=== WORK INCLUDED ===
 
=== WORK INCLUDED ===
  
(1) <b>Membranes:</b> Membranes must be installed to <i>'''RoofStar Guarantee Standards'''</i> and the manufacturer's printed instructions
+
(1) <b>Membranes:</b> Membranes must be installed to '''''RoofStar Guarantee Standards''''' and the manufacturer's printed instructions
  
 
(2) <b>Adhesion:</b> Membranes must be fully adhered, where exposed, and mechanically fastened at terminations 300 mm (12") o/c
 
(2) <b>Adhesion:</b> Membranes must be fully adhered, where exposed, and mechanically fastened at terminations 300 mm (12") o/c
Line 20: Line 20:
 
(3) <b>Height:</b> The minimum vertical sealed height above the maximum water level is 150 mm (6"). The membrane run up the slope will vary with roof pitch. Increase height in heavy snow regions.
 
(3) <b>Height:</b> The minimum vertical sealed height above the maximum water level is 150 mm (6"). The membrane run up the slope will vary with roof pitch. Increase height in heavy snow regions.
  
(4) <b>[[RoofStar Guarantee Standards for Cedar Shakes %26 Shingles Roof Systems#STR-CSEAVE| '''Eave Protection''']]:</b> Built-in gutter membranes can be extended to act as an eave protection membrane. Underlay or eave protection membrane must overlap built-in gutter membrane by a minimum of 200 mm (8") and be installed in shingle fashion (not shown for clarity).
+
(4) <b>[[RoofStar Guarantee Standards for Cedar Shakes %26 Shingles Roof Assemblies#STR-CSEAVE| '''Eave Protection''']]:</b> Built-in gutter membranes can be extended to act as an eave protection membrane. Underlay or eave protection membrane must overlap built-in gutter membrane by a minimum of 200 mm (8") and be installed in shingle fashion (not shown for clarity).
  
 
=== RELATED WORK BY OTHERS ===
 
=== RELATED WORK BY OTHERS ===
Line 28: Line 28:
 
(B) <b>ACCEPTABLE DECK</b>
 
(B) <b>ACCEPTABLE DECK</b>
  
NOTE: <b>*</b> Refer to <i>RGC Guarantee Standards</i> for additional requirements.
+
NOTE: <b>*</b> Refer to '''''RoofStar Guarantee Standards''''' for additional requirements.
 
</div><!-- COL-6-MD -->
 
</div><!-- COL-6-MD -->
 
</div><!-- PANEL BODY -->
 
</div><!-- PANEL BODY -->
Line 36: Line 36:
  
  
 
+
[[RoofStar Guarantee Standards for Cedar Shakes & Shingles Roof Assemblies|<i class="fa fa-chevron-circle-left fa" ></i> RoofStar Guarantee Standards for Cedar Shakes & Shingles Roof Assemblies]]
[[RoofStar Guarantee Standards for Cedar Shakes & Shingles Roof Systems|<i class="fa fa-chevron-circle-left fa" ></i> RoofStar Guarantee Standards for Cedar Shakes & Shingles Roof Systems]]
 
  
 
[[Cedar Shakes & Shingles Construction Details|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''Cedar Shakes & Shingles Construction Details'']]
 
[[Cedar Shakes & Shingles Construction Details|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''Cedar Shakes & Shingles Construction Details'']]
  
[[Section:G. Construction Details|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''Construction Details'']]
+
[[Construction Details|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''Construction Details'']]

Revision as of 18:07, 23 October 2017

RoofStar Guarantee Standards are blue-linked
Cedar Shakes & Shingles Details

8.3.1.jpg

1 WORK INCLUDED

(1) Membranes: Membranes must be installed to RoofStar Guarantee Standards and the manufacturer's printed instructions

(2) Adhesion: Membranes must be fully adhered, where exposed, and mechanically fastened at terminations 300 mm (12") o/c

(3) Height: The minimum vertical sealed height above the maximum water level is 150 mm (6"). The membrane run up the slope will vary with roof pitch. Increase height in heavy snow regions.

(4) Eave Protection: Built-in gutter membranes can be extended to act as an eave protection membrane. Underlay or eave protection membrane must overlap built-in gutter membrane by a minimum of 200 mm (8") and be installed in shingle fashion (not shown for clarity).

2 RELATED WORK BY OTHERS

(A) DIMENSIONS: Dimensions of parapets, cants and water loading of gutters are variable and should be determined by design authority

(B) ACCEPTABLE DECK

NOTE: * Refer to RoofStar Guarantee Standards for additional requirements.