1 WORK INCLUDED
- (1) Underlayment
- Proprietary underlayment installed perpendicular to the slope with 50 mm (2") minimum side laps and 100 mm (4") minimum end laps.
- (2) Ice And Water Protection
- One ply of accepted self-adhered modified bituminous membrane.
- (3) Edge Metal Flashing
- Installed to manufacturer’s printed instructions.
- Note
- This specification is only applicable to slopes 1
- 3 (4" in 12") or greater
- Slip sheet not shown for clarity
2 RELATED WORK BY OTHERS
- (A) Acceptable Deck
- NOTE: * Refer to RGC Guarantee Standards for additional requirements.