Difference between revisions of "SBS Fall Protection Anchor in Roof"
Difference between revisions of "SBS Fall Protection Anchor in Roof"
(→WORK INCLUDED) |
(→WORK INCLUDED) |
||
Line 4: | Line 4: | ||
;(1) '''Flashing''': 0.08 mm (0.032", 20 gauge) Aluminum or 0.56 mm (16 oz) copper to CSA B272-93 flashing supplied by anchor manufacturer with flanges sealed by roofer. | ;(1) '''Flashing''': 0.08 mm (0.032", 20 gauge) Aluminum or 0.56 mm (16 oz) copper to CSA B272-93 flashing supplied by anchor manufacturer with flanges sealed by roofer. | ||
;(2) '''Flashing Flange''': minimum 100 mm (4") flange set in coating of compatible sealant. | ;(2) '''Flashing Flange''': minimum 100 mm (4") flange set in coating of compatible sealant. | ||
− | ;(3) [[RoofStar Guarantee Standards for SBS Roof Systems#SBSBASE|'''Primary Membrane''']] and [[RoofStar Guarantee Standards for SBS Roof Systems# | + | ;(3) [[RoofStar Guarantee Standards for SBS Roof Systems#SBSBASE|'''Primary Membrane''']] and [[RoofStar Guarantee Standards for SBS Roof Systems#SBSSTRIPFLASH|'''Membrane Flashing''']] |
;(4) [[RoofStar Guarantee Standards for SBS Roof Systems#SBSPMRA|'''Protected Membrane Roof Assembly''']]: Flashing to extend a minimum 200 mm (8") above finished roof surface (pavers, ballast, or walkways) | ;(4) [[RoofStar Guarantee Standards for SBS Roof Systems#SBSPMRA|'''Protected Membrane Roof Assembly''']]: Flashing to extend a minimum 200 mm (8") above finished roof surface (pavers, ballast, or walkways) | ||
;(5) [[RoofStar Guarantee Standards for SBS Roof Systems#SBS-STRIPPING|'''Conventional Roof Assembly''']]: Flashing to extend a minimum 200 mm (8") above finished roof surface. | ;(5) [[RoofStar Guarantee Standards for SBS Roof Systems#SBS-STRIPPING|'''Conventional Roof Assembly''']]: Flashing to extend a minimum 200 mm (8") above finished roof surface. |
Revision as of 21:32, 5 August 2016
1 WORK INCLUDED
- (1) Flashing
- 0.08 mm (0.032", 20 gauge) Aluminum or 0.56 mm (16 oz) copper to CSA B272-93 flashing supplied by anchor manufacturer with flanges sealed by roofer.
- (2) Flashing Flange
- minimum 100 mm (4") flange set in coating of compatible sealant.
- (3) Primary Membrane and Membrane Flashing
- (4) Protected Membrane Roof Assembly
- Flashing to extend a minimum 200 mm (8") above finished roof surface (pavers, ballast, or walkways)
- (5) Conventional Roof Assembly
- Flashing to extend a minimum 200 mm (8") above finished roof surface.
- (6) Insulation
- See available insulation products in the Accepted Materials section of this Manual.
2 WORK BY OTHERS
- (A) Acceptable Deck
- Concrete slab shown, see anchor manufacturer's attachment details for other deck types.
- (B) Roof Anchor
- to CSA Z91-M90
- (C) Anchor Eye
- to CSA Z91-M90
- (D) Water Tight Cap
NOTE: Refer to RoofStar Guarantee Standards for additional requirements.