Difference between revisions of "SBS Fall Protection Anchor in Wall (Protected)"
Difference between revisions of "SBS Fall Protection Anchor in Wall (Protected)"
(→RELATED WORK BY OTHERS) |
|||
Line 25: | Line 25: | ||
− | [[Section:D. Application: Low Slope Roofs|<i class="fa fa-chevron-circle-left fa | + | [[Section:D. Application: Low Slope Roofs|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''SBS Application'']] |
− | [[SBS Construction Details|<i class="fa fa-chevron-circle-left fa | + | [[SBS Construction Details|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''SBS Construction Details'']] |
− | [[Section:G. Construction Details|<i class="fa fa-chevron-circle-left fa | + | [[Section:G. Construction Details|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''Construction Details'']] |
Revision as of 17:56, 8 August 2016
1 WORK INCLUDED
- (1) Inverted (Protected) Roof Assembly
- (2) Counter-flashing
- (3) Insulation - XPS
- See available insulation products in the Accepted Materials section of this Manual.
- (4) Primary Membrane
2 RELATED WORK BY OTHERS
- (A) Acceptable Deck
- (B) Anchor
- to CSA Z91-M90 - Poured concrete shown, see anchor manufacturer's attachment for other wall types and attachment methods.
- (C) Anchor Eye
- to CSA Z91-M90
- (D) Anchor Placement For Roof Decks Accessible By General Public/Residential Occupants
- Maximum 100 mm (4") above finished roof surface (design to prevent climbing) and not less than 3-1/2" above the finished roof surfacing.
- (E) Plywood
- 15.9 mm (5/8") treated where required.
NOTE: Refer to RoofStar Guarantee Standards for additional requirements.