Difference between revisions of "ASM Eave Protection and Underlayment (Low Slopes)"
Difference between revisions of "ASM Eave Protection and Underlayment (Low Slopes)"
(→WORK INCLUDED) |
|||
Line 8: | Line 8: | ||
<div style="text-align:center; vertical-align:center"> | <div style="text-align:center; vertical-align:center"> | ||
[[File:8.1.4.2.1.jpg|class=img-responsive]] | [[File:8.1.4.2.1.jpg|class=img-responsive]] | ||
+ | </div> | ||
+ | </div><!-- COL-MD-6 --> | ||
+ | |||
+ | ::Click below for a printable version of this page. | ||
+ | |||
+ | <div style="width:150px; text-align: left;"> | ||
+ | :[[File:ASM 8.1.2 Thumb for PDF.jpg|100 px|link=http://rpm.rcabc.org/images/1/1d/ASM_8.1.2_Self-adhered_Underlayemnt.pdf|'''Print Sheet''']] | ||
</div> | </div> | ||
</div><!-- COL-MD-6 --> | </div><!-- COL-MD-6 --> |
Revision as of 16:57, 1 August 2019
RoofStar Guarantee Standards are blue-linked |
ASM Details
1 WORK INCLUDED
- (1) Underlayment
- One ply of self-adhered modified bituminous underlayment material. Lap 50 mm (2") minimum on sides and 100 mm (4") minimum on ends.
- (2) Eave Protection
- One ply of self-adhered modified bituminous underlayment material. Lap 50 mm (2") minimum on sides and 100 mm (4") minimum on ends.
- (3) Edge Metal Flashing
- Installed to manufacturer's printed instructions.
- (4) Metal flashing underlayment/separation membrane
- required for metal flashings installed on wood substrates.
- Note: This application is required on slopes greater than 1:6 (2" in 12") and less than 1:3 (4" in 12").
2 RELATED WORK BY OTHERS
- (A) Acceptable Deck
NOTE: Refer to RoofStar Guarantee Standards for additional requirements.
RoofStar Guarantee Standards for ASM Roof Assemblies