=== WORK INCLUDED === | === WORK INCLUDED === | ||
− | |||
(1) <b>Primary Waterproofing Membrane: </b>Fully adhered to acceptable substrates (concrete slab depicted), installed as per <i>RGC Guarantee Standards E </i>and Membrane Manufacturer's installation specifications. | (1) <b>Primary Waterproofing Membrane: </b>Fully adhered to acceptable substrates (concrete slab depicted), installed as per <i>RGC Guarantee Standards E </i>and Membrane Manufacturer's installation specifications. | ||
− | (2)<b> Membrane Flashing (stripping): </b>Carried up walls a minimum 200 mm (8") above membrane surface (Deck) and a minimum of 100mm (4") above top surface of permeable waterproofing wearing surfaces and overburdens. | + | (2) <b> Membrane Flashing (stripping): </b>Carried up walls a minimum 200 mm (8") above membrane surface (Deck) and a minimum of 100mm (4") above top surface of permeable waterproofing wearing surfaces and overburdens. |
− | (3)<b> Membrane Primer or Adhesive: </b>proprietary primer or adhesive, application and quantities as directed by membrane manufacturers published application specifications. | + | (3) <b> Membrane Primer or Adhesive: </b>proprietary primer or adhesive, application and quantities as directed by membrane manufacturers published application specifications. |
− | (4)<b>Metal Base Flashing:</b> Required on all waterproofing assemblies flashing lengths joined by use of S-locks or standing seam joints. | + | (4) <b>Metal Base Flashing:</b> Required on all waterproofing assemblies flashing lengths joined by use of S-locks or standing seam joints. |
− | (5)<b>Metal Counter Flashing:</b> Set in reglet fastened with expanding type concrete pins, join flashing lengths by use of S-locks or standing seam joints. | + | (5) <b>Metal Counter Flashing:</b> Set in reglet fastened with expanding type concrete pins, join flashing lengths by use of S-locks or standing seam joints. |
− | (6)<b> Fasteners: </b>Suitable expanding type concrete pins. | + | (6) <b> Fasteners: </b>Suitable expanding type concrete pins. |
− | (7)<b> Caulking: </b>Polyurethane sealant, fill void and tool smooth. | + | (7) <b> Caulking: </b>Polyurethane sealant, fill void and tool smooth. |
=== RELATED WORK BY OTHERS === | === RELATED WORK BY OTHERS === | ||
− | |||
(A)<b>Concrete Wall:</b> Must be dry, smooth and primed for membrane flashing to be adhered directly. (Plywood or fibre-mat reinforced cement board may be required). | (A)<b>Concrete Wall:</b> Must be dry, smooth and primed for membrane flashing to be adhered directly. (Plywood or fibre-mat reinforced cement board may be required). | ||
(B)<b>Reglet: </b>minimum 75mm (3/4") in depth, saw cut or manufactured preformed reglet. | (B)<b>Reglet: </b>minimum 75mm (3/4") in depth, saw cut or manufactured preformed reglet. | ||
+ | </div><!-- COL-6-MD --> | ||
+ | </div><!-- PANEL BODY --> | ||
+ | </div><!-- PANEL --> | ||
− | NOTE: Refer to | + | '''NOTE''': Refer to '''''RoofStar Guarantee Standards''''' for additional requirements. |
<hr> | <hr> | ||
Line 32: | Line 39: | ||
− | |||
− | [[Waterproofing Construction Details|<i class="fa fa-chevron-circle-left fa | + | [[Section:F. Application: Waterproofing Plazas, Promenades and Terraces|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''Waterproofing Application'']] |
+ | |||
+ | [[Waterproofing Construction Details|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''Waterproofing Construction Details'']] | ||
− | [[Section:G. Construction Details|<i class="fa fa-chevron-circle-left fa | + | [[Section:G. Construction Details|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''Construction Details'']] |
Revision as of 21:48, 19 August 2016
1 WORK INCLUDED
(1) Primary Waterproofing Membrane: Fully adhered to acceptable substrates (concrete slab depicted), installed as per RGC Guarantee Standards E and Membrane Manufacturer's installation specifications.
(2) Membrane Flashing (stripping): Carried up walls a minimum 200 mm (8") above membrane surface (Deck) and a minimum of 100mm (4") above top surface of permeable waterproofing wearing surfaces and overburdens.
(3) Membrane Primer or Adhesive: proprietary primer or adhesive, application and quantities as directed by membrane manufacturers published application specifications.
(4) Metal Base Flashing: Required on all waterproofing assemblies flashing lengths joined by use of S-locks or standing seam joints.
(5) Metal Counter Flashing: Set in reglet fastened with expanding type concrete pins, join flashing lengths by use of S-locks or standing seam joints.
(6) Fasteners: Suitable expanding type concrete pins.
(7) Caulking: Polyurethane sealant, fill void and tool smooth.
2 RELATED WORK BY OTHERS
(A)Concrete Wall: Must be dry, smooth and primed for membrane flashing to be adhered directly. (Plywood or fibre-mat reinforced cement board may be required).
(B)Reglet: minimum 75mm (3/4") in depth, saw cut or manufactured preformed reglet.
NOTE: Refer to RoofStar Guarantee Standards for additional requirements.
Back to Waterproofing Application