=== WORK INCLUDED ===
 
=== WORK INCLUDED ===
 +
;(1) [[RoofStar Guarantee Standards for ASM Roof Systems#ASMUNDERLAYMENT|'''Underlayment''']]: Proprietary underlayment installed perpendicular to the slope with 50 mm (2") minimum side laps and 100 mm (4") minimum end laps.
 +
;(2) [[RoofStar Guarantee Standards for ASM Roof Systems#ASMICE|'''Ice and Water Protection''']]: One ply of accepted self-adhered modified bituminous membrane.
 +
;(3) [[RoofStar Guarantee Standards for ASM Roof Systems#ASMEDGE|'''Edge Metal Flashing''']]: Installed to manufacturer&#8217;s printed instructions.
  
;(1) <b>Underlayment</b>:
+
:'''Note:'''
:Proprietary underlayment installed perpendicular to the slope with 50 mm (2") minimum side laps and 100 mm (4") minimum end laps.
 
 
 
;(2) <b>Ice And Water Protection</b>:
 
:One ply of accepted self-adhered modified bituminous membrane.
 
 
 
;(3) <b>Edge Metal Flashing</b>:
 
:Installed to manufacturer&#8217;s printed instructions.
 
 
 
;Note:  
 
 
;* This specification is only applicable to slopes 1:3 (4" in 12") or greater
 
;* This specification is only applicable to slopes 1:3 (4" in 12") or greater
 
;* Slip sheet not shown for clarity
 
;* Slip sheet not shown for clarity
 +
 +
<hr>
  
  
 
=== RELATED WORK BY OTHERS ===
 
=== RELATED WORK BY OTHERS ===
 +
;(A) [[RoofStar Guarantee Standards for ASM Roof Systems#ASMDECK|'''Acceptable Deck''']]
  
;(A) <b>Acceptable Deck</b>
 
  
  
'''NOTE''': Refer to <i>RGC Guarantee Standards</i> for additional requirements.
+
'''NOTE''': Refer to '''''RoofStar Guarantee Standards''''' for additional requirements.
  
  
Line 32: Line 27:
  
  
[[Section:E. Application: Steep Slope Roofs|<i class="fa fa-chevron-circle-left fa-2x" ></i> Back to ''ASM Application'']]
+
[[Section:E. Application: Steep Slope Roofs|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''ASM Application'']]
  
[[Architectural Sheet Metal Construction Details|<i class="fa fa-chevron-circle-left fa-2x" ></i> Back to ''ASM Construction Details'']]
+
[[Architectural Sheet Metal Construction Details|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''ASM Construction Details'']]
  
[[Section:G. Construction Details|<i class="fa fa-chevron-circle-left fa-2x" ></i> Back to ''Construction Details'']]
+
[[Section:G. Construction Details|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''Construction Details'']]

Revision as of 18:19, 9 August 2016

8.1.jpg


1 WORK INCLUDED

(1) Underlayment
Proprietary underlayment installed perpendicular to the slope with 50 mm (2") minimum side laps and 100 mm (4") minimum end laps.
(2) Ice and Water Protection
One ply of accepted self-adhered modified bituminous membrane.
(3) Edge Metal Flashing
Installed to manufacturer’s printed instructions.
Note:
This specification is only applicable to slopes 1
  • 3 (4" in 12") or greater
  • Slip sheet not shown for clarity


2 RELATED WORK BY OTHERS

(A) Acceptable Deck


NOTE: Refer to RoofStar Guarantee Standards for additional requirements.