;(1) '''Flashing''': 0.08 mm (0.032", 20 gauge) Aluminum or 0.56 mm (16 oz) copper to CSA B272-93 flashing supplied by anchor manufacturer with flanges sealed by roofer. | ;(1) '''Flashing''': 0.08 mm (0.032", 20 gauge) Aluminum or 0.56 mm (16 oz) copper to CSA B272-93 flashing supplied by anchor manufacturer with flanges sealed by roofer. | ||
;(2) '''Flashing Flange''': minimum 100 mm (4") flange set in coating of compatible sealant. | ;(2) '''Flashing Flange''': minimum 100 mm (4") flange set in coating of compatible sealant. | ||
− | ;(3) [[RoofStar Guarantee Standards for SBS Roof | + | ;(3) [[RoofStar Guarantee Standards for SBS Modified Bitumen Roof Assemblies#SBSBASE|'''Primary Membrane''']] and [[RoofStar Guarantee Standards for SBS Roof Systems#SBSSTRIPFLASH|'''Membrane Flashing''']]. |
− | ;(4) [[RoofStar Guarantee Standards for SBS Roof | + | ;(4) [[RoofStar Guarantee Standards for SBS Modified Bitumen Roof Assemblies#SBSPMRA|'''Protected Membrane Roof Assembly''']]: Flashing to extend a minimum 200 mm (8") above finished roof surface (pavers, ballast, or walkways) |
− | ;(5) [[RoofStar Guarantee Standards for SBS Roof | + | ;(5) [[RoofStar Guarantee Standards for SBS Modified Bitumen Roof Assemblies#SBS-STRIPPING|'''Conventional Roof Assembly''']]: Flashing to extend a minimum 200 mm (8") above finished roof surface. |
− | ;(6) [[RoofStar Guarantee Standards for SBS Roof | + | ;(6) [[RoofStar Guarantee Standards for SBS Modified Bitumen Roof Assemblies#SBSINSULATION|'''Insulation''']]: See available insulation products in the [[Roof Deck Insulation|'''Accepted Materials''']] section of this Manual. |
<hr> | <hr> | ||
=== WORK BY OTHERS === | === WORK BY OTHERS === | ||
− | ;(A) [[RoofStar Guarantee Standards for SBS Roof | + | ;(A) [[RoofStar Guarantee Standards for SBS Modified Bitumen Roof Assemblies#SBSDECKS|'''Acceptable Deck''']]: Concrete slab shown, see anchor manufacturer's attachment details for other deck types. |
;(B) '''Roof Anchor''':to CSA Z91-M90 | ;(B) '''Roof Anchor''':to CSA Z91-M90 | ||
;(C) '''Anchor Eye''': to CSA Z91-M90 | ;(C) '''Anchor Eye''': to CSA Z91-M90 |
Revision as of 16:33, 23 October 2017
RoofStar Guarantee Standards are blue-linked |
SBS Details
1 WORK INCLUDED
- (1) Flashing
- 0.08 mm (0.032", 20 gauge) Aluminum or 0.56 mm (16 oz) copper to CSA B272-93 flashing supplied by anchor manufacturer with flanges sealed by roofer.
- (2) Flashing Flange
- minimum 100 mm (4") flange set in coating of compatible sealant.
- (3) Primary Membrane and Membrane Flashing.
- (4) Protected Membrane Roof Assembly
- Flashing to extend a minimum 200 mm (8") above finished roof surface (pavers, ballast, or walkways)
- (5) Conventional Roof Assembly
- Flashing to extend a minimum 200 mm (8") above finished roof surface.
- (6) Insulation
- See available insulation products in the Accepted Materials section of this Manual.
2 WORK BY OTHERS
- (A) Acceptable Deck
- Concrete slab shown, see anchor manufacturer's attachment details for other deck types.
- (B) Roof Anchor
- to CSA Z91-M90
- (C) Anchor Eye
- to CSA Z91-M90
- (D) Water Tight Cap
NOTE: Refer to RoofStar Guarantee Standards for additional requirements.