Difference between revisions of "SBS Fall Protection Anchor in Roof"
Difference between revisions of "SBS Fall Protection Anchor in Roof"
(Created page with "File:10.3.7.1.jpg === WORK INCLUDED === (1) <b>Flashing</b>: 0.08 mm (0.032", 20 gauge) Aluminum or 0.56 mm (16 oz) copper to CSA B272-93 flashing supplied by anchor manu...") |
|||
Line 2: | Line 2: | ||
=== WORK INCLUDED === | === WORK INCLUDED === | ||
− | (1) | + | ;(1) '''Flashing''': 0.08 mm (0.032", 20 gauge) Aluminum or 0.56 mm (16 oz) copper to CSA B272-93 flashing supplied by anchor manufacturer with flanges sealed by roofer. |
− | + | ;(2) '''Flashing Flange''': minimum 100 mm (4") flange set in coating of compatible sealant. | |
− | (2) | + | ;(3) [[RoofStar Guarantee Standards for SBS Roof Systems#SBSBASE|'''Primary Membrane''']] and [[RoofStar Guarantee Standards for SBS Roof Systems#SBSBASE|'''Membrane Flashing''']] |
− | + | ;(4) [[RoofStar Guarantee Standards for SBS Roof Systems#SBSPMRA|'''Protected Membrane Roof Assembly''']]: Flashing to extend a minimum 200 mm (8") above finished roof surface (pavers, ballast, or walkways) | |
− | (3) | + | ;(5) [[RoofStar Guarantee Standards for SBS Roof Systems#SBS-STRIPPING|'''Conventional Roof Assembly''']]: Flashing to extend a minimum 200 mm (8") above finished roof surface. |
− | + | ;(6) [[RoofStar Guarantee Standards for SBS Roof Systems#SBSINSULATION|'''Insulation''']]: See available insulation products in the [[Roof Deck Insulation|'''Accepted Materials''']] section of this Manual. | |
− | (4) | ||
− | |||
− | (5) | ||
− | |||
− | (6) | ||
=== WORK BY OTHERS === | === WORK BY OTHERS === | ||
− | (A) | + | ;(A) [[RoofStar Guarantee Standards for SBS Roof Systems#SBSDECKS|'''Acceptable Deck''']]: Concrete slab shown, see anchor manufacturer's attachment details for other deck types. |
− | + | ;(B) '''Roof Anchor''':to CSA Z91-M90 | |
− | (B) | + | ;(C) '''Anchor Eye''': to CSA Z91-M90 |
− | + | ;(D) '''Water Tight Cap''' | |
− | (C) | ||
− | |||
− | (D) | ||
− | '''NOTE''': Refer to | + | '''NOTE''': Refer to '''''RoofStar Guarantee Standards''''' for additional requirements. |
Revision as of 21:29, 5 August 2016
1 WORK INCLUDED
- (1) Flashing
- 0.08 mm (0.032", 20 gauge) Aluminum or 0.56 mm (16 oz) copper to CSA B272-93 flashing supplied by anchor manufacturer with flanges sealed by roofer.
- (2) Flashing Flange
- minimum 100 mm (4") flange set in coating of compatible sealant.
- (3) Primary Membrane and Membrane Flashing
- (4) Protected Membrane Roof Assembly
- Flashing to extend a minimum 200 mm (8") above finished roof surface (pavers, ballast, or walkways)
- (5) Conventional Roof Assembly
- Flashing to extend a minimum 200 mm (8") above finished roof surface.
- (6) Insulation
- See available insulation products in the Accepted Materials section of this Manual.
2 WORK BY OTHERS
- (A) Acceptable Deck
- Concrete slab shown, see anchor manufacturer's attachment details for other deck types.
- (B) Roof Anchor
- to CSA Z91-M90
- (C) Anchor Eye
- to CSA Z91-M90
- (D) Water Tight Cap
NOTE: Refer to RoofStar Guarantee Standards for additional requirements.