Difference between revisions of "Template:PERIMETER FLASHINGS - METAL (EPDM, TPO)"
Difference between revisions of "Template:PERIMETER FLASHINGS - METAL (EPDM, TPO)"
(→Seams) |
(→Attachment) |
||
(20 intermediate revisions by the same user not shown) | |||
Line 1: | Line 1: | ||
+ | __NOTOC__ | ||
=== General === | === General === | ||
Line 7: | Line 8: | ||
<span class="principles">Gravel stop-type flashings may be used, provided manufacturer's printed instructions are followed</span> (see Section reference, if required).<span class="reference"> The exceptions are overflow drains and roof scuppers that are installed through walls. These items are to be located by others.</span> | <span class="principles">Gravel stop-type flashings may be used, provided manufacturer's printed instructions are followed</span> (see Section reference, if required).<span class="reference"> The exceptions are overflow drains and roof scuppers that are installed through walls. These items are to be located by others.</span> | ||
− | <p class="reference">Sheet metal flashings are designed to divert water away from the membrane flashing termination, usually onto the roof. The metal flashing also protects the membrane from deterioration due to the elements and from mechanical damage. The metal flashing is not a waterproofing membrane, therefore the roofing membrane should be continuous under the metal | + | <p class="reference">Sheet metal flashings are designed to divert water away from the membrane flashing termination, usually onto the roof. The metal flashing also protects the membrane from deterioration due to the elements and from mechanical damage. The metal flashing is not a waterproofing membrane, therefore the roofing membrane should be continuous under the metal.</p> |
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
<p class="reference">For further details, the Sheet Metal and Air Conditioning Contractors National Association, Inc. (SMACNA) publishes a reliable reference for the proper design and installation of architectural sheet metal. The Architectural Sheet Metal Manual is available from: | <p class="reference">For further details, the Sheet Metal and Air Conditioning Contractors National Association, Inc. (SMACNA) publishes a reliable reference for the proper design and installation of architectural sheet metal. The Architectural Sheet Metal Manual is available from: | ||
Line 41: | Line 35: | ||
=== Attachment === | === Attachment === | ||
+ | The use of concealed in-seam fasteners is required. {{hilite | Metal flashings end joint S-lock seams must have a minimum 1 screw type fastener every 200 mm (8”). For standing seam applications, clips must be a minimum 24 gauge in thickness, 38 mm (1-1/2”) wide, each secured with minimum 2 screws, and placed a minimum of 1 clip every 200 mm (8”). Fasteners must have a low-profile head and penetrate the substrate a minimum of 19 mm (3/4”). || 2017-September-28 }} | ||
+ | |||
+ | Any {{hilite | exposed || 2017-September-28 }} fastening of metal flashings on the top of parapet surfaces is strongly discouraged and is not permitted as the only attachment method. | ||
− | + | If top-surface fastening must be used because of a specific job site condition, only appropriate screw-type fasteners with neoprene washers may be used. {{hilite | Only in-seam S-lock and standing seam clip fasteners are exempt from this requirement. || 2017-September-28 }} | |
− | + | The outside and inside face of metal cap flashing must be attached with cladding fasteners (screws), and/or concealed clips. Continuous and discontinuous concealed clips and or cladding screw fasteners or a combination of these attachment methods are acceptable to secure metal cap flashing. No fastening of flashing is permitted within 87.7 mm (3 ½") of the roof surface. Note: Cladding fasteners or concealed clips are not required on the inside face of roof edge cant strip details. | |
Cladding fasteners (screws) with gasketed washers, used as exposed fasteners for metal flashing, must be No. 8 or better, made of metal compatible with and corresponding in colour to, the flashing material being installed. Nails are not acceptable as exposed fasteners. The minimum number of cladding screws used to face fasten metal cap flashing shall be three (3) fasteners equally spaced (±10%) between seams of flashing formed from 3000 mm (10 ft.) metal stock and a minimum of two fasteners equally spaced (±10%) between flashing seams formed from 2400 mm (8 ft.) metal stock. | Cladding fasteners (screws) with gasketed washers, used as exposed fasteners for metal flashing, must be No. 8 or better, made of metal compatible with and corresponding in colour to, the flashing material being installed. Nails are not acceptable as exposed fasteners. The minimum number of cladding screws used to face fasten metal cap flashing shall be three (3) fasteners equally spaced (±10%) between seams of flashing formed from 3000 mm (10 ft.) metal stock and a minimum of two fasteners equally spaced (±10%) between flashing seams formed from 2400 mm (8 ft.) metal stock. | ||
− | Concealed clips, both continuous and discontinuous, shall be formed from the same metal type as the flashing being secured and be minimum 24 gauge in thickness. In addition, concealed clips are to be fastened as close to the bottom edge (hook) as practical but must not be fastened further than a maximum of 75 mm (3") from the bottom edge (hook). Concealed clips must engage drip or safety edges by a minimum of 12.7 mm ( | + | |
+ | Concealed clips, both continuous and discontinuous, shall be formed from the same metal type as the flashing being secured and be minimum 24 gauge in thickness. In addition, concealed clips are to be fastened as close to the bottom edge (hook) as practical but must not be fastened further than a maximum of 75 mm (3") from the bottom edge (hook). Concealed clips must engage drip or safety edges by a minimum of 12.7 mm (½"). | ||
− | Continuous Concealed Clips are to be attached with appropriate corrosive resistant fasteners spaced at a maximum of 300 mm (12") o/c. | + | '''Continuous Concealed Clips''' are to be attached with appropriate corrosive resistant fasteners spaced at a maximum of 300 mm (12") o/c. |
− | Discontinuous Concealed Clips shall consist of a single clip centred between the seams of each length of metal flashing. Clips shall be a minimum of 1000 mm (40") in length for flashing formed from 3000 mm (10 ft.) metal stock and a minimum 800 mm (32") in length for 2400 mm (8 ft.) metal stock. Discontinuous clips for shorter flashing lengths shall be approximately | + | |
+ | '''Discontinuous Concealed Clips''' shall consist of a single clip centred between the seams of each length of metal flashing. Clips shall be a minimum of 1000 mm (40") in length for flashing formed from 3000 mm (10 ft.) metal stock and a minimum 800 mm (32") in length for 2400 mm (8 ft.) metal stock. Discontinuous clips for shorter flashing lengths shall be approximately ⅓ the length of the metal flashing but not less than 100 mm (4") in length. Corrosive resistant fasteners for clips, to be spaced a maximum of 300 mm (12") o/c. | ||
=== Curb Heights (Roof Openings) === | === Curb Heights (Roof Openings) === | ||
Line 58: | Line 57: | ||
=== Seams === | === Seams === | ||
− | Standing seams and S-lock seams are both acceptable. | + | Standing seams and S-lock seams are both acceptable (see [[MF Details:G1.7.1 Metal Flashings (Cap Flashings - Joint Ends)|'''G1.7.1 Metal Flashing (Cap Flashing - Joint Ends)''']]). |
+ | |||
+ | Seaming of inside corners shall be carried to the base of the cant or the base of the metal. S-locks shall be fastened before the insertion of successive flashing. | ||
− | + | Lap seams are acceptable only where the vertical run on the inside corner is less than 100 mm (4"). | |
− | |||
When the vertical height exceeds 300 mm (12"), standard seaming practices will be followed. When cants are not used on curbs, standard seaming practices (standing seams) shall be followed at all times, with the exception of the vertical flashing portion that is lapped to fit under counter flashing or equipment flanges. | When the vertical height exceeds 300 mm (12"), standard seaming practices will be followed. When cants are not used on curbs, standard seaming practices (standing seams) shall be followed at all times, with the exception of the vertical flashing portion that is lapped to fit under counter flashing or equipment flanges. | ||
Line 68: | Line 68: | ||
The design authority shall choose and specify the seaming system. | The design authority shall choose and specify the seaming system. | ||
+ | <div id=EPDMWOODBLOCKING></div> | ||
+ | <div id=TPOWOODBLOCKING></div> | ||
+ | <div id=METALCAP-TPO></div> | ||
+ | <div id=TPOMETALBASE></div> | ||
=== Cap Flashings, Base Flashings and Reglets === | === Cap Flashings, Base Flashings and Reglets === | ||
− | The top surface of walls (parapets, expansion joints, firewalls, roof dividers, etc.) wider than 100 mm (4" nominal) shall be constructed to provide positive slope to drain and be covered with metal cap flashing. Provide a reglet for all flashings terminating in concrete or masonry walls. When wall flashing terminates in a reglet, typically on high parapet walls, a coping flashing is required at the top of the parapet wall ( | + | The top surface of walls (parapets, expansion joints, firewalls, roof dividers, etc.) wider than 100 mm (4" nominal) shall be constructed to provide positive slope to drain and be covered with metal cap flashing. Provide a reglet for all flashings terminating in concrete or masonry walls. When wall flashing terminates in a reglet, typically on high parapet walls, a coping flashing is required at the top of the parapet wall (for cross-reference, see SBS detail [[SBS Details:D1.7.4 Parapets & Copings (Low Parapet - Unsupported by Wall)|'''D1.7.4 Parapets & Copings (Low Parapet - Unsupported by Wall''')]]). On new construction projects reglet and sloped wood blocking at top surface of concrete or masonry walls are to be installed by others. |
+ | |||
+ | <p class="principles">On flexible membrane conventional roofing systems, when metal wall or curb base flashings are not specified, both the '''''RoofStar Guarantee''''' Accepted Materials and manufacturer's approved wall or curb stripping membranes are acceptable when used with a secondary metal counter flashing placed a maximum of 250 mm (10") above the surface of the roof assembly. Stucco stops are not considered secondary metal counter flashing (for cross-reference, see [[SBS Details:D1.7.11 Counter-flashings & Reglets (Stucco Wall: Re-roofing)|'''D1.7.11 Counter-flashings & Reglets (Stucco Wall: Re-roofing)''']]).</p> | ||
+ | |||
+ | Metal base flashing is required on all vertical surfaces, walls, curbs, etc. when hot asphalt is used to adhere stripping (flashing) membranes. | ||
− | + | Metal base flashings are required on all walls and curbs on roof systems that utilize gravel ballast filter mats. Metal base flashings on protected and modified protected membrane roofs must “kick out” minimum 50 mm (2") over insulation and filter fabric. (see [[SBS Details:D1.7.2 Assemblies (Protected Membrane)|'''D1.7.2 Assemblies (Protected Membrane)''']]). | |
− | Metal base | + | Metal base flashing shall be kept approximately 25 mm (1") above gravel to prevent immersion in water with the exception of protected and modified protected roof systems. |
− | Neither | + | Neither 90-lb mineral roofing nor asphalt strip-type shingles are acceptable as parapet flashing in lieu of sheet metal flashing. |
− | + | ||
+ | Reglets must be 200 mm (8") minimum to 300 mm (12") maximum above the roof surface in conventional and protected membrane roofs. Roof surface is defined as the top of the roofing assembly, be it membrane or ballast. | ||
In the case of multi-wythe masonry, composite walls, or parapets, and where not restricted by seismic codes, continuous flexible thru-wall flashings must be supplied and installed (by others), at the next course above the reglet or, alternatively, the inside of the parapet wall must be completely flashed or cladded. | In the case of multi-wythe masonry, composite walls, or parapets, and where not restricted by seismic codes, continuous flexible thru-wall flashings must be supplied and installed (by others), at the next course above the reglet or, alternatively, the inside of the parapet wall must be completely flashed or cladded. | ||
− | |||
− | |||
− | <div class="principles">Gum edge or gum lip flashings should be avoided in all circumstances. If job conditions allow for no other alternative, written permission from | + | <div class="principles">Gum edge or gum lip flashings should be avoided in all circumstances. If job conditions allow for no other alternative, written permission from the '''''RoofStar Guarantee Program''''' for use of gum edge flashing must be obtained (also called surface reglet) (for cross-reference, see [[SBS Details:D1.7.13 Counter-flashings & Reglets (Double Surface Reglet)|'''D1.7.13 Counter-flashings & Reglets (Double Surface Reglet)''']]).</div> |
=== Flashing on Stucco Walls === | === Flashing on Stucco Walls === | ||
− | On stucco-faced walls, only 2-piece flashings are permitted. The | + | On stucco-faced walls, only 2-piece flashings are permitted. The lower piece, retaining the stucco, must have a vertical flange to extend behind stucco and building paper. Stucco stops are not considered metal counter flashings (for cross-reference, see [[SBS Details:D1.7.11 Counter-flashings & Reglets (Stucco Wall: Re-roofing)|'''D1.7.11 Counter-flashings & Reglets (Stucco Wall: Re-roofing)''']]). |
Latest revision as of 22:01, 7 March 2018
1 General
All roof protrusion and penetration flashings, vents, curbs, sleepers, pipes cable, drains, etc. shall NOT be installed LESS than 200mm (8") from the base of walls, cants, eaves and other roof equipment, protrusion and penetration flashings.
Metal base flashing shall be kept approximately 25 mm (1") above gravel to prevent immersion in water with the exception of protected and modified protected roof systems.
Gravel stop-type flashings may be used, provided manufacturer's printed instructions are followed (see Section reference, if required). The exceptions are overflow drains and roof scuppers that are installed through walls. These items are to be located by others.
Sheet metal flashings are designed to divert water away from the membrane flashing termination, usually onto the roof. The metal flashing also protects the membrane from deterioration due to the elements and from mechanical damage. The metal flashing is not a waterproofing membrane, therefore the roofing membrane should be continuous under the metal.
For further details, the Sheet Metal and Air Conditioning Contractors National Association, Inc. (SMACNA) publishes a reliable reference for the proper design and installation of architectural sheet metal. The Architectural Sheet Metal Manual is available from:
- Sheet Metal and Air Conditioning Contractors National Association, Inc.
- c/o British Columbia Sheet Metal Association
- 156 - 4664 Lougheed Hwy Burnaby, B.C. V5C 5T5 (604) 299-4641
2 Material Selection
The following minimum gauges and / or weights of commonly used metals or alloys will be applied to all projects under the Guarantee Program. The length of metal flashing shall be limited to a maximum of 3.04 m (10').
GALVANIZED STEEL: 0.50 mm (0.0196", 26 gauge) galvanized steel sheet, conforming to ASTM A653 / A653M-06 CS Type B, Z275 (G90) coating. Thickness tolerance as per ASTM A924/A924M-06 ±0.08 mm (0.003") for sheet widths not exceeding 1500 mm (60").
ALUMINIUM – ZINC ALLOY COATED STEEL: 0.50 mm (0.0196", 26 gauge) aluminium-zinc alloy coated steel sheet, conforming to ASTM A792/A792M-06 CS Type B, AZM150 (AZ50) coating. Thickness tolerance as per ASTM A924/A924M-06 ±0.08 mm (0.003") for sheet widths not exceeding 1500 mm (60").
ALUMINIUM: 0.80 mm (0.032", 20 gauge) aluminium sheet, utility quality to CSA HA Series - 1975, plain or embossed finish. Maximum thickness tolerance variation ± 0.06 mm (0.0025") based on 1200 mm (48") wide sheet.
STAINLESS STEEL: 0.38 mm (0.014", 28 gauge) stainless steel, Type 302, 304, 316, 2B finish to ASTM A167-82. Maximum thickness tolerance variation ± 0.04 mm (0.0015") based on 1200 mm (48") wide sheet. COPPER: 0.56 mm (0.022", 16 oz.) copper sheet, cold rolled roofing copper to ASTM B370-81. Maximum thickness tolerance variation ± 0.09 mm (0.0035") based on 1200 mm (48") wide sheet.
ZINC: 0.80 mm (0.031") zinc Sheet conforming to European standard EN 988-1996. Maximum thickness tolerance variation ± 0.03 mm (0.0012").
3 Attachment
The use of concealed in-seam fasteners is required. Metal flashings end joint S-lock seams must have a minimum 1 screw type fastener every 200 mm (8”). For standing seam applications, clips must be a minimum 24 gauge in thickness, 38 mm (1-1/2”) wide, each secured with minimum 2 screws, and placed a minimum of 1 clip every 200 mm (8”). Fasteners must have a low-profile head and penetrate the substrate a minimum of 19 mm (3/4”).
Any exposed fastening of metal flashings on the top of parapet surfaces is strongly discouraged and is not permitted as the only attachment method.
If top-surface fastening must be used because of a specific job site condition, only appropriate screw-type fasteners with neoprene washers may be used. Only in-seam S-lock and standing seam clip fasteners are exempt from this requirement.
The outside and inside face of metal cap flashing must be attached with cladding fasteners (screws), and/or concealed clips. Continuous and discontinuous concealed clips and or cladding screw fasteners or a combination of these attachment methods are acceptable to secure metal cap flashing. No fastening of flashing is permitted within 87.7 mm (3 ½") of the roof surface. Note: Cladding fasteners or concealed clips are not required on the inside face of roof edge cant strip details.
Cladding fasteners (screws) with gasketed washers, used as exposed fasteners for metal flashing, must be No. 8 or better, made of metal compatible with and corresponding in colour to, the flashing material being installed. Nails are not acceptable as exposed fasteners. The minimum number of cladding screws used to face fasten metal cap flashing shall be three (3) fasteners equally spaced (±10%) between seams of flashing formed from 3000 mm (10 ft.) metal stock and a minimum of two fasteners equally spaced (±10%) between flashing seams formed from 2400 mm (8 ft.) metal stock.
Concealed clips, both continuous and discontinuous, shall be formed from the same metal type as the flashing being secured and be minimum 24 gauge in thickness. In addition, concealed clips are to be fastened as close to the bottom edge (hook) as practical but must not be fastened further than a maximum of 75 mm (3") from the bottom edge (hook). Concealed clips must engage drip or safety edges by a minimum of 12.7 mm (½").
Continuous Concealed Clips are to be attached with appropriate corrosive resistant fasteners spaced at a maximum of 300 mm (12") o/c.
Discontinuous Concealed Clips shall consist of a single clip centred between the seams of each length of metal flashing. Clips shall be a minimum of 1000 mm (40") in length for flashing formed from 3000 mm (10 ft.) metal stock and a minimum 800 mm (32") in length for 2400 mm (8 ft.) metal stock. Discontinuous clips for shorter flashing lengths shall be approximately ⅓ the length of the metal flashing but not less than 100 mm (4") in length. Corrosive resistant fasteners for clips, to be spaced a maximum of 300 mm (12") o/c.
4 Curb Heights (Roof Openings)
On all roofing assemblies (protected, modified protected or conventional), the minimum curb height (equipment curbs, vent curbs, etc.) shall be 200 mm (8") above the roof surfacing. Surfacing is defined as the top of the roofing assembly, be it membrane or ballast.
5 Seams
Standing seams and S-lock seams are both acceptable (see G1.7.1 Metal Flashing (Cap Flashing - Joint Ends)).
Seaming of inside corners shall be carried to the base of the cant or the base of the metal. S-locks shall be fastened before the insertion of successive flashing.
Lap seams are acceptable only where the vertical run on the inside corner is less than 100 mm (4").
When the vertical height exceeds 300 mm (12"), standard seaming practices will be followed. When cants are not used on curbs, standard seaming practices (standing seams) shall be followed at all times, with the exception of the vertical flashing portion that is lapped to fit under counter flashing or equipment flanges.
For roof curb-flashing seams ( e.g. equipment, skylights, etc.), which do not exceed 300 mm (12") in height, lap-type seams may be used on the vertical portion provided standing seams are used in the cant area.
The design authority shall choose and specify the seaming system.
6 Cap Flashings, Base Flashings and Reglets
The top surface of walls (parapets, expansion joints, firewalls, roof dividers, etc.) wider than 100 mm (4" nominal) shall be constructed to provide positive slope to drain and be covered with metal cap flashing. Provide a reglet for all flashings terminating in concrete or masonry walls. When wall flashing terminates in a reglet, typically on high parapet walls, a coping flashing is required at the top of the parapet wall (for cross-reference, see SBS detail D1.7.4 Parapets & Copings (Low Parapet - Unsupported by Wall)). On new construction projects reglet and sloped wood blocking at top surface of concrete or masonry walls are to be installed by others.
On flexible membrane conventional roofing systems, when metal wall or curb base flashings are not specified, both the RoofStar Guarantee Accepted Materials and manufacturer's approved wall or curb stripping membranes are acceptable when used with a secondary metal counter flashing placed a maximum of 250 mm (10") above the surface of the roof assembly. Stucco stops are not considered secondary metal counter flashing (for cross-reference, see D1.7.11 Counter-flashings & Reglets (Stucco Wall: Re-roofing)).
Metal base flashing is required on all vertical surfaces, walls, curbs, etc. when hot asphalt is used to adhere stripping (flashing) membranes.
Metal base flashings are required on all walls and curbs on roof systems that utilize gravel ballast filter mats. Metal base flashings on protected and modified protected membrane roofs must “kick out” minimum 50 mm (2") over insulation and filter fabric. (see D1.7.2 Assemblies (Protected Membrane)).
Metal base flashing shall be kept approximately 25 mm (1") above gravel to prevent immersion in water with the exception of protected and modified protected roof systems.
Neither 90-lb mineral roofing nor asphalt strip-type shingles are acceptable as parapet flashing in lieu of sheet metal flashing.
Reglets must be 200 mm (8") minimum to 300 mm (12") maximum above the roof surface in conventional and protected membrane roofs. Roof surface is defined as the top of the roofing assembly, be it membrane or ballast.
In the case of multi-wythe masonry, composite walls, or parapets, and where not restricted by seismic codes, continuous flexible thru-wall flashings must be supplied and installed (by others), at the next course above the reglet or, alternatively, the inside of the parapet wall must be completely flashed or cladded.
7 Flashing on Stucco Walls
On stucco-faced walls, only 2-piece flashings are permitted. The lower piece, retaining the stucco, must have a vertical flange to extend behind stucco and building paper. Stucco stops are not considered metal counter flashings (for cross-reference, see D1.7.11 Counter-flashings & Reglets (Stucco Wall: Re-roofing)).