Line 1: Line 1:
The drawings contained within this section are intended to represent a variety of modified bituminous roof system applications while remaining generic with regards to manufacturers’ specific application specifications. They do not represent all possible manufacturer application roof system designs. Consult manufacturers’ specifications and RoofStar Guarantee Standards to develop a system acceptable to both the manufacturer and RGC.
+
{{Template:RPM Info}}
 +
__NONUMBEREDHEADINGS__
 +
{{DISPLAYTITLE:<span style="position: absolute; clip: rect(1px 1px 1px 1px); clip: rect(1px, 1px, 1px, 1px);">{{FULLPAGENAME}}</span>}}
 +
__NOTOC__
  
For further information about SBS membrane system design and requirements, see '''[[SBS Roof Systems|SBS Roof Systems]]'''.
+
:<big><big>Division D - Construction Details</big></big>
 +
:<hr>
 +
:<big><big><big><big><big>Construction Details for SBS-modified Bitumen Membrane Roof Systems</big></big></big></big></big>
  
<div class="col-md-6">
+
<div class="col-md-2">
:[[SBS Details:D1.7.1-1 Assemblies (Insulated Conventional)|D1.7.1-1 Assemblies (Insulated Conventional)]]
+
:[[File:SBS Systems page thumb.JPG | link=http://rpm.rcabc.org/images/6/62/SBS_Systems_page_thumb.JPG |225 px]]
:[[SBS Details:D1.7.1-2 Assemblies (Protected Membrane)|D1.7.1-2 Assemblies (Protected Membrane)]]
+
:<small><small>Photo Credit: RCABC Image Library</small></small>
 +
</div>
  
:[[SBS Details:D1.7.2-1 Parapets & Copings (Low Parapet - Wall Supported)|D1.7.2-1 Parapets & Copings (Low Parapet - Wall Supported)]]
+
<div class="col-md-10">
:[[SBS Details:D1.7.2-2 Parapets & Copings (Low Parapet - Unsupported by Wall)|D1.7.2-2 Parapets & Copings (Low Parapet - Unsupported by Wall)]]
+
:The drawings linked on this page are intended to represent a variety of SBS-modified Bitumen Membrane roof system applications while remaining generic with regards to manufacturers&#8217; specific application specifications. They do not represent all possible manufacturer application roof system designs. Consult each manufacturers&#8217; specifications and the '''''RoofStar Guarantee Standards''''' to develop a system acceptable to both the manufacturer and the '''''RoofStar Guarantee Program'''''.
:[[SBS Details:D1.7.2-3 Parapets & Copings (High Parapet - Wall Supported)|D1.7.2-3 Parapets & Copings (High Parapet - Wall Supported)]]
 
:[[SBS Details:D1.7.2-4 Parapets & Copings (Parapet - Wall Transition)|D1.7.2-4 Parapets & Copings (Parapet - Wall Transition)]]
 
  
:[[SBS Details:D1.7.3-1 Edges & Fascia (Cant Edge)|D1.7.3-1 Edges & Fascia (Cant Edge)]]
+
:For further information about SBS-modified Bitumen Membrane System designs and requirements, see the '''[http://rpm.rcabc.org/index.php?title=SBS_Roof_Systems_Standard Standard for SBS-modified Bitumen Membrane Roof Systems]'''.
:[[SBS Details:D1.7.3-2 Edges & Fascia (Gravel Stop)|D1.7.3-2 Edges & Fascia (Gravel Stop)]]
+
</div>
  
:[[SBS Details:D1.7.4-1 Counter-flashings & Reglets (Deck - Wall Supported)|D1.7.4-1 Counter-flashings & Reglets (Deck - Wall Supported)]]
+
<div class="col-md-12">
:[[SBS Details:D1.7.4-2 Counter-flashings & Reglets (Deck - Unsupported by Wall)|D1.7.4-2 Counter-flashings & Reglets (Deck - Unsupported by Wall)]]
 
:[[SBS Details:D1.7.4-3 Counter-flashings & Reglets (Stucco Wall: Re-roofing)|D1.7.4-3 Counter-flashings & Reglets (Stucco Wall: Re-roofing)]]
 
:[[SBS Details:D1.7.4-4 Counter-flashings & Reglets (Stucco Wall: New)|D1.7.4-4 Counter-flashings & Reglets (Stucco Wall: New)('''Under Construction''')]]
 
:[[SBS Details:D1.7.4-5 Counter-flashings & Reglets (Double Surface Reglet)|D1.7.4-5 Counter-flashings & Reglets (Double Surface Reglet)]]
 
:[[SBS Details:D1.7.4-6 Counter-flashings & Reglets (Low Door Sill)|D1.7.4-6 Counter-flashings & Reglets (Low Door Sill)]]
 
:[[SBS Details:D1.7.4-7 Counter-flashings & Reglets (Window Curb)|D1.7.4-7 Counter-flashings & Reglets (Window Curb)]]
 
 
</div>
 
</div>
<div class="col-md-6">
+
<div class="col-md-4">
:[[SBS Details:D1.7.5-1 Roof-Wall Transitions (Expansion Joint)|D1.7.5-1 Roof-Wall Transitions (Expansion Joint)]]
+
<hr>
:[[SBS Details:D1.7.5-2 Roof-Wall Transitions (Divider/Joint)|D1.7.5-2 Roof-Wall Transitions (Divider/Control Joint)]]
+
===Part 1 - General===
:[[SBS Details:D1.7.5-3 Roof-Wall Transitions (Fire Separation Joint)|D1.7.5-3 Roof-Wall Transitions (Fire Separation Joint)]]
+
====='''Permitted Roof Systems''' ([[SBS_Roof_Systems_Standard#1.1.3.1._Permitted_Roof_Systems | Article 1.1.3.1.]])=====
:[[SBS Details:D1.7.5-4 Roof-Wall Transitions (Fire Separation Wall)|D1.7.5-4 Roof-Wall Transitions (Fire Separation Wall)]]
+
<ol>
 +
<li>[[SBS Conventionally Insulated System (typical) | {{hilite | Conventionally Insulated System (Typical)|| 2021-February-7 }}]]
 +
<li>[[SBS Conventionally Insulated System (alternate) | {{hilite | Conventionally Insulated System (Alternate)|| 2021-February-7 }}]]
 +
<li>[[SBS Protected Roof Assembly (typical) | {{hilite | Protected Roof Assembly (Typical) || 2021-February-7 }}]]
 +
</li></ol>
 +
 
 +
===Part 6 - Air and Vapour Controls===
 +
====='''Continuity and Support''' ([[SBS_Roof_Systems_Standard#6.3.2.1._Continuity_and_Support | Article 6.3.2.1.]])=====
 +
<ol>
 +
<li>[[SBS Air and Vapour Controls (field)| {{hilite | Air and Vapour Controls (Field)|| 2021-February-7 }}]]
 +
</li></ol>
  
:[[SBS Details:D1.7.20 Curbs & Sleepers (Equipment Sleeper)|D1.7.20 Curbs & Sleepers (Equipment Sleeper)]]
+
===Part 10 - Perimeters and Walls===
:[[SBS Details:D1.7.21 Curbs & Sleepers (Multiple Roof Penetrations)|D1.7.21 Curbs & Sleepers (Multiple Roof Penetrations)]]
+
====='''General Application''' ([[SBS_Roof_Systems_Standard#10.3.2.3._General_Application_Requirements_for_Perimeters_and_Walls | Article 10.3.2.3.]])=====
:[[SBS Details:D1.7.22 Curbs & Sleepers (Basic Curb)|D1.7.22 Curbs & Sleepers (Basic Curb)]]
+
<ol>
:[[SBS Details:D1.7.23 Curbs & Sleepers (Mechanical Opening)|D1.7.23 Curbs & Sleepers (Mechanical Opening)]]
+
<li>[[SBS Membrane Termination A | Membrane Termination A]]
:[[SBS Details:D1.7.24 Curbs & Sleepers (Pre-curb for Planters)|D1.7.24 Curbs & Sleepers (Pre-curb for Planters)]]
+
<li>[[SBS Membrane Termination B | Membrane Termination B]]
 +
<li>[[SBS Membrane Termination C | Membrane Termination C]]
 +
<li>[[SBS Membrane Termination D | Membrane Termination D]]
 +
<li>[[SBS Membrane Termination E | Membrane Termination E]]
 +
<li>[[SBS Membrane Termination F | Membrane Termination F]]
 +
</li></ol>
  
:[[SBS Details:D1.7.25 Strip-in Flashings (Metal Plumbing)|D1.7.25 Strip-in Flashings (Metal Plumbing)]]
+
====='''Parapets''' ([[SBS_Roof_Systems_Standard#10.3.4.1._Parapets | Article 10.3.4.1.]])=====
:[[SBS Details:D1.7.26 Strip-in Flashings (Two-part Cable)|D1.7.26 Strip-in Flashings (Two-part Cable)]]
+
<ol>
:[[SBS Details:D1.7.27 Strip-in Flashings (Gum Pan/Pitch Pocket)|D1.7.27 Strip-in Flashings (Gum Pan/Pitch Pocket)]]
+
<li>[[SBS Parapet (Typical)| Parapet (Typical)]]
 +
<li>[[SBS Parapet (Independent of Roof Structure) | Parapet (Independent of Roof Structure)]]  
 +
<li>[[SBS Tall Parapet | Tall Parapet]]
 +
<li>[[SBS Parapet-Wall Connection | Parapet-Wall Connection]]
 +
</li></ol>
 +
 
 +
====='''Low-profile Edges''' ([[SBS_Roof_Systems_Standard#10.3.4.2._Low_Profile_Edges | Article 10.3.4.2.]])=====
 +
<ol>
 +
<li>[[SBS Metal Edge Termination| {{hilite | Metal Edge Termination|| 2021-February-7 }}]]
 +
<li>[[SBS Canted Edge | {{hilite | Canted Edge|| 2021-February-7 }}]]
 +
</li></ol>
  
:[[SBS Details:D1.7.28 Water & Drainage (Cast Iron Drain)|D1.7.28 Water & Drainage (Cast Iron Drain)]]
 
:[[SBS Details:D1.7.29 Water & Drainage (Spun Copper Drain)|D1.7.29 Water & Drainage (Spun Copper Drain)]]
 
:[[SBS Details:D1.7.30 Water & Drainage (Clamping Spun Copper Drain)|D1.7.30 Water & Drainage (Clamping Spun Copper Drain)]]
 
:[[SBS Details:D1.7.31 Water & Drainage (Open Wall Scupper)|D1.7.31 Water & Drainage (Open Wall Scupper)]]
 
:[[SBS Details:D1.7.32 Water & Drainage (Through-wall Scupper)|D1.7.32 Water & Drainage (Through-wall Scupper)]]
 
  
:[[SBS Details:D1.7.33 Miscellaneous Penetrations (Roof Anchor)|D1.7.33 Miscellaneous Penetrations (Roof Anchor)]]
 
:[[SBS Details:D1.7.34 Miscellaneous Penetrations (Wall Anchor - Conventional Roof Assy)|D1.7.34 Miscellaneous Penetrations (Wall Anchor - Conventional Roof Assy)]]
 
:[[SBS Details:D1.7.35 Miscellaneous Penetrations (Wall Anchor - Protected Roof Assy)|D1.7.35 Miscellaneous Penetrations (Wall Anchor - Protected Roof Assy)]]
 
:[[SBS Details:D1.7.36 Miscellaneous Penetrations (Guardrails)|D1.7.36 Miscellaneous Penetrations (Guardrails)]]
 
 
</div>
 
</div>
 +
<div class="col-md-4">
 +
<hr>
 +
 +
===Part 10 (continued)===
 +
====='''Fire Separations''' ([[SBS_Roof_Systems_Standard#10.3.4.4._Fire_Separation_Walls | Article 10.3.4.4.]])=====
 +
<ol>
 +
<li>[[SBS Fire Separation Joint |Fire Separation Joint]]
 +
<li>[[SBS Fire Separation Wall | Fire Separation Wall]]
 +
</li></ol>
 +
 +
====='''Doors, Windows, and Wall Openings''' ([[SBS_Roof_Systems_Standard#10.3.4.5._Doors.2C_Windows.2C_and_Wall_Openings | Article 10.3.4.5.]])=====
 +
<ol>
 +
<li>[[SBS Low Door Opening | {{hilite | Low Door Opening || 2022-February-5 }}]]
 +
<li>[[SBS Window Opening | Window Opening]]
 +
</li></ol>
 +
 +
====='''Expansion Joints''' ([[SBS_Roof_Systems_Standard#10.3.6.1._Expansion_Joints | Article 10.3.6.1.]])=====
 +
<ol>
 +
<li>[[SBS Expansion Joint (Wall) | Expansion Joint (Wall)]]
 +
<li>[[SBS Expansion Joint (Field)| Expansion Joint (Field)]]
 +
</li></ol>
 +
 +
====='''Control Joints (Roof Dividers)''' ([[SBS_Roof_Systems_Standard#10.3.6.2._Control_Joints_.28Roof_Dividers.29 | Article 10.3.6.2.]])=====
 +
<ol>
 +
<li>[[SBS Control Joint (Roof Divider)| Control Joint (Roof Divider)]]
 +
</li></ol>
 +
 +
===Part 11 - Drainage===
 +
====='''Cast-iron Roof Drains''' ([[SBS_Roof_Systems_Standard#11.3.3.2._General_Requirements_for_Cast-iron_Roof_Drains | Article 11.3.3.2.]])=====
 +
<ol>
 +
<li>[[SBS 11.3.2.2-1 Cast Iron Drains| Cast Iron Drains]]
 +
</li></ol>
 +
 +
====='''Flanged Insert-type Roof Drains''' ([[SBS_Roof_Systems_Standard#11.3.3.6._Flanged_Insert-type_Roof_Drains | Article 11.3.3.6.]])=====
 +
<ol>
 +
<li>[[SBS Flanged Insert Drain| Flanged Insert Drain]]
 +
<li>[[SBS Flanged Insert Drain (Clamping Ring)| Flanged Insert Drain (Clamping Ring)]]
 +
</li></ol>
 +
 +
====='''Scuppers and Overflows''' ([[SBS_Roof_Systems_Standard#11.3.3.7._Scuppers_and_Overflows | Article 11.3.3.7.]])=====
 +
<ol>
 +
<li>[[SBS Open-wall Scupper Drain | Open-wall Scupper Drain ]]
 +
<li>[[SBS Through-wall Scupper Drain | Through-wall Scupper Drain ]]
 +
</li></ol>
  
 +
</div>
 +
<div class="col-md-4">
 
<hr>
 
<hr>
  
 +
===Part 12 - Penetrations and Curbs===
 +
 +
====='''Flashing Penetrations''' ([[SBS_Roof_Systems_Standard#12.3.2.1._General_Requirements_for_Flashing_Penetrations | Article 12.3.2.1.]])=====
 +
<ol>
 +
<li>[[SBS Plumbing Vent (Conventional Roof System)| Plumbing Vent (Conventional Roof System)]]
 +
<li>[[SBS 2-Part Retrofit Flashing (Cable Penetration) | {{hilite | 2-Part Retrofit Flashing (Cable Penetration) || 2021-February-7 }}]]
 +
<li>[[SBS Fall Protection Anchor in Roof | Fall Protection Anchor in Roof]]
 +
<li>[[SBS Fall Protection Anchor in Wall  | Fall Protection Anchor in Wall]]
 +
<li>[[SBS Fall Protection Anchor in Wall (Protected) | SBS Fall Protection Anchor in Wall (Protected Roof System)]]
 +
</li></ol>
 +
 +
====='''Curbs, Sleepers, and Equipment Pads''' ([[SBS_Roof_Systems_Standard#12.3.2.4._Curbs.2C_Sleepers.2C_and_Equipment_Pads | Article 12.3.2.4.]])=====
 +
<ol>
 +
<li>[[SBS Basic Curb| {{hilite | Basic Curb || 2021-February-7 }}]]
 +
<li>[[SBS Curb for Multiple Penetrations| Curb for Multiple Penetrations]]
 +
<li>[[SBS Mechanical Equipment Curb| Mechanical Equipment Curb]]
 +
<li>[[SBS Equipment Sleeper | Equipment Sleeper]]
 +
</li></ol>
 +
 +
====='''Railings, Ladders, and Other Attached Structures''' ([[SBS_Roof_Systems_Standard#12.3.2.7._Railings.2C_Ladders.2C_and_Other_Attached_Structures | Article 12.3.2.7.]])=====
 +
<ol>
 +
<li>[[SBS Railing | Railing]]
 +
</li></ol>
 +
 +
====='''Sealant Pockets''' ([[SBS_Roof_Systems_Standard#12.3.2.8._Sealant_Pockets | Article 12.3.2.8.]])=====
 +
<ol>
 +
<li>[[SBS Sealant Pocket| Sealant Pocket]]
 +
</li></ol>
 +
 +
===Part 13 - Linear Metal Flashing===
 +
:See the separate page, [[Linear_Metal_Flashing_Details | Construction Details for Linear Metal Flashings]].
 +
 +
===Part 14 - The Roof as a Platform===
 +
 +
====='''Structures and Equipment''' ([[SBS_Roof_Systems_Standard#14.3.2.7._Structures_and_Equipment | Article 14.3.2.7.]])=====
 +
<ol>
 +
<li>[[SBS Structural Planter | Structural Planter]]
 +
</li></ol>
  
 +
</div>
  
 +
<div class="col-md-12">
 +
<hr>
  
[[SBS Roof Systems|<i class="fa fa-chevron-circle-left" ></i> Back to ''SBS Roof Systems'']]
+
[[SBS Roof Systems Standard|<i class="fa fa-chevron-circle-left" ></i> ''Standard for SBS-modified Bitumen Membrane Roof Systems'']]
  
[[Construction Details|<i class="fa fa-chevron-circle-left" ></i> Back to ''Construction Details Section'']]
+
[[Main Page | <i class="fa fa-home fa"></i> Home]]
 +
{{Template:RPM Page Footer with Copyright and Current Date}}
 +
</div>

Latest revision as of 15:35, 14 August 2024



Division D - Construction Details

Construction Details for SBS-modified Bitumen Membrane Roof Systems
SBS Systems page thumb.JPG
Photo Credit: RCABC Image Library
The drawings linked on this page are intended to represent a variety of SBS-modified Bitumen Membrane roof system applications while remaining generic with regards to manufacturers’ specific application specifications. They do not represent all possible manufacturer application roof system designs. Consult each manufacturers’ specifications and the RoofStar Guarantee Standards to develop a system acceptable to both the manufacturer and the RoofStar Guarantee Program.
For further information about SBS-modified Bitumen Membrane System designs and requirements, see the Standard for SBS-modified Bitumen Membrane Roof Systems.

Standard for SBS-modified Bitumen Membrane Roof Systems