Difference between revisions of "SBS Basic Curb"
Difference between revisions of "SBS Basic Curb"
m (James Klassen moved page SBS Details:D1.7.6-3 Curbs & Sleepers (Basic Curb) to SBS 11.3.3.2-1 Curbs and Sleepers (basic curb)) |
(→WORK INCLUDED) |
||
Line 31: | Line 31: | ||
;(7) [[RoofStar Guarantee Standards for SBS Modified Bitumen Roof Assemblies#SBSBASE|'''Cap Sheet''']]: Applied according to manufacturer’s printed instructions and to <i>RoofStar Guarantee Standards</i>. | ;(7) [[RoofStar Guarantee Standards for SBS Modified Bitumen Roof Assemblies#SBSBASE|'''Cap Sheet''']]: Applied according to manufacturer’s printed instructions and to <i>RoofStar Guarantee Standards</i>. | ||
;(8) [[RoofStar Guarantee Standards for SBS Modified Bitumen Roof Assemblies#SBS-STRIPPING|'''Cap Sheet Flashing''']]: Applied according to manufacturer’s printed instructions and to <i>RoofStar Guarantee Standards</i> to top of curb. | ;(8) [[RoofStar Guarantee Standards for SBS Modified Bitumen Roof Assemblies#SBS-STRIPPING|'''Cap Sheet Flashing''']]: Applied according to manufacturer’s printed instructions and to <i>RoofStar Guarantee Standards</i> to top of curb. | ||
− | ;(9) [[RoofStar Guarantee Standards for SBS Modified Bitumen Roof Assemblies#METALCAP-SBS|'''Metal Flashing''']]: | + | ;(9) [[RoofStar Guarantee Standards for SBS Modified Bitumen Roof Assemblies#METALCAP-SBS|'''Metal Flashing''']]: Designed and installed in keeping with the '''''RoofStar Guarantee Standards''''' when required by the ''Design Authority''. |
;(10) '''Fire-stop Tape''': Recommended. | ;(10) '''Fire-stop Tape''': Recommended. | ||
Revision as of 23:00, 10 February 2020
RoofStar Guarantee Standards are blue-linked |
SBS Details
1 WORK INCLUDED
- (1) Supporting Deck Overlay
- Required when insulation is too thin to span flutes of steel decking or when required as thermal barrier by design authority.
- (2) Air or Vapour Control Layers
- If required by design authority.
- (3) Insulation
- Mechanically fastened. See available insulation products in the Accepted Materials section of this Manual.
- (4) Insulation Overlay
- Asphalt adhered or mechanically fastened. Two layers required over heat-sensitive insulation.
- (5) Base Sheet
- Adhered to overlay board using asphalt, cold adhesive, self-adhered, mechanical attachment or torch applied according to manufacturer’s specification and to RoofStar Guarantee Standards. Torching directly to wood surfaces is not permitted.
- (6) Base Sheet Flashing
- Adhered according to manufacturer’s specifications, using cold adhesive, self-adhered, or torch applied to cover boards, or mechanically attached membrane. Torching directly to wood surfaces is not permitted.
- (7) Cap Sheet
- Applied according to manufacturer’s printed instructions and to RoofStar Guarantee Standards.
- (8) Cap Sheet Flashing
- Applied according to manufacturer’s printed instructions and to RoofStar Guarantee Standards to top of curb.
- (9) Metal Flashing
- Designed and installed in keeping with the RoofStar Guarantee Standards when required by the Design Authority.
- (10) Fire-stop Tape
- Recommended.
2 RELATED WORK BY OTHERS
- (A) Acceptable Supporting Deck Structure
- (B) Air and Vapour Control Layer Seal
- (C) Wood Blocking
- Minimum 200 mm (8") in height. (See asphalt adhered or mechanically fastened. Two layers required over heat-sensitive insulation. Cant is optional).
NOTE: Refer to RoofStar Guarantee Standards for additional requirements.
Back to RoofStar Guarantee Standards for SBS Modified Bitumen Roof Assemblies