outside edge.
+
;(6) [[SBS Roof Systems Standard#PART_10|'''Membrane Flashing (attachment & termination)''']]: Mechanically fasten at terminations.  At least one ply must extend over outside edge.
;(7) [[SBS Roof Systems Standard#METALCAP-SBS|'''Metal Base Flashing''']]: Optional on flexible membrane systems. Required on assemblies using gravel ballast filter mats.
+
;(7) [[SBS Roof Systems Standard#PART_13|'''Metal Base Flashing''']]: Optional on flexible membrane systems. Required on assemblies using gravel ballast filter mats.
;(8) [[SBS Roof Systems Standard#METALCAP-SBS|'''Metal Cap Flashing''']]: Must overlap exterior wall finish.  Fasten with  concealed clip-type fasteners  <b>or</b> cladding screws evenly spaced between seams.
+
;(8) [[SBS Roof Systems Standard#PART_13|'''Metal Cap Flashing''']]: Must overlap exterior wall finish.  Fasten with  concealed clip-type fasteners  <b>or</b> cladding screws evenly spaced between seams.
;(9) [[SBS Roof Systems Standard#SBSWALLTIEIN|'''Wall Tie-in''']]: Minimum 2 mm (0.078") self-adhered  modified bitumen or flexible membrane manufacturers approved detail.
+
;(9) [[SBS Roof Systems Standard#PART_10|'''Wall Tie-in''']]: Minimum 2 mm (0.078") self-adhered  modified bitumen or flexible membrane manufacturers approved detail.
;(10)[[SBS Roof Systems Standard#METALCAP-SBS|'''Metal Counter-flashing''']]:
+
;(10)[[SBS Roof Systems Standard#PART_13|'''Metal Counter-flashing''']]:
  
 
<hr>
 
<hr>
Line 41: Line 43:
 
=== RELATED WORK BY OTHERS ===
 
=== RELATED WORK BY OTHERS ===
  
;(A) [[SBS Roof Systems Standard#SBSDECKS|'''Acceptable Supporting Deck Structure''']]
+
;(A) [[SBS Roof Systems Standard#PART_2|'''Acceptable Supporting Deck Structure''']]
;(B) [[SBS Roof Systems Standard#SBSAIRVAPOUR|'''Air and Vapour Control Layer Seal''']]
+
;(B) [[SBS Roof Systems Standard#PART_6|'''Air and Vapour Control Layer Seal''']]
;(C) [[SBS Roof Systems Standard#SBSWALLSUB|'''Acceptable Wall Surface''']]
+
;(C) [[SBS Roof Systems Standard#PART_2|'''Acceptable Wall Surface''']]
;(D) [[SBS Roof Systems Standard#SBSWOODBLOCKING|'''Wood Blocking''']]  
+
;(D) [[SBS Roof Systems Standard#PART_10|'''Wood Blocking''']]  
;(E) [[SBS Roof Systems Standard#SBSSLOPEDWOODBLOCKING|'''Sloped Wood Blocking''']]
+
;(E) [[SBS Roof Systems Standard#PART_10|'''Sloped Wood Blocking''']]
 
:Required over 100 mm (4") parapet width.
 
:Required over 100 mm (4") parapet width.
;(F) [[SBS Roof Systems Standard#SBS-STRIPPING|'''Wall Sheathing Membrane''']]: Minimum 1 mm (0.040") self-adhered modified bitumen.
+
;(F) [[SBS Roof Systems Standard#PART_10|'''Wall Sheathing Membrane''']]: Minimum 1 mm (0.040") self-adhered modified bitumen.
 
;(G) <b>Wall Cladding</b>
 
;(G) <b>Wall Cladding</b>
 
</div><!-- COL-6-MD -->
 
</div><!-- COL-6-MD -->

Revision as of 18:53, 27 June 2022



Division D - Construction Details


SBS | Parapet-Wall Connection ( Article 10.3.4.1.)

Notice to Reader
Images used in a Construction Detail are representative and not prescriptive, and are not necessarily drawn to scale. They are intended to support the related Standard (Ref. Division A, Article 2.2.1.2.).

The reader may link to the related Article in the detail title, or link to the Standard as it relates to a specific element in the detail. All hyperlinks are displayed blue text.

SBS Details

10.3.1.4.jpg

Click below for a printable version of this page.
Print Sheet

1 WORK INCLUDED

(1) Supporting Deck Overlay
If required by design authority.
(2) Air or Vapour Control Layers
If required by design authority.
(3) Insulation
See list of Accepted Materials.
(4) Insulation Overlay
As required.
(5) Primary Membrane and Membrane Protection
(6) Membrane Flashing (attachment & termination)
Mechanically fasten at terminations. At least one ply must extend over outside edge.
(7) Metal Base Flashing
Optional on flexible membrane systems. Required on assemblies using gravel ballast filter mats.
(8) Metal Cap Flashing
Must overlap exterior wall finish. Fasten with concealed clip-type fasteners or cladding screws evenly spaced between seams.
(9) Wall Tie-in
Minimum 2 mm (0.078") self-adhered modified bitumen or flexible membrane manufacturers approved detail.
(10)Metal Counter-flashing

2 RELATED WORK BY OTHERS

(A) Acceptable Supporting Deck Structure
(B) Air and Vapour Control Layer Seal
(C) Acceptable Wall Surface
(D) Wood Blocking
(E) Sloped Wood Blocking
Required over 100 mm (4") parapet width.
(F) Wall Sheathing Membrane
Minimum 1 mm (0.040") self-adhered modified bitumen.
(G) Wall Cladding

NOTE: See the Standard for additional requirements.