=== WORK INCLUDED === | === WORK INCLUDED === | ||
− | ;[[RoofStar Guarantee Standards for SBS Roof Systems#SBSSUBSTRATES|'''Gypsum Board''']]: | + | ;(1) [[RoofStar Guarantee Standards for SBS Roof Systems#SBSSUBSTRATES|'''Gypsum Board''']]: |
:If required by design authority. | :If required by design authority. | ||
− | ;[[RoofStar Guarantee Standards for SBS Roof Systems#SBSVAPOUR|'''Vapour Retarder''']]: | + | ;(2) [[RoofStar Guarantee Standards for SBS Roof Systems#SBSVAPOUR|'''Vapour Retarder''']]: |
:If required by design authority. | :If required by design authority. | ||
− | ;[[RoofStar Guarantee Standards for SBS Roof Systems#SBSINSULATION|'''Insulation''']]: | + | ;(3) [[RoofStar Guarantee Standards for SBS Roof Systems#SBSINSULATION|'''Insulation''']]: |
:See list of '''[[Section:C. Accepted Materials|Accepted Materials]]'''. | :See list of '''[[Section:C. Accepted Materials|Accepted Materials]]'''. | ||
− | ;[[RoofStar Guarantee Standards for SBS Roof Systems#SBSINSULATIONOVERLAY|'''Insulation Overlay Board''']]: | + | ;(4) [[RoofStar Guarantee Standards for SBS Roof Systems#SBSINSULATIONOVERLAY|'''Insulation Overlay Board''']]: |
:As required. | :As required. | ||
− | ;[[RoofStar Guarantee Standards for SBS Roof Systems#SBSBASE|'''Primary Membrane and Membrane Protection''']]: | + | ;(5) [[RoofStar Guarantee Standards for SBS Roof Systems#SBSBASE|'''Primary Membrane and Membrane Protection''']]: |
− | ;[[RoofStar Guarantee Standards for SBS Roof Systems#SBS-STRIPPING|'''Membrane Flashing''']]: | + | ;(6) [[RoofStar Guarantee Standards for SBS Roof Systems#SBS-STRIPPING|'''Membrane Flashing''']]: |
:Mechanically fasten to outside face of parapet blocking (D). At least one ply must extend over outside edge. | :Mechanically fasten to outside face of parapet blocking (D). At least one ply must extend over outside edge. | ||
− | ;[[RoofStar Guarantee Standards for SBS Roof Systems# | + | ;(7) [[RoofStar Guarantee Standards for SBS Roof Systems#METALCAP-SBS|'''Metal Base Flashing''']]: |
:Optional on flexible membrane systems. Required on assemblies using gravel ballast filter mats. | :Optional on flexible membrane systems. Required on assemblies using gravel ballast filter mats. | ||
− | ;[[RoofStar Guarantee Standards for SBS Roof Systems#METALCAP-SBS|'''Metal Cap Flashing''']]: | + | ;(8) [[RoofStar Guarantee Standards for SBS Roof Systems#METALCAP-SBS|'''Metal Cap Flashing''']]: |
:Flashings 1 and 2 may be one piece. Fasten with continuous concealed clip-type fasteners <b>or</b> cladding screws evenly spaced between seams. | :Flashings 1 and 2 may be one piece. Fasten with continuous concealed clip-type fasteners <b>or</b> cladding screws evenly spaced between seams. | ||
Revision as of 21:08, 29 July 2016
1 WORK INCLUDED
- (1) Gypsum Board
- If required by design authority.
- (2) Vapour Retarder
- If required by design authority.
- (3) Insulation
- See list of Accepted Materials.
- (4) Insulation Overlay Board
- As required.
- (5) Primary Membrane and Membrane Protection
- (6) Membrane Flashing
- Mechanically fasten to outside face of parapet blocking (D). At least one ply must extend over outside edge.
- (7) Metal Base Flashing
- Optional on flexible membrane systems. Required on assemblies using gravel ballast filter mats.
- (8) Metal Cap Flashing
- Flashings 1 and 2 may be one piece. Fasten with continuous concealed clip-type fasteners or cladding screws evenly spaced between seams.
2 RELATED WORK BY OTHERS
- (A) Acceptable Steel Deck
- (B) Air/Vapour Seal
- (C) Acceptable Wall Surface
- (D) Wood Blocking
- (E) Sloped Wood Blocking
- Required over 100 mm (4") parapet width.
NOTE: Refer to RGC Guarantee Standards for additional requirements.