Difference between revisions of "SBS Parapet (Typical)"
Difference between revisions of "SBS Parapet (Typical)"
(→RELATED WORK BY OTHERS) |
(→RELATED WORK BY OTHERS) |
||
Line 27: | Line 27: | ||
;(E) [[RoofStar Guarantee Standards for SBS Roof Systems#SBSSLOPEDWOODBLOCKING|'''Sloped Wood Blocking''']] | ;(E) [[RoofStar Guarantee Standards for SBS Roof Systems#SBSSLOPEDWOODBLOCKING|'''Sloped Wood Blocking''']] | ||
:Required over 100 mm (4") parapet width. | :Required over 100 mm (4") parapet width. | ||
+ | |||
'''NOTE''': Refer to <i>RGC Guarantee Standards</i> for additional requirements. | '''NOTE''': Refer to <i>RGC Guarantee Standards</i> for additional requirements. |
Revision as of 20:10, 19 July 2016
1 WORK INCLUDED
- 1. Gypsum Board
- If required by design authority.
- 2. Vapour Retarder
- If required by design authority.
- 3. Insulation
- See list of Accepted Materials.
- 4. Insulation Overlay Board
- As required.
- 5. Primary Membrane and Membrane Protection
- 6. Membrane Flashing
- Mechanically fasten to outside face of parapet blocking (D). At least one ply must extend over outside edge.
- 7. Metal Base Flashing
- Optional on flexible membrane systems. Required on assemblies using gravel ballast filter mats.
- 8. Metal Cap Flashing
- Flashings 1 and 2 may be one piece. Fasten with continuous concealed clip-type fasteners or cladding screws evenly spaced between seams.
2 RELATED WORK BY OTHERS
- (A) Acceptable Steel Deck
- (B) Air/Vapour Seal
- (C) Acceptable Wall Surface
- (D) Wood Blocking
- (E) Sloped Wood Blocking
- Required over 100 mm (4") parapet width.
NOTE: Refer to RGC Guarantee Standards for additional requirements.