=== WORK INCLUDED === | === WORK INCLUDED === | ||
;(1) '''Asphalt Shingles''': Installed to manufacturer’s published instructions and '''''RoofStar Guarantee Standards'''''. | ;(1) '''Asphalt Shingles''': Installed to manufacturer’s published instructions and '''''RoofStar Guarantee Standards'''''. | ||
− | ;(2) [[Standard for Asphalt Shingle Systems# | + | ;(2) [[Standard for Asphalt Shingle Systems#AShPART11-APRON|'''Apron Flashing''']] |
: Extended a minimum 100mm (4") beyond corners, interwoven with shingles and step flashings. | : Extended a minimum 100mm (4") beyond corners, interwoven with shingles and step flashings. | ||
− | ;(3) [[Standard for Asphalt Shingle Systems# | + | ;(3) [[Standard for Asphalt Shingle Systems#AShPART11-STEP|'''Step Flashing''']]: Interwoven with each course of shingles, 75mm (3") head lap. |
;(4) '''Final Step flashing''': Extended around corner of the upstand and under back pan flashing. The upstand fold can alternatively be turned outward under the back pan fold. | ;(4) '''Final Step flashing''': Extended around corner of the upstand and under back pan flashing. The upstand fold can alternatively be turned outward under the back pan fold. | ||
− | ;(5) [[Standard for Asphalt Shingle Systems# | + | ;(5) [[Standard for Asphalt Shingle Systems#AShPART11-BACKPAN|'''Backpan Flashing''']]: The back-pan is to be extended 100mm (4") beyond the corner and folded. Apply caulking at the transition corner of the final step flashing and back pan. |
;(6) '''Capillary Section''': A capillary tab is to be extended off the end of the back pan to lead water around the corner. | ;(6) '''Capillary Section''': A capillary tab is to be extended off the end of the back pan to lead water around the corner. | ||
</div><!-- COL-6-MD --> | </div><!-- COL-6-MD --> |
Revision as of 16:59, 8 June 2021
RoofStar Guarantee Standards are blue-linked |
Asphalt Shingle Details
WORK INCLUDED
- (1) Asphalt Shingles
- Installed to manufacturer’s published instructions and RoofStar Guarantee Standards.
- (2) Apron Flashing
- Extended a minimum 100mm (4") beyond corners, interwoven with shingles and step flashings.
- (3) Step Flashing
- Interwoven with each course of shingles, 75mm (3") head lap.
- (4) Final Step flashing
- Extended around corner of the upstand and under back pan flashing. The upstand fold can alternatively be turned outward under the back pan fold.
- (5) Backpan Flashing
- The back-pan is to be extended 100mm (4") beyond the corner and folded. Apply caulking at the transition corner of the final step flashing and back pan.
- (6) Capillary Section
- A capillary tab is to be extended off the end of the back pan to lead water around the corner.
NOTE: Refer to RoofStar Guarantee Standards for additional requirements.
- Proprietary soldered or welded diverter flashing may be used provided they conform to RoofStar Guarantee Standards.
Standard for Asphalt Shingle Systems