==== WORK INCLUDED ====
+
<big><big>Division D - Construction Details</big></big>
 
+
<hr>
(1) <b>Deck Overlay Substrate Boards</b>: two layers of fibre-mat reinforced cement board, minimum thickness 9.5 mm (3/8"), conforming to ASTM C1325-04 <b>or </b>gypsum board with fibreglass facer and silicone treated core, minimum thickness 12 mm  (1/2"), conforming to ASTM E 661
+
<big><big><big><big><big>WP Details:F1.7.4 (Steel Deck - Substrate Overlay Board)</big></big></big></big></big>
 
+
{| class="wikitable" | style="color: black; background-color: orange; width: 100%;text-align:center"
(2)<b> Primary Waterproofing Membrane: </b>Fully adhered<b> </b>to acceptable substrates.
+
| colspan="2"  | <big>'''''Notice to Reader'''''</big>
 
+
|-
(3) <b>Membrane Primer or Adhesive: </b>proprietary primer or adhesive, application and quantities as directed by membrane manufacturers published application specifications.
+
| style="color: black; background-color: #ffffcc; width: 100%;text-align:center" | Images used in a Construction Detail are representative and not prescriptive.  Nor are they necessarily drawn to scale. Rather, they are provided to visually convey the requirements of the Standard they represent. Unless otherwise required by the Standard, dimensions, the selection of materials and their application remains the responsibility of the ''Design Authority''.<br><br>The full text of the referenced requirements in the [[Grade-level Waterproofing Standard | '''Standard''']] may be read by using the <span style="color:#6495ed">'''blue hyperlinks'''</span>
 
+
|}
(4) <b>Membrane flashing </b>(stripping): carried up wall minimum 200 mm (8") above deck surface a minimum of 100mm (4") above top surface of waterproofing assembly. Typical low outside parapet wall depicted, membrane carried over top of wall and down exterior face minimum of 50mm (2").
+
<div class="panel panel-success">
 
+
<div class="panel-heading"><big>'''Waterproofing Details for Plazas, Promenades and Terraces'''</big></div>
(5) <b>Insulation: </b>Optional: Extruded, Expanded Polystyrene, Type 4, CAN/ULC-S701-97, compressive strength of 240 kpa (35 psi).
+
<div class="panel-body">
 
+
<div class="col-md-6">
(6) <b>Metal Base Flashing:</b> Required on all waterproofing assemblies. Flashing lengths joined by use of S-locks or standing seam joints.
+
<div style="text-align:center; vertical-align:center">
(7) <b>Metal Cap or Coping Flashing:</b> Must overlap exterior wall finish. See <i>RGC Guarantee Standard A6.9. </i>Fasten with continuous concealed clip-type fasteners <b>or</b> cladding screws evenly spaced between seams. See <i>RGC Guarantee Standard A6.10</i>  
+
[[File:9.6.4.jpg| link=http://rpm.rcabc.org/images/9/96/9.6.4.jpg | class=img-responsive]]
 
+
</div>
(8) <b>Drainage Medium</b>: Proprietary (purpose-made) drainage board designed to provide secondary drainage below poured concrete wearing slabs and unit masonry (pavers, brick or stone) set in mortar beds.
+
</div><!-- COL-MD-6 -->
 
 
  
==== WORK BY OTHERS ====
+
<div class="col-md-6">
 +
=== WORK INCLUDED ===
  
(A) <b>Acceptable Deck</b>: Steel deck depicted.  
+
;(1) [[Grade-level Waterproofing Standard#WPSTEEL | '''Deck Overlay Substrate Boards''']]: two layers of fibre-mat reinforced cement board, minimum thickness 9.5 mm (3/8"), conforming to ASTM C1325-04 <b>or </b>gypsum board with fibreglass facer and silicone treated core, minimum thickness 12 mm  (1/2"), conforming to ASTM E 661
 +
;(2) [[Grade-level Waterproofing Standard#WPMEMBRANE | '''Primary Waterproofing Membrane''']]: Fully adhered<b> </b>to acceptable substrates.
 +
;(3) Membrane Primer or Adhesive: Proprietary primer or adhesive, application and quantities as directed by membrane manufacturers published application specifications.
 +
;(4) [[Grade-level Waterproofing Standard#WPSTRIPPING | '''Membrane flashing (stripping)''']]: Carried up wall minimum 200 mm (8") above deck surface a minimum of 100mm (4") above top surface of waterproofing assembly. Typical low outside parapet wall depicted, membrane carried over top of wall and down exterior face minimum of 50mm (2").
 +
;(5) [[Grade-level Waterproofing Standard#WPINSULATION | '''Insulation''']]: Optional: Extruded, Expanded Polystyrene, Type 4, CAN/ULC-S701-97, compressive strength of 240 kpa (35 psi).
 +
;(6) [[Grade-level Waterproofing Standard#WPMETAL | '''Metal Base Flashing''']]: Required on all waterproofing assemblies. Flashing lengths joined by use of S-locks or standing seam joints.
 +
;(7) [[Grade-level Waterproofing Standard#WPMETAL | '''Metal Cap Flashing''']]: Must overlap exterior wall finish. See [[Grade-level Waterproofing Standard#WPMETAL|'''15.1''']] for '''''RoofStar Guarantee Standards''''' applicable to base metal flashing.  Fasten with continuous concealed clip-type fasteners <b>or</b> cladding screws evenly spaced between seams. See [[Grade-level Waterproofing Standard#WPFASTENER| '''16.3 Attachment''']].
 +
;(8) [[Grade-level Waterproofing Standard#WPDRAINAGE | '''Drainage Medium''']]: Proprietary (purpose-made) drainage board designed to provide secondary drainage below poured concrete wearing slabs and unit masonry (pavers, brick or stone) set in mortar beds.
  
(B) <b>Wall Finish</b>: Concrete depicted.
+
=== WORK BY OTHERS ===
 +
;(A) [[Grade-level Waterproofing Standard#WPDECK | '''Acceptable Deck''']]: Steel deck depicted.
 +
;(B) Wall Finish: Concrete depicted.
 +
</div><!-- COL-6-MD -->
 +
</div><!-- PANEL BODY -->
 +
</div><!-- PANEL -->
  
<b><i>NOTE: </i> Refer to<i> RGC Guarantee Standards E </i>for additional requirements.</b>
+
'''NOTE''': See the [[Grade-level Waterproofing Standard | '''Standard''']] for additional requirements.
  
 
<hr>
 
<hr>
  
 +
[[Grade-level Waterproofing System Details|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''Grade-level Waterproofing Construction Details'']]
  
 +
[[Main Page | <i class="fa fa-home fa"></i> Home]]
  
[[Section:F. Application: Waterproofing Plazas, Promenades and Terraces|<i class="fa fa-chevron-circle-left fa-2x" ></i> Back to ''Waterproofing Application'']]
+
{{Tempate:RPM Page Footer with Copyright and Current Date}}
 
 
[[Waterproofing Details|<i class="fa fa-chevron-circle-left fa-2x" ></i> Back to ''Waterproofing Construction Details'']]
 
 
 
[[Section:G. Construction Details|<i class="fa fa-chevron-circle-left fa-2x" ></i> Back to ''Construction Details'']]
 

Latest revision as of 21:15, 7 September 2021



Division D - Construction Details


WP Details:F1.7.4 (Steel Deck - Substrate Overlay Board)

Notice to Reader
Images used in a Construction Detail are representative and not prescriptive. Nor are they necessarily drawn to scale. Rather, they are provided to visually convey the requirements of the Standard they represent. Unless otherwise required by the Standard, dimensions, the selection of materials and their application remains the responsibility of the Design Authority.

The full text of the referenced requirements in the Standard may be read by using the blue hyperlinks
Waterproofing Details for Plazas, Promenades and Terraces

9.6.4.jpg

1 WORK INCLUDED

(1) Deck Overlay Substrate Boards
two layers of fibre-mat reinforced cement board, minimum thickness 9.5 mm (3/8"), conforming to ASTM C1325-04 or gypsum board with fibreglass facer and silicone treated core, minimum thickness 12 mm (1/2"), conforming to ASTM E 661
(2) Primary Waterproofing Membrane
Fully adhered to acceptable substrates.
(3) Membrane Primer or Adhesive
Proprietary primer or adhesive, application and quantities as directed by membrane manufacturers published application specifications.
(4) Membrane flashing (stripping)
Carried up wall minimum 200 mm (8") above deck surface a minimum of 100mm (4") above top surface of waterproofing assembly. Typical low outside parapet wall depicted, membrane carried over top of wall and down exterior face minimum of 50mm (2").
(5) Insulation
Optional: Extruded, Expanded Polystyrene, Type 4, CAN/ULC-S701-97, compressive strength of 240 kpa (35 psi).
(6) Metal Base Flashing
Required on all waterproofing assemblies. Flashing lengths joined by use of S-locks or standing seam joints.
(7) Metal Cap Flashing
Must overlap exterior wall finish. See 15.1 for RoofStar Guarantee Standards applicable to base metal flashing. Fasten with continuous concealed clip-type fasteners or cladding screws evenly spaced between seams. See 16.3 Attachment.
(8) Drainage Medium
Proprietary (purpose-made) drainage board designed to provide secondary drainage below poured concrete wearing slabs and unit masonry (pavers, brick or stone) set in mortar beds.

2 WORK BY OTHERS

(A) Acceptable Deck
Steel deck depicted.
(B) Wall Finish
Concrete depicted.

NOTE: See the Standard for additional requirements.


Back to Grade-level Waterproofing Construction Details