Difference between revisions of "SBS Fall Protection Anchor in Wall (Protected)"

Jump to: navigation, search

Difference between revisions of "SBS Fall Protection Anchor in Wall (Protected)"

(RELATED WORK BY OTHERS)
Line 13: Line 13:
 
<div class="col-md-6">
 
<div class="col-md-6">
 
=== WORK INCLUDED ===
 
=== WORK INCLUDED ===
;(1) [[RoofStar Guarantee Standards for SBS Roof Systems#SBSPMRA|'''Inverted (Protected) Roof Assembly''']]
+
;(1) [[RoofStar Guarantee Standards for SBS Modified Bitumen Roof Assemblies#SBSPMRA|'''Inverted (Protected) Roof Assembly''']]
;(2) [[RoofStar Guarantee Standards for SBS Roof Systems#METALCAP-SBS|'''Counter-flashing''']]
+
;(2) [[RoofStar Guarantee Standards for SBS Modified Bitumen Roof Assemblies#METALCAP-SBS|'''Counter-flashing''']]
;(3) [[RoofStar Guarantee Standards for SBS Roof Systems#SBSINSULATION|'''Insulation - XPS''']]: See available insulation products in the [[Roof Deck Insulation|'''Accepted Materials''']] section of this Manual.
+
;(3) [[RoofStar Guarantee Standards for SBS Modified Bitumen Roof Assemblies#SBSINSULATION|'''Insulation - XPS''']]: See available insulation products in the [[Roof Deck Insulation|'''Accepted Materials''']] section of this Manual.
;(4) [[RoofStar Guarantee Standards for SBS Roof Systems#SBSBASE|'''Primary Membrane''']]
+
;(4) [[RoofStar Guarantee Standards for SBS Modified Bitumen Roof Assemblies#SBSBASE|'''Primary Membrane''']]
  
 
<hr>
 
<hr>
  
 
=== RELATED WORK BY OTHERS ===
 
=== RELATED WORK BY OTHERS ===
;(A) [[RoofStar Guarantee Standards for SBS Roof Systems#SBSDECKS|'''Acceptable Deck''']]
+
;(A) [[RoofStar Guarantee Standards for SBS Modified Bitumen Roof Assemblies#SBSDECKS|'''Acceptable Deck''']]
 
;(B) '''Anchor''': to CSA Z91-M90 - Poured concrete shown, see anchor manufacturer's attachment for other wall types and attachment methods.
 
;(B) '''Anchor''': to CSA Z91-M90 - Poured concrete shown, see anchor manufacturer's attachment for other wall types and attachment methods.
 
;(C) '''Anchor Eye''': to CSA Z91-M90
 
;(C) '''Anchor Eye''': to CSA Z91-M90

Revision as of 16:35, 23 October 2017

RoofStar Guarantee Standards are blue-linked
SBS Details

10.3.7.3.jpg

1 WORK INCLUDED

(1) Inverted (Protected) Roof Assembly
(2) Counter-flashing
(3) Insulation - XPS
See available insulation products in the Accepted Materials section of this Manual.
(4) Primary Membrane

2 RELATED WORK BY OTHERS

(A) Acceptable Deck
(B) Anchor
to CSA Z91-M90 - Poured concrete shown, see anchor manufacturer's attachment for other wall types and attachment methods.
(C) Anchor Eye
to CSA Z91-M90
(D) Anchor Placement For Roof Decks Accessible By General Public/Residential Occupants
Maximum 100 mm (4") above finished roof surface (design to prevent climbing) and not less than 3-1/2" above the finished roof surfacing.
(E) Plywood
15.9 mm (5/8") treated where required.

NOTE: Refer to RoofStar Guarantee Standards for additional requirements.




Back to RoofStar Guarantee Standards for SBS Modified Bitumen Roof Assemblies

Back to SBS Modified Bitumen Construction Details

Back to Construction Details