Difference between revisions of "TPO Roof System Details"

Jump to: navigation, search

Difference between revisions of "TPO Roof System Details"

(Part 10 - Perimeters and Walls)
 
(47 intermediate revisions by the same user not shown)
Line 1: Line 1:
The drawings contained within this section are intended to represent a variety of modified bituminous roof system designs while remaining generic with regards to manufacturers’ specific application specifications. They do not represent all possible manufacturer application roof system designs. Consult manufacturers’ specifications and RoofStar Guarantee Standards to develop a system acceptable to both the manufacturer and RGC.
+
{{Template:RPM Info}}
  
For further information about SBS membrane system designs, see '''[[TPO/PVC (Thermoplastic Membranes) Roof Systems]]'''.
+
__NONUMBEREDHEADINGS__
 +
{{DISPLAYTITLE:<span style="position: absolute; clip: rect(1px 1px 1px 1px); clip: rect(1px, 1px, 1px, 1px);">{{FULLPAGENAME}}</span>}}
 +
__NOTOC__
  
 +
:<big><big>Division D - Construction Details</big></big>
 +
:<hr>
 +
:<big><big><big><big><big>Construction Details for TPO Membrane Roof Systems</big></big></big></big></big>
  
:[[TPO Details:D3.7.1 (Mechanically Attached Generic Conventional Assembly)|D3.7.1 Mechanically Attached Generic Conventional Assembly]]
+
<div class="col-md-2">
:[[TPO Details:D3.7.2 (Fully Adhered)|D3.7.2 Fully Adhered]]
+
:[[File:TPO project (courtesy Carlisle Syntec).jpg| link=http://rpm.rcabc.org/images/5/58/TPO_project_%28courtesy_Carlisle_Syntec%29.jpg | 175 px]]
:[[TPO Details:D3.7.3 (Ballasted Protected Membrane)|D3.7.3 Ballasted Protected Membrane]]
+
</div>
:[[TPO Details:D3.7.4 (Curb Opening)|D3.7.4 Curb Opening]]
 
:[[TPO Details:D3.7.5 (Clamping Copper Drain)|D3.7.5 Clamping Copper Drain]]
 
:[[TPO Details:D3.7.6 (Two-Part Box Flashing)|D3.7.6 Two-Part Box Flashing]]
 
:[[TPO Details:D3.7.7 (Mechanical Curb Opening)|D3.7.7 Mechanical Curb Opening]]
 
:[[TPO Details:D3.7.8 (Roof Edge)|D3.7.8 Roof Edge]]
 
  
 +
<div class="col-md-10">
 +
:The drawings linked on this page are intended to represent a variety of TPO Membrane roof system applications while remaining generic with regards to manufacturers&#8217; specific application specifications. They do not represent all possible ''manufacturer'' application roof system designs. Consult each ''manufacturer's'' specifications and the '''''RoofStar Guarantee Standards''''' to develop a system acceptable to both the manufacturer and the '''''RoofStar Guarantee Program'''''.
 +
 +
:For further information about TPO Membrane System designs and requirements, see the '''[https://rpm.rcabc.org/index.php?title=TPO_Roof_Systems_Standard Standard for TPO Membrane Roof Systems]'''.
 +
</div>
 +
 +
<div class="col-md-12">
 +
</div>
 +
<div class="col-md-4">
 +
<hr>
 +
===Part 1 - General===
 +
====='''Permitted Roof Systems''' ([[TPO_Roof_Systems_Standard#1.1.3.1._Permitted_Roof_Systems | Article 1.1.3.1.]])=====
 +
<ol>
 +
<li>[[TPO Conventionally Insulated System (Typical)| Conventionally Insulated System (Typical)]]
 +
<li>[[TPO Conventionally Insulated System (Alternate) | Conventionally Insulated System (Alternate)]]
 +
<li>[[TPO Protected Roof Assembly (Typical)  | Protected Roof Assembly (Typical)]]
 +
</li></ol>
 +
 +
===Part 6 - Air and Vapour Controls===
 +
====='''Continuity and Support''' ([[TPO_Roof_Systems_Standard#6.3.2.1._Continuity_and_Support | Article 6.3.2.1.]])=====
 +
<ol>
 +
<li>[[TPO Air and Vapour Controls (Field) | {{hilite | Air and Vapour Controls (Field)|| 2021-February-7 }}]]
 +
</li></ol>
 +
 +
 +
</div>
 +
<div class="col-md-4">
 
<hr>
 
<hr>
  
:'''NOTE''': The following pages are currently under construction
+
===Part 10 - Perimeters and Walls===
 +
====='''General Application''' ([[TPO_Roof_Systems_Standard#10.3.2.3._General_Application_Requirements_for_Perimeters_and_Walls | Article 10.3.2.3.]])=====
 +
<ol>
 +
<li>[[TPO Membrane Termination A | Membrane Termination A]]
 +
<li>[[TPO Membrane Termination B | Membrane Termination B]]
 +
<li>[[TPO Membrane Termination C | Membrane Termination C]]
 +
<li>[[TPO Membrane Termination D | Membrane Termination D]]
 +
<li>[[TPO Membrane Termination E | Membrane Termination E]]
 +
<li>[[TPO Membrane Termination F | Membrane Termination F]]
 +
</li></ol>
  
:[[TPO Details:D3.7.1 Assemblies (Insulated Conventional)|D3.7.1 Assemblies (Insulated Conventional)(Under Construction)]]
+
====='''Low-profile Edges''' ([[TPO_Roof_Systems_Standard#10.3.4.2._Low_Profile_Edges | Article 10.3.4.2.]])=====
:[[TPO Details:D3.7.2 Assemblies (Protected Membrane)|D3.7.2 Assemblies (Protected Membrane)(Under Construction)]]
+
<ol>
:[[TPO Details:D3.7.3 Parapets & Copings (High - Wall Supported)|D3.7.3 Parapets & Copings (High - Wall Supported)(Under Construction)]]
+
<li>[[TPO Metal Edge Termination | Metal Edge Termination]]
:[[TPO Details:D3.7.4 Parapets & Copings (Parapet - Wall Transition)|D3.7.4 Parapets & Copings (Parapet - Wall Transition)(Under Construction)]]
+
</li></ol>
:[[TPO Details:D3.7.5 Edges & Fascia (Cant Edge)|D3.7.5 Edges & Fascia (Cant Edge)(Under Construction)]]
 
:[[TPO Details:D3.7.6 Edges & Fascia (Gravel Stop)|D3.7.6 Edges & Fascia (Gravel Stop)(Under Construction)]]
 
:[[TPO Details:D3.7.7 Edges & Fascia (Flat Edge Termination)|D3.7.7 Edges & Fascia (Flat Edge Termination)(Under Construction)]]
 
:[[TPO Details:D3.7.8 Counter-flashings & Reglets (Deck - Wall Supported)|D3.7.8 Counter-flashings & Reglets (Deck - Wall Supported)(Under Construction)]]
 
:[[TPO Details:D3.7.9 Counter-flashings & Reglets (Deck - Unsupported by Wall)|D3.7.9 Counter-flashings & Reglets (Deck - Unsupported by Wall)(Under Construction)]]
 
:[[TPO Details:D3.7.10 Counter-flashings & Reglets (Stucco Wall: Re-roofing)|D3.7.10 Counter-flashings & Reglets (Stucco Wall: Re-roofing)(Under Construction)]]
 
:[[TPO Details:D3.7.11 Counter-flashings & Reglets (Stucco Wall: New)|D3.7.11 Counter-flashings & Reglets (Stucco Wall: New)(Under Construction)]]
 
:[[TPO Details:D3.7.12 Counter-flashings & Reglets (Double Surface Reglet)|D3.7.12 Counter-flashings & Reglets (Double Surface Reglet)(Under Construction)]]
 
:[[TPO Details:D3.7.13 Counter-flashings & Reglets (Low Door Sill)|D3.7.13 Counter-flashings & Reglets (Low Door Sill)(Under Construction)]]
 
:[[TPO Details:D3.7.14 Counter-flashings & Reglets (Window Curb)|D3.7.14 Counter-flashings & Reglets (Window Curb)(Under Construction)]]
 
:[[TPO Details:D3.7.15 Roof-Wall Transitions (Expansion Joint)|D3.7.15 Roof-Wall Transitions (Expansion Joint)(Under Construction)]]
 
:[[TPO Details:D3.7.16 Roof-Wall Transitions (Divider/Control Joint)|D3.7.16 Roof-Wall Transitions (Divider/Control Joint)(Under Construction)]]
 
:[[TPO Details:D3.7.17 Roof-Wall Transitions (Fire Separation Joint)|D3.7.17 Roof-Wall Transitions (Fire Separation Joint)(Under Construction)]]
 
:[[TPO Details:D3.7.18 Roof-Wall Transitions (Fire Separation Wall)|D3.7.18 Roof-Wall Transitions (Fire Separation Wall)(Under Construction)]]
 
:[[TPO Details:D3.7.19 Curbs & Sleepers (Equipment Sleeper)|D3.7.19 Curbs & Sleepers (Equipment Sleeper)(Under Construction)]]
 
:[[TPO Details:D3.7.20 Curbs & Sleepers (Multiple Roof Penetrations)|D3.7.20 Curbs & Sleepers (Multiple Roof Penetrations)(Under Construction)]]
 
:[[TPO Details:D3.7.21 Curbs & Sleepers (Basic Curb)|D3.7.21 Curbs & Sleepers (Basic Curb)(Under Construction)]]
 
:[[TPO Details:D3.7.22 Curbs & Sleepers (Mechanical Opening)|D3.7.22 Curbs & Sleepers (Mechanical Opening)(Under Construction)]]
 
:[[TPO Details:D3.7.23 Curbs & Sleepers (Pre-curb for Planters)|D3.7.23 Curbs & Sleepers (Pre-curb for Planters)(Under Construction)]]
 
:[[TPO Details:D3.7.24 Strip-in Flashings (Metal Plumbing)|D3.7.24 Strip-in Flashings (Metal Plumbing)(Under Construction)]]
 
:[[TPO Details:D3.7.25 Strip-in Flashings (Two-part Cable)|D3.7.25 Strip-in Flashings (Two-part Cable)(Under Construction)]]
 
:[[TPO Details:D3.7.26 Strip-in Flashings (Pourable Sealer Pocket)|D3.7.26 Strip-in Flashings (Pourable Sealer Pocket)(Under Construction)]]
 
:[[TPO Details:D3.7.27 Water & Drainage (Cast Iron Drain)|D3.7.27 Water & Drainage (Cast Iron Drain)(Under Construction)]]
 
:[[TPO Details:D3.7.28 Water & Drainage (Spun Copper Drain)|D3.7.28 Water & Drainage (Spun Copper Drain)(Under Construction)]]
 
:[[TPO Details:D3.7.29 Water & Drainage (Clamping Spun Copper Drain)|D3.7.29 Water & Drainage (Clamping Spun Copper Drain)(Under Construction)]]
 
:[[TPO Details:D3.7.30 Water & Drainage (Open Wall Scupper)|D3.7.30 Water & Drainage (Open Wall Scupper)(Under Construction)]]
 
:[[TPO Details:D3.7.31 Water & Drainage (Through-wall Scupper)|D3.7.31 Water & Drainage (Through-wall Scupper)(Under Construction)]]
 
:[[TPO Details:D3.7.32 Miscellaneous Penetrations (Roof Anchor)|D3.7.32 Miscellaneous Penetrations (Roof Anchor)(Under Construction)]]
 
:[[TPO Details:D3.7.33 Miscellaneous Penetrations (Wall Anchor - Conventional Roof Assy)|D3.7.33 Miscellaneous Penetrations (Wall Anchor - Conventional Roof Assy)(Under Construction)]]
 
:[[TPO Details:D3.7.34 Miscellaneous Penetrations (Wall Anchor - Protected Roof Assy)|D3.7.34 Miscellaneous Penetrations (Wall Anchor - Protected Roof Assy)(Under Construction)]]
 
  
 +
===Part 11 - Drainage===
 +
 +
</div>
 +
<div class="col-md-4">
 
<hr>
 
<hr>
  
 +
===Part 12 - Penetrations and Curbs===
  
 +
===Part 13 - Linear Metal Flashing===
 +
:See the separate page, [[Linear_Metal_Flashing_Details | Construction Details for Linear Metal Flashings]].
  
 +
===Part 14 - The Roof as a Platform===
 +
 +
</div>
 +
 +
<div class="col-md-12">
 +
<hr>
  
[[TPO/PVC (Thermoplastic Membranes) Roof Systems|<i class="fa fa-chevron-circle-left fa-2x" ></i> Back to ''TPO/PVC Roof Systems'']]
+
[[TPO Roof Systems Standard|<i class="fa fa-chevron-circle-left" ></i> ''Standard for TPO Membrane Roof Systems'']]
  
[[Section:G. Construction Details|<i class="fa fa-chevron-circle-left fa-2x" ></i> Back to ''Construction Details Section'']]
+
[[Main Page | <i class="fa fa-home fa"></i> Home]]
 +
{{Template:RPM Page Footer with Copyright and Current Date}}
 +
</div>

Latest revision as of 16:39, 26 February 2024



Division D - Construction Details

Construction Details for TPO Membrane Roof Systems
TPO project (courtesy Carlisle Syntec).jpg
The drawings linked on this page are intended to represent a variety of TPO Membrane roof system applications while remaining generic with regards to manufacturers’ specific application specifications. They do not represent all possible manufacturer application roof system designs. Consult each manufacturer's specifications and the RoofStar Guarantee Standards to develop a system acceptable to both the manufacturer and the RoofStar Guarantee Program.
For further information about TPO Membrane System designs and requirements, see the Standard for TPO Membrane Roof Systems.

Part 12 - Penetrations and Curbs

Part 13 - Linear Metal Flashing

See the separate page, Construction Details for Linear Metal Flashings.

Part 14 - The Roof as a Platform


Standard for TPO Membrane Roof Systems

Home

© RCABC 2024
RoofStarTM is a registered Trademark of the RCABC.
No reproduction of this material, in whole or in part, is lawful without the expressed permission of the RCABC Guarantee Corp.