=== WORK INCLUDED === | === WORK INCLUDED === | ||
;(1) [[RoofStar Guarantee Standards for SBS Roof Systems#SBSBASE|'''Primary Roof Membrane''']] | ;(1) [[RoofStar Guarantee Standards for SBS Roof Systems#SBSBASE|'''Primary Roof Membrane''']] | ||
Line 15: | Line 23: | ||
;(A) [[RoofStar Guarantee Standards for SBS Roof Systems#SBSDECKS|'''Acceptable Deck''']]: Concrete slab shown | ;(A) [[RoofStar Guarantee Standards for SBS Roof Systems#SBSDECKS|'''Acceptable Deck''']]: Concrete slab shown | ||
;(B) '''Wall Cladding and Flashing''' | ;(B) '''Wall Cladding and Flashing''' | ||
− | + | </div><!-- COL-6-MD --> | |
+ | </div><!-- PANEL BODY --> | ||
+ | </div><!-- PANEL --> | ||
'''NOTE''': Refer to '''''RoofStar Guarantee Standards''''' for additional requirements. | '''NOTE''': Refer to '''''RoofStar Guarantee Standards''''' for additional requirements. |
Revision as of 17:59, 19 August 2016
SBS Details
1 WORK INCLUDED
- (1) Primary Roof Membrane
- (2) Membrane Flashing
- Carried up wall minimum 200 mm (8") above roof surface. At doorsill openings membrane flashing may be less than 200mm (8") in height but must not be less than 100mm (4") in height above the primary roof membrane. When doorsills are less than 200mm (8") a metal waterstop flashing must be mechanically attached to backside of doorsill framing or opening and be sealed with membrane flashing. Membrane gussets must be installed at doorsill opening corners.
- (3) Protection/Drainage Layer
- Optional
- (4) Metal Base Flashing
- Optional on flexible membrane systems. Required on assemblies using gravel ballast filter mats.
- (5) Metal Counter-flashing
- (6) Metal Water-stop Flashing
- Mechanically attached to inside of door sill framing or opening. Cut flashing to fit opening and install membrane gussets at corners.
- (7) Metal Pan Sill Flashing
- Optional - Metal pan with water stop formed with pan folded, welded or soldered corners mechanically attached to inside of door sill frame or opening and sealed with membrane flashing.
2 RELATED WORK BY OTHERS
- (A) Acceptable Deck
- Concrete slab shown
- (B) Wall Cladding and Flashing
NOTE: Refer to RoofStar Guarantee Standards for additional requirements.