Difference between revisions of "WP Details:F1.7.4 (Steel Deck - Substrate Overlay Board)"

Jump to: navigation, search

Difference between revisions of "WP Details:F1.7.4 (Steel Deck - Substrate Overlay Board)"

Line 25: Line 25:
  
 
(6) <b>Metal Base Flashing:</b> Required on all waterproofing assemblies. Flashing lengths joined by use of S-locks or standing seam joints.
 
(6) <b>Metal Base Flashing:</b> Required on all waterproofing assemblies. Flashing lengths joined by use of S-locks or standing seam joints.
(7) <b>Metal Cap or Coping Flashing:</b> Must overlap exterior wall finish. See the RoofStar Guarantee Standards for [[RoofStar Guarantee Standards for SBS Roof Systems#SBSMETALFLASH|'''base metal flashing''']].  Fasten with continuous concealed clip-type fasteners <b>or</b> cladding screws evenly spaced between seams. See R''oofStar Guarantee Standards (SBS Roof Systems)'' [[RoofStar Guarantee Standards for SBS Roof Systems#SBSMETALFASTENER| '''12.3 Attachment''']] for cross-reference.
+
(7) <b>Metal Cap or Coping Flashing:</b> Must overlap exterior wall finish. See [[RoofStar Guarantee Standards for Waterproofing#WPMETAL|'''15.1''']] for RoofStar Guarantee Standards applicable to base metal flashing.  Fasten with continuous concealed clip-type fasteners <b>or</b> cladding screws evenly spaced between seams. See [[RoofStar Guarantee Standards for Waterproofing#WPFASTENER| '''15.3 Attachment''']].
  
 
(8) <b>Drainage Medium</b>: Proprietary (purpose-made) drainage board designed to provide secondary drainage below poured concrete wearing slabs and unit masonry (pavers, brick or stone) set in mortar beds.  
 
(8) <b>Drainage Medium</b>: Proprietary (purpose-made) drainage board designed to provide secondary drainage below poured concrete wearing slabs and unit masonry (pavers, brick or stone) set in mortar beds.  

Revision as of 15:34, 1 September 2016

RoofStar Guarantee Standards are blue-linked
Waterproofing Details for Plazas, Promenades and Terraces

9.6.4.jpg

1 WORK INCLUDED

(1) Deck Overlay Substrate Boards: two layers of fibre-mat reinforced cement board, minimum thickness 9.5 mm (3/8"), conforming to ASTM C1325-04 or gypsum board with fibreglass facer and silicone treated core, minimum thickness 12 mm (1/2"), conforming to ASTM E 661

(2) Primary Waterproofing Membrane: Fully adhered to acceptable substrates.

(3) Membrane Primer or Adhesive: proprietary primer or adhesive, application and quantities as directed by membrane manufacturers published application specifications.

(4) Membrane flashing (stripping): carried up wall minimum 200 mm (8") above deck surface a minimum of 100mm (4") above top surface of waterproofing assembly. Typical low outside parapet wall depicted, membrane carried over top of wall and down exterior face minimum of 50mm (2").

(5) Insulation: Optional: Extruded, Expanded Polystyrene, Type 4, CAN/ULC-S701-97, compressive strength of 240 kpa (35 psi).

(6) Metal Base Flashing: Required on all waterproofing assemblies. Flashing lengths joined by use of S-locks or standing seam joints. (7) Metal Cap or Coping Flashing: Must overlap exterior wall finish. See 15.1 for RoofStar Guarantee Standards applicable to base metal flashing. Fasten with continuous concealed clip-type fasteners or cladding screws evenly spaced between seams. See 15.3 Attachment.

(8) Drainage Medium: Proprietary (purpose-made) drainage board designed to provide secondary drainage below poured concrete wearing slabs and unit masonry (pavers, brick or stone) set in mortar beds.


2 WORK BY OTHERS

(A) Acceptable Deck: Steel deck depicted.

(B) Wall Finish: Concrete depicted.

NOTE: Refer to RoofStar Guarantee Standards for additional requirements.




Back to Waterproofing Application

Back to Waterproofing Construction Details

Back to Construction Details