=== WORK INCLUDED ===
 
=== WORK INCLUDED ===
 
;(1) [[RoofStar Guarantee Standards for SBS Roof Systems#SBSPMRA|'''Inverted (Protected) Roof Assembly''']]
 
;(1) [[RoofStar Guarantee Standards for SBS Roof Systems#SBSPMRA|'''Inverted (Protected) Roof Assembly''']]
Line 15: Line 23:
 
;(D) '''Anchor Placement For Roof Decks Accessible By General Public/Residential Occupants''': Maximum 100 mm (4") above finished roof surface (design to prevent climbing) and not less than 3-1/2" above the finished  roof surfacing.
 
;(D) '''Anchor Placement For Roof Decks Accessible By General Public/Residential Occupants''': Maximum 100 mm (4") above finished roof surface (design to prevent climbing) and not less than 3-1/2" above the finished  roof surfacing.
 
;(E) '''Plywood''': 15.9 mm (5/8") treated where required.
 
;(E) '''Plywood''': 15.9 mm (5/8") treated where required.
 
+
</div><!-- COL-6-MD -->
 +
</div><!-- PANEL BODY -->
 +
</div><!-- PANEL -->
  
 
'''NOTE''': Refer to '''''RoofStar Guarantee Standards''''' for additional requirements.
 
'''NOTE''': Refer to '''''RoofStar Guarantee Standards''''' for additional requirements.

Revision as of 18:15, 19 August 2016

SBS Details

10.3.7.3.jpg

1 WORK INCLUDED

(1) Inverted (Protected) Roof Assembly
(2) Counter-flashing
(3) Insulation - XPS
See available insulation products in the Accepted Materials section of this Manual.
(4) Primary Membrane

2 RELATED WORK BY OTHERS

(A) Acceptable Deck
(B) Anchor
to CSA Z91-M90 - Poured concrete shown, see anchor manufacturer's attachment for other wall types and attachment methods.
(C) Anchor Eye
to CSA Z91-M90
(D) Anchor Placement For Roof Decks Accessible By General Public/Residential Occupants
Maximum 100 mm (4") above finished roof surface (design to prevent climbing) and not less than 3-1/2" above the finished roof surfacing.
(E) Plywood
15.9 mm (5/8") treated where required.

NOTE: Refer to RoofStar Guarantee Standards for additional requirements.