Difference between revisions of "WP Details:F1.7.10 (Walls - Double Surface Reglet Flashing)"

Jump to: navigation, search

Difference between revisions of "WP Details:F1.7.10 (Walls - Double Surface Reglet Flashing)"

Line 14: Line 14:
 
=== WORK INCLUDED ===
 
=== WORK INCLUDED ===
  
(1) <b>Primary Waterproofing Membrane: </b>Fully adhered to acceptable substrates (concrete slab depicted), installed as per [[RoofStar Guarantee Standards for Waterproofing|'''RoofStar Guarantee Standards for Waterproofing Plazas, Promenades & Terraces''']] and Membrane Manufacturer's installation specifications.  
+
(1) [http://{{SERVERNAME}}/index.php?title=RoofStar_Guarantee_Standards_for_Waterproofing#WPMEMBRANE '''Primary Waterproofing Membrane''']: Fully adhered to acceptable substrates (concrete slab depicted), installed as per [[RoofStar Guarantee Standards for Waterproofing|'''RoofStar Guarantee Standards for Waterproofing Plazas, Promenades & Terraces''']] and Membrane Manufacturer's installation specifications.  
  
(2) <b> Membrane Flashing: </b>Carried up wall minimum 200 mm (8") above deck surface and minimum 100 mm (4") above top of finished permeable wearing course or overburden.
+
(2) [http://{{SERVERNAME}}/index.php?title=RoofStar_Guarantee_Standards_for_Waterproofing#WPSTRIPPING  '''Membrane Flashing''']: </b>Carried up wall minimum 200 mm (8") above deck surface and minimum 100 mm (4") above top of finished permeable wearing course or overburden.
  
 
(3) <b> Primary Surface Reglet: </b>Install as detailed with steel channel and concrete pins.  Adhered membrane termination held in place by clamping pressure and pins.  
 
(3) <b> Primary Surface Reglet: </b>Install as detailed with steel channel and concrete pins.  Adhered membrane termination held in place by clamping pressure and pins.  

Revision as of 18:00, 12 October 2016

RoofStar Guarantee Standards are blue-linked
Waterproofing Details for Plazas, Promenades and Terraces

9.6.10.jpg

1 WORK INCLUDED

(1) Primary Waterproofing Membrane: Fully adhered to acceptable substrates (concrete slab depicted), installed as per RoofStar Guarantee Standards for Waterproofing Plazas, Promenades & Terraces and Membrane Manufacturer's installation specifications.

(2) Membrane Flashing: Carried up wall minimum 200 mm (8") above deck surface and minimum 100 mm (4") above top of finished permeable wearing course or overburden.

(3) Primary Surface Reglet: Install as detailed with steel channel and concrete pins. Adhered membrane termination held in place by clamping pressure and pins.

(4) Fasteners: Suitable expanding type concrete pins.

(5) Clamping Bar: Steel channel with elongated holes to permit expansion/contraction, pinned into concrete at maximum 400 mm (16") o/c. Bar dimensions to be a minimum 38 mm (1 ½") wide x 12 mm (1/2") thick C-channel, formed from a minimum 22 gauge galvanized or pre-finished steel.

(6) Caulking: Polyurethane sealant, fill to top of the flashing and crown to promote drainage.(7) Surface Reglet Counter Flashing: To cover lower reglet assembly, pinned directly without a clamping bar at maximum 300 mm (12") o/c. (Interlocking hooked type assembly optional)

2 RELATED WORK BY OTHERS

(A) Concrete, Stone or Steel Wall Finish: Must be dry, smooth and primed for membrane flashing to be adhered directly. (Plywood or fibre-mat reinforced cement board may be required).

NOTE: * AVOID SURFACE REGLET: (wherever possible) Use preformed or saw cut REGLETS:

NOTE: Refer to RoofStar Guarantee Standards for additional requirements.




Back to Waterproofing Application

Back to Waterproofing Construction Details

Back to Construction Details