=== WORK INCLUDED ===
+
{{DISPLAYTITLE:<span style="position: absolute; clip: rect(1px 1px 1px 1px); clip: rect(1px, 1px, 1px, 1px);">{{FULLPAGENAME}}</span>}}
 +
__NOTOC__
  
(1) <b>Gypsum Overlay Board: </b>If required by design authority.
+
<big><big>Division D - Construction Details</big></big>
 +
<hr>
 +
<big><big><big><big><big>SBS | Parapet-Wall Connection ([[SBS_Roof_Systems_Standard#10.3.4.1._Parapets | Article 10.3.4.1.]])</big></big></big></big></big>
 +
{{Template:Construction Details Header}}
 +
<div class="panel panel-success">
 +
<div class="panel-heading"><big>'''SBS Details'''</big></div>
 +
<div class="panel-body">
 +
<div class="col-md-6">
 +
<div style="text-align:center; vertical-align:center">
 +
[[File:10.3.1.4.jpg|class=img-responsive]]
 +
</div>
  
(2) <b>Vapour Retarder</b>: If required by design authority.
+
</div><!-- COL-MD-6 -->
  
(3) <b>Insulation:</b> See list of accepted materials in Section 2.2.
+
<div class="col-md-6">
 +
=== WORK INCLUDED ===
  
(4) <b>Insulation Overlay</b>: As required. See <i>RGC Guarantee Standard B4.1, B4.2 </i>and<i> C4.1</i>
+
;(1) [[SBS Roof Systems Standard#PART_5|'''Supporting Deck Overlay''']]: If required by design authority.
 +
;(2) [[SBS Roof Systems Standard#PART_6|'''Air or Vapour Control Layers''']]:If required by design authority.
 +
;(3) [[SBS Roof Systems Standard#PART_7|'''Insulation''']]:
 +
:See list of '''[[Division C: Accepted Materials|Accepted Materials]]'''.
 +
;(4) [[SBS Roof Systems Standard#PART_8|'''Insulation Overlay''']]:
 +
:As required.
 +
;(5) [[SBS Roof Systems Standard#PART_9|'''Primary Membrane''']] and [[RoofStar Guarantee Standards for SBS Modified Bitumen Roof Assemblies#SBSPROTECTION| '''Membrane Protection''']]:
 +
;(6) [[SBS Roof Systems Standard#PART_10|'''Membrane Flashing (attachment & termination)''']]: Mechanically fasten at terminations.  At least one ply must extend over outside edge.
 +
;(7) [[SBS Roof Systems Standard#PART_13|'''Metal Base Flashing''']]: Optional on flexible membrane systems. Required on assemblies using gravel ballast filter mats.
 +
;(8) [[SBS Roof Systems Standard#PART_13|'''Metal Cap Flashing''']]: Must overlap exterior wall finish. Fasten with  concealed clip-type fasteners  <b>or</b> cladding screws evenly spaced between seams.
 +
;(9) [[SBS Roof Systems Standard#PART_10|'''Wall Tie-in''']]: Minimum 2 mm (0.078") self-adhered  modified bitumen or flexible membrane manufacturers approved detail.
 +
;(10)[[SBS Roof Systems Standard#PART_13|'''Metal Counter-flashing''']]:
  
(5) <b>Primary Membrane and Membrane Protection</b>
+
<hr>
 
 
(6) <b>Membrane Flashing:</b> Mechanically fasten at terminations.  At least one ply must extend over outside edge. See <i>RGC Guarantee Standard A5.6</i>
 
 
 
(7)<b> Metal Base Flashing:</b> Optional on flexible membrane systems. Required on assemblies using gravel ballast filter mats. See <i>RGC Guarantee Standard A6.9</i>
 
 
 
(8) <b>Metal Cap Flashing:</b> Must overlap exterior wall finish. See <i>RGC Guarantee Standard A6.9 </i>Fasten with  concealed clip-type fasteners  <b>or</b> cladding screws evenly spaced between seams. See <i>RGC Guarantee Standard A6.10.</i>
 
 
 
(9) <b>Wall Tie-In Membrane:</b> Minimum 2 mm (0.078") self-adhered  modified bitumen or flexible membrane manufacturer&#8217;s approved detail.
 
 
 
(10) <b>Metal Counter Flashing</b>
 
  
 
=== RELATED WORK BY OTHERS ===
 
=== RELATED WORK BY OTHERS ===
  
(A) <b>Acceptable Deck</b>
+
;(A) [[SBS Roof Systems Standard#PART_2|'''Acceptable Supporting Deck Structure''']]
 
+
;(B) [[SBS Roof Systems Standard#PART_6|'''Air and Vapour Control Layer Seal''']]
(B) <b>Air / Vapour Seal</b>
+
;(C) [[SBS Roof Systems Standard#PART_2|'''Acceptable Wall Surface''']]
 
+
;(D) [[SBS Roof Systems Standard#PART_10|'''Wood Blocking''']]
(C) <b>Acceptable Wall Surface</b>
+
;(E) [[SBS Roof Systems Standard#PART_10|'''Sloped Wood Blocking''']]
 
+
:Required over 100 mm (4") parapet width.
(D) <b>Wood Blocking</b>
+
;(F) [[SBS Roof Systems Standard#PART_10|'''Wall Sheathing Membrane''']]: Minimum 1 mm (0.040") self-adhered modified bitumen.
 
+
;(G) <b>Wall Cladding</b>
(E) <b>Sloped Wood Blocking:</b> Required over 100 mm (4") parapet width. See <i>RGC Guarantee Standard A6.9</i>
+
</div><!-- COL-6-MD -->
 
+
</div><!-- PANEL BODY -->
(F) <b>Wall Sheathing Membrane</b>
+
</div><!-- PANEL -->
 
 
(G) <b>Wall Cladding</b>
 
 
 
 
 
'''NOTE''': Refer to <i>RGC Guarantee Standards</i> for additional requirements.
 
  
 +
'''NOTE''': See the [[SBS Roof Systems Standard | '''Standard''']] for additional requirements.
  
 
<hr>
 
<hr>
  
 +
[[SBS Roof System Details|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''"SBS" Roof System Details'']]
  
 +
[[Main Page | <i class="fa fa-home fa"></i> Home]]
  
 
+
{{Tempate:RPM Page Footer with Copyright and Current Date}}
[[Section:D. Application: Low Slope Roofs|<i class="fa fa-chevron-circle-left fa-2x" ></i> Back to ''SBS Application'']]
 
 
 
[[SBS Construction Details|<i class="fa fa-chevron-circle-left fa-2x" ></i> Back to ''SBS Construction Details'']]
 
 
 
[[Section:G. Construction Details|<i class="fa fa-chevron-circle-left fa-2x" ></i> Back to ''Construction Details'']]
 

Latest revision as of 17:50, 27 October 2023



Division D - Construction Details


SBS | Parapet-Wall Connection ( Article 10.3.4.1.)

Notice to Reader
Images used in a Construction Detail are representative and not prescriptive, and are not necessarily drawn to scale. They are intended to support the related Standard (Ref. Division A, Article 2.2.1.2.).

The reader may link to the related Article in the detail title, or link to the Standard as it relates to a specific element in the detail. All hyperlinks are displayed blue text.

SBS Details

10.3.1.4.jpg

1 WORK INCLUDED

(1) Supporting Deck Overlay
If required by design authority.
(2) Air or Vapour Control Layers
If required by design authority.
(3) Insulation
See list of Accepted Materials.
(4) Insulation Overlay
As required.
(5) Primary Membrane and Membrane Protection
(6) Membrane Flashing (attachment & termination)
Mechanically fasten at terminations. At least one ply must extend over outside edge.
(7) Metal Base Flashing
Optional on flexible membrane systems. Required on assemblies using gravel ballast filter mats.
(8) Metal Cap Flashing
Must overlap exterior wall finish. Fasten with concealed clip-type fasteners or cladding screws evenly spaced between seams.
(9) Wall Tie-in
Minimum 2 mm (0.078") self-adhered modified bitumen or flexible membrane manufacturers approved detail.
(10)Metal Counter-flashing

2 RELATED WORK BY OTHERS

(A) Acceptable Supporting Deck Structure
(B) Air and Vapour Control Layer Seal
(C) Acceptable Wall Surface
(D) Wood Blocking
(E) Sloped Wood Blocking
Required over 100 mm (4") parapet width.
(F) Wall Sheathing Membrane
Minimum 1 mm (0.040") self-adhered modified bitumen.
(G) Wall Cladding

NOTE: See the Standard for additional requirements.


Back to "SBS" Roof System Details

Home

© RCABC 2024
RoofStarTM is a registered Trademark of the RCABC.