=== WORK INCLUDED ===
 
=== WORK INCLUDED ===
  
;(1) [[SBS Roof Systems Standard#SBSSUBSTRATES|'''Supporting Deck Overlay''']]:  
+
;(1) [[SBS Roof Systems Standard#PART_2|'''Supporting Deck Overlay''']]:  
 
:If required by design authority.
 
:If required by design authority.
;(2) [[SBS Roof Systems Standard#SBSAIRVAPOUR|'''Air or Vapour Control Layers''']]:
+
;(2) [[SBS Roof Systems Standard#PART_6|'''Air or Vapour Control Layers''']]:
 
:If required by design authority.
 
:If required by design authority.
;(3) [[SBS Roof Systems Standard#SBSINSULATION|'''Insulation''']]:
+
;(3) [[SBS Roof Systems Standard#PART_7|'''Insulation''']]:
 
:See list of '''[[Section:C. Accepted Materials|Accepted Materials]]'''.
 
:See list of '''[[Section:C. Accepted Materials|Accepted Materials]]'''.
;(4) [[SBS Roof Systems Standard#SBSINSULATIONOVERLAY|'''Insulation Overlay''']]:
+
;(4) [[SBS Roof Systems Standard#PART_8|'''Insulation Overlay''']]:
 
:As required.
 
:As required.
;(5) [[SBS Roof Systems Standard#SBSBASE|'''Primary Membrane and Membrane Protection''']]:
+
;(5) [[SBS Roof Systems Standard#PART_9|'''Primary Membrane and Membrane Protection''']]:
;(6) [[SBS Roof Systems Standard#SBS-STRIPPING|'''Membrane Flashing''']]:
+
;(6) [[SBS Roof Systems Standard#PART_10|'''Membrane Flashing''']]:
 
:Mechanically fasten to outside face of parapet blocking (D). At least one ply must extend over outside edge.
 
:Mechanically fasten to outside face of parapet blocking (D). At least one ply must extend over outside edge.
;(7) [[SBS Roof Systems Standard#METALCAP-SBS|'''Metal Base Flashing''']]:
+
;(7) [[SBS Roof Systems Standard#PART_13|'''Metal Base Flashing''']]:
 
:Optional on flexible membrane systems. Required on assemblies using gravel ballast filter mats.
 
:Optional on flexible membrane systems. Required on assemblies using gravel ballast filter mats.
;(8) [[SBS Roof Systems Standard#METALCAP-SBS|'''Metal Cap Flashing''']]:
+
;(8) [[SBS Roof Systems Standard#PART_13|'''Metal Cap Flashing''']]:
 
:Flashings 1 and 2 may be one piece.  Fasten with continuous concealed clip-type fasteners <b>or</b> cladding screws evenly spaced between seams.
 
:Flashings 1 and 2 may be one piece.  Fasten with continuous concealed clip-type fasteners <b>or</b> cladding screws evenly spaced between seams.
  
Line 44: Line 44:
 
=== RELATED WORK BY OTHERS ===
 
=== RELATED WORK BY OTHERS ===
  
;(A) [[SBS Roof Systems Standard#SBS-STEELDECK|'''Acceptable Supporting Steel Deck Structure''']]
+
;(A) [[SBS Roof Systems Standard#PART_2|'''Acceptable Supporting Steel Deck Structure''']]
;(B) [[SBS Roof Systems Standard#SBSAIRVAPOUR|'''Air/Vapour Seal''']]
+
;(B) [[SBS Roof Systems Standard#PART_6|'''Air/Vapour Seal''']]
;(C) [[SBS Roof Systems Standard#SBSWALLSUB|'''Acceptable Wall Surface''']]
+
;(C) [[SBS Roof Systems Standard#PART_2|'''Acceptable Wall Surface''']]
 
;(D) '''Wood Blocking'''
 
;(D) '''Wood Blocking'''
;(E) [[SBS Roof Systems Standard#SBSSLOPEDWOODBLOCKING|'''Sloped Wood Blocking''']]
+
;(E) [[SBS Roof Systems Standard#PART_10|'''Sloped Wood Blocking''']]
 
:Required over 100 mm (4") parapet width.
 
:Required over 100 mm (4") parapet width.
 
</div><!-- COL-6-MD -->
 
</div><!-- COL-6-MD -->

Revision as of 14:56, 1 September 2021


Notice to Reader
Images used in a Construction Detail are representative and not prescriptive. Nor are they necessarily drawn to scale. Rather, they are provided to visually convey the requirements of the Standard they represent. Unless otherwise required by the Standard, dimensions, the selection of materials and their application remains the responsibility of the Design Authority.

The full text of the referenced requirements in the Standard may be read by using the blue hyperlinks
SBS Details

10.3.1.1.jpg

Click below for a printable version of this page.
Print Sheet

1 WORK INCLUDED

(1) Supporting Deck Overlay
If required by design authority.
(2) Air or Vapour Control Layers
If required by design authority.
(3) Insulation
See list of Accepted Materials.
(4) Insulation Overlay
As required.
(5) Primary Membrane and Membrane Protection
(6) Membrane Flashing
Mechanically fasten to outside face of parapet blocking (D). At least one ply must extend over outside edge.
(7) Metal Base Flashing
Optional on flexible membrane systems. Required on assemblies using gravel ballast filter mats.
(8) Metal Cap Flashing
Flashings 1 and 2 may be one piece. Fasten with continuous concealed clip-type fasteners or cladding screws evenly spaced between seams.

2 RELATED WORK BY OTHERS

(A) Acceptable Supporting Steel Deck Structure
(B) Air/Vapour Seal
(C) Acceptable Wall Surface
(D) Wood Blocking
(E) Sloped Wood Blocking
Required over 100 mm (4") parapet width.

NOTE: See the Standard for additional requirements.