Difference between revisions of "WP Details:F1.7.9 (Walls - Reglet & Counter-Flashings)"
Difference between revisions of "WP Details:F1.7.9 (Walls - Reglet & Counter-Flashings)"
Line 13: | Line 13: | ||
<div class="col-md-6"> | <div class="col-md-6"> | ||
=== WORK INCLUDED === | === WORK INCLUDED === | ||
− | (1) | + | (1) [http://{{SERVERNAME}}/index.php?title=RoofStar_Guarantee_Standards_for_Waterproofing#WPMEMBRANE '''Primary Waterproofing Membrane''']: Fully adhered to acceptable substrates (concrete slab depicted), installed as per [[RoofStar Guarantee Standards for Waterproofing|'''RoofStar Guarantee Standards for Waterproofing Plazas, Promenades & Terraces''']] and Membrane Manufacturer's installation specifications. |
− | (2) | + | (2) [http://{{SERVERNAME}}/index.php?title=RoofStar_Guarantee_Standards_for_Waterproofing#WPSTRIPPING '''Membrane Flashing (stripping)''']: Carried up walls a minimum 200 mm (8") above membrane surface (Deck) and a minimum of 100mm (4") above top surface of permeable waterproofing wearing surfaces and overburdens. |
(3) <b> Membrane Primer or Adhesive: </b>proprietary primer or adhesive, application and quantities as directed by membrane manufacturers published application specifications. | (3) <b> Membrane Primer or Adhesive: </b>proprietary primer or adhesive, application and quantities as directed by membrane manufacturers published application specifications. | ||
− | (4) | + | (4) [http://{{SERVERNAME}}/index.php?title=RoofStar_Guarantee_Standards_for_Waterproofing#WPMETAL '''Metal Base Flashing''']: Required on all waterproofing assemblies flashing lengths joined by use of S-locks or standing seam joints. |
− | (5) | + | (5) [http://{{SERVERNAME}}/index.php?title=RoofStar_Guarantee_Standards_for_Waterproofing#WPMETAL '''Metal Counter Flashing''']: Set in reglet fastened with expanding type concrete pins, join flashing lengths by use of S-locks or standing seam joints. |
(6) <b> Fasteners: </b>Suitable expanding type concrete pins. | (6) <b> Fasteners: </b>Suitable expanding type concrete pins. | ||
Line 28: | Line 28: | ||
=== RELATED WORK BY OTHERS === | === RELATED WORK BY OTHERS === | ||
− | (A)<b>Concrete Wall:</b> Must be dry, smooth and primed for membrane flashing to be adhered directly. (Plywood or fibre-mat reinforced cement board may be required). | + | (A) <b>Concrete Wall:</b> Must be dry, smooth and primed for membrane flashing to be adhered directly. (Plywood or fibre-mat reinforced cement board may be required). |
− | (B) | + | (B) [http://{{SERVERNAME}}/index.php?title=RoofStar_Guarantee_Standards_for_Waterproofing#WPREGLET '''Reglet''']: </b>minimum 75mm (3/4") in depth, saw cut or manufactured preformed reglet. |
</div><!-- COL-6-MD --> | </div><!-- COL-6-MD --> | ||
</div><!-- PANEL BODY --> | </div><!-- PANEL BODY --> |
Revision as of 17:52, 12 October 2016
RoofStar Guarantee Standards are blue-linked |
1 WORK INCLUDED
(1) Primary Waterproofing Membrane: Fully adhered to acceptable substrates (concrete slab depicted), installed as per RoofStar Guarantee Standards for Waterproofing Plazas, Promenades & Terraces and Membrane Manufacturer's installation specifications.
(2) Membrane Flashing (stripping): Carried up walls a minimum 200 mm (8") above membrane surface (Deck) and a minimum of 100mm (4") above top surface of permeable waterproofing wearing surfaces and overburdens.
(3) Membrane Primer or Adhesive: proprietary primer or adhesive, application and quantities as directed by membrane manufacturers published application specifications.
(4) Metal Base Flashing: Required on all waterproofing assemblies flashing lengths joined by use of S-locks or standing seam joints.
(5) Metal Counter Flashing: Set in reglet fastened with expanding type concrete pins, join flashing lengths by use of S-locks or standing seam joints.
(6) Fasteners: Suitable expanding type concrete pins.
(7) Caulking: Polyurethane sealant, fill void and tool smooth.
2 RELATED WORK BY OTHERS
(A) Concrete Wall: Must be dry, smooth and primed for membrane flashing to be adhered directly. (Plywood or fibre-mat reinforced cement board may be required).
(B) Reglet: minimum 75mm (3/4") in depth, saw cut or manufactured preformed reglet.
NOTE: Refer to RoofStar Guarantee Standards for additional requirements.
Back to Waterproofing Application