1 WORK INCLUDED

(1) Underlayment: The type of underlay required is determined by roof slope (see Section 8.1.4.1 and Section 8.1.4.2).

(2) Slip Sheet: Recommended over asphaltic underlays and / or as required by metal roof panel manufacturer.

(3) Metal Panel Clip: Installed to metal roof panel manufacturer’s printed instructions.

(4) Architectural Metal Roof Panel

(5) Metal Curb Flashing

(6) Cricket: Required for curbs more than 900 mm (36") wide

(7) Accepted Caulking: Two rows accepted caulking between overlapping sheets, with preformed closures on trapezoidal ribbed roof panels.

(8) Counter Flashing


2 RELATED WORK BY OTHERS

(A) Acceptable Deck

(B) Wood Curb: 200 mm (8") minimum height


NOTE: Refer to RGC Guarantee Standards for additional requirements.