=== WORK INCLUDED === | === WORK INCLUDED === | ||
− | (1) | + | (1) [http://{{SERVERNAME}}/index.php?title=RoofStar_Guarantee_Standards_for_Waterproofing#WPMEMBRANE '''Primary Waterproofing Membrane''']: Fully adhered to acceptable substrates (concrete slab depicted), installed as per [[RoofStar Guarantee Standards for Waterproofing|'''RoofStar Guarantee Standards for Waterproofing Plazas, Promenades & Terraces''']] and Membrane Manufacturer's installation specifications. |
− | (2) | + | (2) [http://{{SERVERNAME}}/index.php?title=RoofStar_Guarantee_Standards_for_Waterproofing#WPSTRIPPING '''Membrane Flashing''']: </b>Carried up wall minimum 200 mm (8") above deck surface and minimum 100 mm (4") above top of finished permeable wearing course or overburden. |
(3) <b> Primary Surface Reglet: </b>Install as detailed with steel channel and concrete pins. Adhered membrane termination held in place by clamping pressure and pins. | (3) <b> Primary Surface Reglet: </b>Install as detailed with steel channel and concrete pins. Adhered membrane termination held in place by clamping pressure and pins. |
Revision as of 18:00, 12 October 2016
RoofStar Guarantee Standards are blue-linked |
1 WORK INCLUDED
(1) Primary Waterproofing Membrane: Fully adhered to acceptable substrates (concrete slab depicted), installed as per RoofStar Guarantee Standards for Waterproofing Plazas, Promenades & Terraces and Membrane Manufacturer's installation specifications.
(2) Membrane Flashing: Carried up wall minimum 200 mm (8") above deck surface and minimum 100 mm (4") above top of finished permeable wearing course or overburden.
(3) Primary Surface Reglet: Install as detailed with steel channel and concrete pins. Adhered membrane termination held in place by clamping pressure and pins.
(4) Fasteners: Suitable expanding type concrete pins.
(5) Clamping Bar: Steel channel with elongated holes to permit expansion/contraction, pinned into concrete at maximum 400 mm (16") o/c. Bar dimensions to be a minimum 38 mm (1 ½") wide x 12 mm (1/2") thick C-channel, formed from a minimum 22 gauge galvanized or pre-finished steel.
(6) Caulking: Polyurethane sealant, fill to top of the flashing and crown to promote drainage.(7) Surface Reglet Counter Flashing: To cover lower reglet assembly, pinned directly without a clamping bar at maximum 300 mm (12") o/c. (Interlocking hooked type assembly optional)
2 RELATED WORK BY OTHERS
(A) Concrete, Stone or Steel Wall Finish: Must be dry, smooth and primed for membrane flashing to be adhered directly. (Plywood or fibre-mat reinforced cement board may be required).
NOTE: * AVOID SURFACE REGLET: (wherever possible) Use preformed or saw cut REGLETS:
NOTE: Refer to RoofStar Guarantee Standards for additional requirements.
Back to Waterproofing Application