Difference between revisions of "WP Details:F1.7.9 (Walls - Reglet & Counter-Flashings)"
Difference between revisions of "WP Details:F1.7.9 (Walls - Reglet & Counter-Flashings)"
(Created page with "<hr> File:9.6.9.jpg ==== WORK INCLUDED ==== (1) <b>Primary Waterproofing Membrane: </b>Fully adhered to acceptable substrates (concrete slab depicted), installed as per...") |
(→RELATED WORK BY OTHERS) |
||
Line 34: | Line 34: | ||
[[Section:F. Application: Waterproofing Plazas, Promenades and Terraces|<i class="fa fa-chevron-circle-left fa-2x" ></i> Back to ''Waterproofing Application'']] | [[Section:F. Application: Waterproofing Plazas, Promenades and Terraces|<i class="fa fa-chevron-circle-left fa-2x" ></i> Back to ''Waterproofing Application'']] | ||
− | [[Waterproofing Details|<i class="fa fa-chevron-circle-left fa-2x" ></i> Back to ''Waterproofing Construction Details'']] | + | [[Waterproofing Construction Details|<i class="fa fa-chevron-circle-left fa-2x" ></i> Back to ''Waterproofing Construction Details'']] |
[[Section:G. Construction Details|<i class="fa fa-chevron-circle-left fa-2x" ></i> Back to ''Construction Details'']] | [[Section:G. Construction Details|<i class="fa fa-chevron-circle-left fa-2x" ></i> Back to ''Construction Details'']] |
Revision as of 17:54, 23 December 2015
1 WORK INCLUDED
(1) Primary Waterproofing Membrane: Fully adhered to acceptable substrates (concrete slab depicted), installed as per RGC Guarantee Standards E and Membrane Manufacturer's installation specifications.
(2) Membrane Flashing (stripping): Carried up walls a minimum 200 mm (8") above membrane surface (Deck) and a minimum of 100mm (4") above top surface of permeable waterproofing wearing surfaces and overburdens.
(3) Membrane Primer or Adhesive: proprietary primer or adhesive, application and quantities as directed by membrane manufacturers published application specifications.
(4)Metal Base Flashing: Required on all waterproofing assemblies flashing lengths joined by use of S-locks or standing seam joints.
(5)Metal Counter Flashing: Set in reglet fastened with expanding type concrete pins, join flashing lengths by use of S-locks or standing seam joints.
(6) Fasteners: Suitable expanding type concrete pins.
(7) Caulking: Polyurethane sealant, fill void and tool smooth.
2 RELATED WORK BY OTHERS
(A)Concrete Wall: Must be dry, smooth and primed for membrane flashing to be adhered directly. (Plywood or fibre-mat reinforced cement board may be required).
(B)Reglet: minimum 75mm (3/4") in depth, saw cut or manufactured preformed reglet.
NOTE: Refer to RGC Guarantee Standards E for additional requirements.