=== WORK INCLUDED ===
 
=== WORK INCLUDED ===
 +
;(1) [[RoofStar Guarantee Standards for ASM Roof Systems#ASMUNDERLAYMENT|'''Underlayment''']]: The type of underlay required is determined by roof slope.
 +
;(2) '''Insulation Overlay Protection''': Recommended.
 +
;(3) [[RoofStar Guarantee Standards for ASM Roof Systems#ASMPANEL |'''Architectural Metal Roof Panel''']] : Turn up (bread panned) at termination.
 +
;(4) 'Z'-Bar: Installed to meet adequate attachment for UL I-90 wind uplift requirements.
 +
;(5) [[RoofStar Guarantee Standards for ASM Roof Systems#ASMINS |'''Insulation''']]:  Installed between &#8216;Z&#8217; bars or wood battens on 600 mm (24") centres.
 +
;(6) [[RoofStar Guarantee Standards for ASM Roof Systems#ASMCLOSURE |'''Pre-formed Foam Closures''']]: Set in accepted caulking.
 +
;(7) [[RoofStar Guarantee Standards for ASM Roof Systems#ASMEXFASTEN |'''Exposed Fasteners''']]: High domed, gasketed cladding type screws compatible with metal roof panel.
 +
;(8) '''Metal Cap Flashing''': Joints overlapped 100 mm (4") minimum, sealed with two rows of accepted caulking. Exposed edges must be turned under 12.7 mm (1/2").
 +
;(9) [[RoofStar Guarantee Standards for ASM Roof Systems#ASMDRAG |'''Drag-load Fasteners''']]: Compatible non-corrosive fasteners.
  
(1) <b>Underlayment</b>: The type of underlay required is determined by roof slope (see Section 8.1.4.1 and Section 8.1.4.2).
+
<hr>
 
 
(2) <b>Insulation Overlay Protection</b>: Recommended.
 
 
 
(3) <b>Architectural Metal Roof Panel</b>: Turn up (bread panned) at termination.
 
 
 
(4) <b>&#8216;Z&#8217; Bar:</b> Installed to meet adequate attachment for UL I-90 wind uplift requirements.
 
 
 
(5) <b>Insulation</b>:  Installed between &#8216;Z&#8217; bars or wood battens on 600 mm (24") centres.
 
 
 
(6) <b>Preformed Foam Closure</b>: Set in accepted caulking.
 
 
 
(7) <b>Exposed Fastener</b>: High domed, gasketed cladding type screws compatible with metal roof panel.
 
 
 
(8) <b>Metal Cap Flashing</b>: Joints overlapped 100 mm (4") minimum, sealed with two rows of accepted caulking. Exposed edges must be turned under 12.7 mm (1/2").
 
 
 
(9) <b>Drag Load Fastening:</b> compatible non-corrosive fasteners.
 
 
 
  
 
=== RELATED WORK BY OTHERS ===
 
=== RELATED WORK BY OTHERS ===
 +
;(A) [[RoofStar Guarantee Standards for ASM Roof Systems#ASMDECK|'''Acceptable Deck''']]
  
(A) <b>Acceptable Deck</b>
 
 
 
'''NOTE''': Refer to <i>RGC Guarantee Standards</i> for additional requirements.
 
  
 +
'''NOTE''': Refer to '''''RoofStar Guarantee Standards''''' for additional requirements.
  
 
<hr>
 
<hr>
Line 36: Line 25:
  
  
 +
[[Section:E. Application: Steep Slope Roofs|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''ASM Application'']]
  
[[Section:E. Application: Steep Slope Roofs|<i class="fa fa-chevron-circle-left fa-2x" ></i> Back to ''ASM Application'']]
+
[[Architectural Sheet Metal Construction Details|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''ASM Construction Details'']]
 
 
[[Architectural Sheet Metal Construction Details|<i class="fa fa-chevron-circle-left fa-2x" ></i> Back to ''ASM Construction Details'']]
 
  
[[Section:G. Construction Details|<i class="fa fa-chevron-circle-left fa-2x" ></i> Back to ''Construction Details'']]
+
[[Section:G. Construction Details|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''Construction Details'']]

Revision as of 18:19, 10 August 2016

8.1.4.12.1.jpg


1 WORK INCLUDED

(1) Underlayment
The type of underlay required is determined by roof slope.
(2) Insulation Overlay Protection
Recommended.
(3) Architectural Metal Roof Panel 
Turn up (bread panned) at termination.
(4) 'Z'-Bar
Installed to meet adequate attachment for UL I-90 wind uplift requirements.
(5) Insulation
Installed between ‘Z’ bars or wood battens on 600 mm (24") centres.
(6) Pre-formed Foam Closures
Set in accepted caulking.
(7) Exposed Fasteners
High domed, gasketed cladding type screws compatible with metal roof panel.
(8) Metal Cap Flashing
Joints overlapped 100 mm (4") minimum, sealed with two rows of accepted caulking. Exposed edges must be turned under 12.7 mm (1/2").
(9) Drag-load Fasteners
Compatible non-corrosive fasteners.

2 RELATED WORK BY OTHERS