RoofStar Guarantee Standards are blue-linked |
ASM Details
1 WORK INCLUDED
- (1) Membranes
- Membranes must be installed to RoofStar Guarantee Standards and the manufacturer's printed instructions
- (2) Adhesion
- Membranes must be fully adhered, where exposed, and mechanically fastened at terminations 300 mm (12") o/c
- (3) Height
- The minimum vertical sealed height above the maximum water level is 150 mm (6"). The membrane run up the slope will vary with roof pitch. Increase height in heavy snow regions.
- (4) Ice and Water Protection
- Built-in gutter membranes can be extended to act as an eave protection membrane. Underlay or eave protection membrane must overlap built-in gutter membrane by a minimum of 200 mm (8") and be installed in shingle fashion (not shown for clarity).
2 RELATED WORK BY OTHERS
- (A) Dimension
- Dimensions of parapets, cants and water loading of gutters are variable and should be determined by design authority
- (B) Acceptable Deck
NOTE: Refer to RoofStar Guarantee Standards for additional requirements.
RoofStar Guarantee Standards for ASM Roof Systems