Difference between revisions of "ASM Eave Protection and Underlayment"

Jump to: navigation, search

Difference between revisions of "ASM Eave Protection and Underlayment"

Line 31: Line 31:
  
 
'''NOTE''': Refer to '''''RoofStar Guarantee Standards''''' for additional requirements.
 
'''NOTE''': Refer to '''''RoofStar Guarantee Standards''''' for additional requirements.
 
  
 
<hr>
 
<hr>
  
  
 
+
[[RoofStar Guarantee Standards for ASM Roof Assemblies|<i class="fa fa-chevron-circle-left fa" ></i> RoofStar Guarantee Standards for ASM Roof Assemblies]]
 
 
[[RoofStar Guarantee Standards for ASM Roof Systems|<i class="fa fa-chevron-circle-left fa" ></i> RoofStar Guarantee Standards for ASM Roof Systems]]
 
  
 
[[Architectural Sheet Metal Construction Details|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''ASM Construction Details'']]
 
[[Architectural Sheet Metal Construction Details|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''ASM Construction Details'']]
  
 
[[Section:G. Construction Details|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''Construction Details'']]
 
[[Section:G. Construction Details|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''Construction Details'']]

Revision as of 17:31, 23 October 2017

RoofStar Guarantee Standards are blue-linked
ASM Details

8.1.jpg

1 WORK INCLUDED

(1) Underlayment
Proprietary underlayment installed perpendicular to the slope with 50 mm (2") minimum side laps and 100 mm (4") minimum end laps.
(2) Ice and Water Protection
One ply of accepted self-adhered modified bituminous membrane.
(3) Edge Metal Flashing
Installed to manufacturer's printed instructions.
Note:
  • This specification is only applicable to slopes 1:3 (4" in 12") or greater
  • Slip sheet not shown for clarity

2 RELATED WORK BY OTHERS

(A) Acceptable Deck


NOTE: Refer to RoofStar Guarantee Standards for additional requirements.