;(A) [[RoofStar Guarantee Standards for SBS Roof Systems#SBSDECKS|'''Acceptable Deck''']]
 
;(A) [[RoofStar Guarantee Standards for SBS Roof Systems#SBSDECKS|'''Acceptable Deck''']]
 
;(B) '''Air / Vapour Seal'''
 
;(B) '''Air / Vapour Seal'''
;(C) '''Mechanical Curb''': Minimum 200 mm (8") and maximum 300 mm (12") above finished roof surface.
+
;(C) '''Mechanical Curb''': Minimum 200 mm (8") above finished roof surface.
 
;(D) '''Rigid Insulation'''
 
;(D) '''Rigid Insulation'''
 
;(E) '''Wood Nailing Board'''
 
;(E) '''Wood Nailing Board'''

Revision as of 16:18, 20 February 2017

RoofStar Guarantee Standards are blue-linked
SBS Details

D1.7.6-4(1).jpg

D1.7.6-4 (2).jpg


Click below for a printable version of this page.
Print Sheet


1 WORK INCLUDED

(1) Gypsum Deck Overlay
Required when insulation is too thin to span flutes of steel decking or when required as thermal barrier by design authority.
(2) Vapour Retarder
If required by design authority.
(3) Insulation
Mechanically fastened. See available insulation products in the Accepted Materials section of this Manual.
(4) Insulation Overlay Board
As required.
(5) Base Sheet
Adhered to overlay board using asphalt, cold adhesive, self-adhered, mechanical attachment or torch applied according to manufacturer's specification. Torching directly to wood surfaces is not permitted.
(6) Base Sheet Flashing
Adhered according to manufacturer's specifications, using cold adhesive, hot asphalt, self-adhered or torch applied to cover boards, or mechanically attached membrane. Must be tucked under metal flange and mechanically attached to nailing strip.
(7) Cap Sheet
Applied according to manufacturer's printed instructions and to RoofStar Guarantee Standards.
(8) Cap Sheet Flashing
Applied according to manufacturer's printed instructions and to RoofStar Guarantee Standards. Must be tucked under metal flange and mechanically attached to the nailing strip.
(9) Metal Flashing
Mechanically fasten, standing seam at corners. Full width base flashing optional on flexible membranes. Partial skirt flashing minimum 75 mm (3") required on mechanical curbs that require flashing under metal flange.
(10) Alternate Corner Cap (Shop-manufactured)
Weld seams. Bed in two parallel courses of butyl tape or acceptable sealant. Mechanically fasten to outside face of curb flange.
(11) Butyl Tape (sealant)
(12) Fasteners
Flanged fasteners with neoprene washers.

2 RELATED WORK BY OTHERS

(A) Acceptable Deck
(B) Air / Vapour Seal
(C) Mechanical Curb
Minimum 200 mm (8") above finished roof surface.
(D) Rigid Insulation
(E) Wood Nailing Board
(F) Neoprene Gasket for RTU

NOTE: Refer to RoofStar Guarantee Standards for additional requirements.

  • Some mechanical curbs are designed to allow membrane flashing to be carried up onto metal flange. Install according to manufacturers’ instructions.




Back to RoofStar Guarantee Standards for SBS Roof Systems

Back to SBS Construction Details

Back to Construction Details