Difference between revisions of "SBS Mechanical Equipment Curb"
Difference between revisions of "SBS Mechanical Equipment Curb"
Line 46: | Line 46: | ||
;(B) [[SBS Roof Systems Standard#SBSAIRVAPOUR|'''Air or Vapour Control Layer Seal''']] | ;(B) [[SBS Roof Systems Standard#SBSAIRVAPOUR|'''Air or Vapour Control Layer Seal''']] | ||
;(C) '''Mechanical Curb''': Minimum 200 mm (8") above finished roof surface. | ;(C) '''Mechanical Curb''': Minimum 200 mm (8") above finished roof surface. | ||
+ | :* Some mechanical curbs are designed to allow membrane flashing to be carried up onto metal flange. Install according to manufacturers’ instructions. | ||
;(D) '''Rigid Insulation''' | ;(D) '''Rigid Insulation''' | ||
;(E) '''Wood Nailing Board''' | ;(E) '''Wood Nailing Board''' | ||
Line 53: | Line 54: | ||
</div><!-- PANEL --> | </div><!-- PANEL --> | ||
− | '''NOTE''': | + | '''NOTE''': See the [[SBS Roof Systems Standard | '''Standard''']] for additional requirements. |
− | |||
− | |||
<hr> | <hr> | ||
+ | [[SBS Roof Systems Standard|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''RoofStar Guarantee Standards for SBS Modified Bitumen Roof Assemblies'']] | ||
− | [[SBS Roof | + | [[SBS Roof System Details|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''SBS Modified Bitumen Construction Details'']] |
− | + | {{Tempate:RPM Page Footer with Copyright and Current Date}} |
Revision as of 17:49, 27 August 2021
Requirements in the Standard are hyper-linked |
SBS Details
1 WORK INCLUDED
- (1) Supporting Deck Overlay
- Required when insulation is too thin to span flutes of steel decking or when required as thermal barrier by design authority.
- (2) Air or Vapour Control Layers
- If required by design authority.
- (3) Insulation
- Mechanically fastened. See available insulation products in the Accepted Materials section of this Manual.
- (4) Insulation Overlay
- As required.
- (5) Base Field Membrane
- Adhered to overlay board using asphalt, cold adhesive, self-adhered, mechanical attachment or torch applied according to manufacturer's specification. Torching directly to wood surfaces is not permitted.
- (6) Base Membrane Flashing
- Adhered according to manufacturer's specifications, using cold adhesive, hot asphalt, self-adhered or torch applied to cover boards, or mechanically attached membrane. Must be tucked under metal flange and mechanically attached to nailing strip.
- (7) Cap Field Membrane
- Applied according to manufacturer's printed instructions and to RoofStar Guarantee Standards.
- (8) Cap Membrane Flashing
- Applied according to manufacturer's printed instructions and to RoofStar Guarantee Standards. Must be tucked under metal flange and mechanically attached to the nailing strip.
- (9) Metal Flashing
- Mechanically fasten, standing seam at corners. Full width base flashing optional on flexible membranes. Partial skirt flashing minimum 75 mm (3") required on mechanical curbs that require flashing under metal flange.
- (10) Alternate Corner Cap (Shop-manufactured)
- Weld seams. Bed in two parallel courses of butyl tape or acceptable sealant. Mechanically fasten to outside face of curb flange.
- (11) Butyl Tape (sealant)
- (12) Fasteners
- Flanged fasteners with neoprene washers.
2 RELATED WORK BY OTHERS
- (A) Acceptable Supporting Deck Structure
- (B) Air or Vapour Control Layer Seal
- (C) Mechanical Curb
- Minimum 200 mm (8") above finished roof surface.
- Some mechanical curbs are designed to allow membrane flashing to be carried up onto metal flange. Install according to manufacturers’ instructions.
- (D) Rigid Insulation
- (E) Wood Nailing Board
- (F) Neoprene Gasket for RTU
NOTE: See the Standard for additional requirements.
Back to RoofStar Guarantee Standards for SBS Modified Bitumen Roof Assemblies
Back to SBS Modified Bitumen Construction Details