Revision as of 15:10, 25 April 2019
RoofStar Guarantee Standards are blue-linked |
ASM Details
1 WORK INCLUDED
- (1) Architectural Metal Roof Panel
- (2) Metal Counter Flashing
- (3) Backpan Flashing
- Required for curbs up to 900 mm (36") wide.
- (4) Metal Curb Flashing
- (5) Acceptable Caulking
- Two rows accepted caulking between overlapping sheets, with preformed closures on trapezoidal ribbed roof panels.
- (6) Cleat.
- (7) Slip Sheet
- Recommended over asphaltic underlays and / or as required by metal roof panel manufacturer.
- (8) Underlayment
- The type of underlay required is determined by roof slope.
- (9) Metal Panel Clip
- Installed to metal roof panel manufacturer's printed instructions.
- (10) Air / Vapour Controls
2 RELATED WORK BY OTHERS
- Acceptable Deck
- Wood Curb
- 200 mm (8") minimum height
NOTE: Refer to RoofStar Guarantee Standards for additional requirements.
RoofStar Guarantee Standards for ASM Roof Assemblies