(1) <b>MEMBRANES:</b> Membranes must be installed to <i>RGC Guarantee Standards</i> and the manufacturer's printed instructions
+
(1) <b>MEMBRANES:</b> Membranes must be installed to <i>'''RoofStar Guarantee Standards'''</i> and the manufacturer's printed instructions
  
 
(2) <b>ADHESION:</b> Membranes must be fully adhered, where exposed, and mechanically fastened at terminations 300 mm (12") o/c
 
(2) <b>ADHESION:</b> Membranes must be fully adhered, where exposed, and mechanically fastened at terminations 300 mm (12") o/c
Line 21: Line 21:
  
 
(4) <b>EAVE PROTECTION:</b> Built-in gutter membranes can be extended to act as an eave protection membrane. Underlay or eave protection membrane must overlap built-in gutter membrane by a minimum of 200 mm (8") and be installed in shingle fashion (not shown for clarity).
 
(4) <b>EAVE PROTECTION:</b> Built-in gutter membranes can be extended to act as an eave protection membrane. Underlay or eave protection membrane must overlap built-in gutter membrane by a minimum of 200 mm (8") and be installed in shingle fashion (not shown for clarity).
 
  
 
=== RELATED WORK BY OTHERS ===
 
=== RELATED WORK BY OTHERS ===

Revision as of 22:23, 11 October 2016

RoofStar Guarantee Standards are blue-linked
Cedar Shakes & Shingles Details

8.3.1.jpg

1 WORK INCLUDED

(1) MEMBRANES: Membranes must be installed to RoofStar Guarantee Standards and the manufacturer's printed instructions

(2) ADHESION: Membranes must be fully adhered, where exposed, and mechanically fastened at terminations 300 mm (12") o/c

(3) HEIGHT: The minimum vertical sealed height above the maximum water level is 150 mm (6"). The membrane run up the slope will vary with roof pitch. Increase height in heavy snow regions.

(4) EAVE PROTECTION: Built-in gutter membranes can be extended to act as an eave protection membrane. Underlay or eave protection membrane must overlap built-in gutter membrane by a minimum of 200 mm (8") and be installed in shingle fashion (not shown for clarity).

2 RELATED WORK BY OTHERS

(A) DIMENSIONS: Dimensions of parapets, cants and water loading of gutters are variable and should be determined by design authority

(B) ACCEPTABLE DECK

NOTE: * Refer to RGC Guarantee Standards for additional requirements.