SBS Details
1 WORK INCLUDED
- (1) Flashing
- 0.08 mm (0.032", 20 gauge) Aluminum or 0.56 mm (16 oz) copper to CSA B272-93 flashing supplied by anchor manufacturer with flanges sealed by roofer.
- (2) Flashing Flange
- minimum 100 mm (4") flange set in coating of compatible sealant.
- (3) Primary Membrane and Membrane Flashing.
- (4) Protected Membrane Roof Assembly
- Flashing to extend a minimum 200 mm (8") above finished roof surface (pavers, ballast, or walkways)
- (5) Conventional Roof Assembly
- Flashing to extend a minimum 200 mm (8") above finished roof surface.
- (6) Insulation
- See available insulation products in the Accepted Materials section of this Manual.
2 WORK BY OTHERS
- (A) Acceptable Deck
- Concrete slab shown, see anchor manufacturer's attachment details for other deck types.
- (B) Roof Anchor
- to CSA Z91-M90
- (C) Anchor Eye
- to CSA Z91-M90
- (D) Water Tight Cap
NOTE: Refer to RoofStar Guarantee Standards for additional requirements.