=== WORK INCLUDED ===
 
=== WORK INCLUDED ===
;(1) [[SBS Roof Systems Standard#SBSSUBSTRATES|'''Supporting Deck Overlay''']]: Required when insulation is too thin to span flutes of steel decking or when required as thermal barrier by design authority.
+
;(1) [[SBS Roof Systems Standard#PART_5|'''Supporting Deck Overlay''']]: Required when insulation is too thin to span flutes of steel decking or when required as thermal barrier by design authority.
;(2) [[SBS Roof Systems Standard#SBSAIRVAPOUR|'''Air or Vapour Control Layers''']]: If required by design authority.
+
;(2) [[SBS Roof Systems Standard#PART_6|'''Air or Vapour Control Layers''']]: If required by design authority.
;(3) [[SBS Roof Systems Standard#SBSINSULATION|'''Insulation''']]: Mechanically fastened.  See available insulation products in the [[Roof Deck Insulation|'''Accepted Materials''']] section of this Manual.
+
;(3) [[SBS Roof Systems Standard#PART_7|'''Insulation''']]: Mechanically fastened.  See available insulation products in the [[Roof Deck Insulation|'''Accepted Materials''']] section of this Manual.
;(4) [[SBS Roof Systems Standard#SBSINSULATIONOVERLAY|'''Insulation Overlay''']]: As required.
+
;(4) [[SBS Roof Systems Standard#PART_8|'''Insulation Overlay''']]: As required.
;(5) [[SBS Roof Systems Standard#SBSBASE|'''Base Field Membrane''']]: Adhered to overlay board using asphalt, cold adhesive, self-adhered, mechanical attachment or torch applied according to manufacturer's specification. Torching directly to wood surfaces is not permitted.
+
;(5) [[SBS Roof Systems Standard#PART_9|'''Base Field Membrane''']]: Adhered to overlay board using asphalt, cold adhesive, self-adhered, mechanical attachment or torch applied according to manufacturer's specification. Torching directly to wood surfaces is not permitted.
;(6) [[SBS Roof Systems Standard#SBS-STRIPPING|'''Base Membrane Flashing''']]: Adhered according to manufacturer's specifications, using cold adhesive, hot asphalt, self-adhered or torch applied to cover boards, or mechanically attached membrane. Must be tucked under metal flange and mechanically attached to nailing strip.
+
;(6) [[SBS Roof Systems Standard#PART_10|'''Base Membrane Flashing''']]: Adhered according to manufacturer's specifications, using cold adhesive, hot asphalt, self-adhered or torch applied to cover boards, or mechanically attached membrane. Must be tucked under metal flange and mechanically attached to nailing strip.
;(7) [[SBS Roof Systems Standard#SBSBASE|'''Cap Field Membrane''']]: Applied according to manufacturer's printed instructions and to <i>RoofStar Guarantee Standards</i>.
+
;(7) [[SBS Roof Systems Standard#PART_9|'''Cap Field Membrane''']]: Applied according to manufacturer's printed instructions and to <i>RoofStar Guarantee Standards</i>.
;(8) [[SBS Roof Systems Standard#SBS-STRIPPING|'''Cap Membrane Flashing''']]: Applied according to manufacturer's printed instructions and to <i>RoofStar Guarantee Standards</i>. Must be tucked under metal flange and mechanically attached to the nailing strip.
+
;(8) [[SBS Roof Systems Standard#PART_10|'''Cap Membrane Flashing''']]: Applied according to manufacturer's printed instructions and to <i>RoofStar Guarantee Standards</i>. Must be tucked under metal flange and mechanically attached to the nailing strip.
;(9) [[SBS Roof Systems Standard#METALCAP-SBS|'''Metal Flashing''']]: Mechanically fasten, standing seam at corners. Full width base flashing optional on flexible membranes. Partial skirt flashing minimum 75 mm (3") required on mechanical curbs that require flashing under metal flange.
+
;(9) [[SBS Roof Systems Standard#PART_13|'''Metal Flashing''']]: Mechanically fasten, standing seam at corners. Full width base flashing optional on flexible membranes. Partial skirt flashing minimum 75 mm (3") required on mechanical curbs that require flashing under metal flange.
;(10) [[SBS Roof Systems Standard#METALCAP-SBS|'''Alternate Corner Cap (Shop-manufactured)''']]: Weld seams.  Bed in two parallel courses of butyl tape or acceptable sealant.  Mechanically fasten to outside face of curb flange.
+
;(10) [[SBS Roof Systems Standard#PART_13|'''Alternate Corner Cap (Shop-manufactured)''']]: Weld seams.  Bed in two parallel courses of butyl tape or acceptable sealant.  Mechanically fasten to outside face of curb flange.
 
;(11) '''Butyl Tape (sealant)'''
 
;(11) '''Butyl Tape (sealant)'''
;(12) [[SBS Roof Systems Standard#SBSMETALFASTENER|'''Fasteners''']]: Flanged fasteners with neoprene washers.
+
;(12) [[SBS Roof Systems Standard#PART_13|'''Fasteners''']]: Flanged fasteners with neoprene washers.
  
 
<hr>
 
<hr>
  
 
=== RELATED WORK BY OTHERS ===
 
=== RELATED WORK BY OTHERS ===
;(A) [[SBS Roof Systems Standard#SBSDECKS|'''Acceptable Supporting Deck Structure''']]
+
;(A) [[SBS Roof Systems Standard#PART_2|'''Acceptable Supporting Deck Structure''']]
;(B) [[SBS Roof Systems Standard#SBSAIRVAPOUR|'''Air or Vapour Control Layer Seal''']]
+
;(B) [[SBS Roof Systems Standard#PART_6|'''Air or Vapour Control Layer Seal''']]
 
;(C) '''Mechanical Curb''': Minimum 200 mm (8") above finished roof surface.
 
;(C) '''Mechanical Curb''': Minimum 200 mm (8") above finished roof surface.
 
:* Some mechanical curbs are designed to allow membrane flashing to be carried up onto metal flange. Install according to manufacturers&#8217; instructions.
 
:* Some mechanical curbs are designed to allow membrane flashing to be carried up onto metal flange. Install according to manufacturers&#8217; instructions.

Revision as of 18:58, 1 September 2021


Notice to Reader
Images used in a Construction Detail are representative and not prescriptive. Nor are they necessarily drawn to scale. Rather, they are provided to visually convey the requirements of the Standard they represent. Unless otherwise required by the Standard, dimensions, the selection of materials and their application remains the responsibility of the Design Authority.

The full text of the referenced requirements in the Standard may be read by using the blue hyperlinks
SBS Details

D1.7.6-4(1).jpg

D1.7.6-4 (2).jpg

Click below for a printable version of this page.
Print Sheet


1 WORK INCLUDED

(1) Supporting Deck Overlay
Required when insulation is too thin to span flutes of steel decking or when required as thermal barrier by design authority.
(2) Air or Vapour Control Layers
If required by design authority.
(3) Insulation
Mechanically fastened. See available insulation products in the Accepted Materials section of this Manual.
(4) Insulation Overlay
As required.
(5) Base Field Membrane
Adhered to overlay board using asphalt, cold adhesive, self-adhered, mechanical attachment or torch applied according to manufacturer's specification. Torching directly to wood surfaces is not permitted.
(6) Base Membrane Flashing
Adhered according to manufacturer's specifications, using cold adhesive, hot asphalt, self-adhered or torch applied to cover boards, or mechanically attached membrane. Must be tucked under metal flange and mechanically attached to nailing strip.
(7) Cap Field Membrane
Applied according to manufacturer's printed instructions and to RoofStar Guarantee Standards.
(8) Cap Membrane Flashing
Applied according to manufacturer's printed instructions and to RoofStar Guarantee Standards. Must be tucked under metal flange and mechanically attached to the nailing strip.
(9) Metal Flashing
Mechanically fasten, standing seam at corners. Full width base flashing optional on flexible membranes. Partial skirt flashing minimum 75 mm (3") required on mechanical curbs that require flashing under metal flange.
(10) Alternate Corner Cap (Shop-manufactured)
Weld seams. Bed in two parallel courses of butyl tape or acceptable sealant. Mechanically fasten to outside face of curb flange.
(11) Butyl Tape (sealant)
(12) Fasteners
Flanged fasteners with neoprene washers.

2 RELATED WORK BY OTHERS

(A) Acceptable Supporting Deck Structure
(B) Air or Vapour Control Layer Seal
(C) Mechanical Curb
Minimum 200 mm (8") above finished roof surface.
  • Some mechanical curbs are designed to allow membrane flashing to be carried up onto metal flange. Install according to manufacturers’ instructions.
(D) Rigid Insulation
(E) Wood Nailing Board
(F) Neoprene Gasket for RTU

NOTE: See the Standard for additional requirements.


Back to "SBS" Roof System Details