Difference between revisions of "TPO Roof System Details"

Jump to: navigation, search

Difference between revisions of "TPO Roof System Details"

(Part 10 - Perimeters and Walls)
 
(30 intermediate revisions by the same user not shown)
Line 1: Line 1:
:The drawings contained within this section are intended to represent a variety of thermoplastic roof system applications while remaining generic with regards to manufacturers’ specific application specifications. They do not represent all possible manufacturer application roof system designs. Consult manufacturers’ specifications and RoofStar Guarantee Standards to develop a system acceptable to both the manufacturer and RGC.
+
{{Template:RPM Info}}
  
:For further information about thermoplastic (TPO and PVC) membrane system designs and requirements, see '''[[TPO/PVC (Thermoplastic Membranes) Roof Systems]]'''.
+
__NONUMBEREDHEADINGS__
 +
{{DISPLAYTITLE:<span style="position: absolute; clip: rect(1px 1px 1px 1px); clip: rect(1px, 1px, 1px, 1px);">{{FULLPAGENAME}}</span>}}
 +
__NOTOC__
  
<div style="width:300px; text-align: left;">
+
:<big><big>Division D - Construction Details</big></big>
:[[File:TPO-PVC Link Drawing.jpg|300 px]]
+
:<hr>
 +
:<big><big><big><big><big>Construction Details for TPO Membrane Roof Systems</big></big></big></big></big>
 +
 
 +
<div class="col-md-2">
 +
:[[File:TPO project (courtesy Carlisle Syntec).jpg| link=http://rpm.rcabc.org/images/5/58/TPO_project_%28courtesy_Carlisle_Syntec%29.jpg | 175 px]]
 +
</div>
 +
 
 +
<div class="col-md-10">
 +
:The drawings linked on this page are intended to represent a variety of TPO Membrane roof system applications while remaining generic with regards to manufacturers&#8217; specific application specifications. They do not represent all possible ''manufacturer'' application roof system designs. Consult each ''manufacturer's'' specifications and the '''''RoofStar Guarantee Standards''''' to develop a system acceptable to both the manufacturer and the '''''RoofStar Guarantee Program'''''.
 +
 
 +
:For further information about TPO Membrane System designs and requirements, see the '''[https://rpm.rcabc.org/index.php?title=TPO_Roof_Systems_Standard Standard for TPO Membrane Roof Systems]'''.
 
</div>
 
</div>
 +
 
<div class="col-md-12">
 
<div class="col-md-12">
<div style="width:40px; vertical-align: center; text-align: left;">
 
[[File:Pdf.png|40 px]]
 
</div>
 
'''NOTE''': 'PDF' shown after a file name below indicates a downloadable print sheet is available for Construction Details.  Click on the detail link and look for the icon.
 
 
</div>
 
</div>
 
<div class="col-md-4">
 
<div class="col-md-4">
 
<hr>
 
<hr>
:[[TPO Details:D3.7.1-1 Assemblies (Insulated Conventional)|D3.7.1-1 Assemblies (Insulated Conventional)]]
+
===Part 1 - General===
:[[TPO Details:D3.7.1-2 Assemblies (Ballasted Protected Membrane)|D3.7.1-2 Assemblies (Ballasted Protected Membrane)]]
+
====='''Permitted Roof Systems''' ([[TPO_Roof_Systems_Standard#1.1.3.1._Permitted_Roof_Systems | Article 1.1.3.1.]])=====
:[[TPO Details:D3.7.1-3 Assemblies (Fully Adhered)|D3.7.1-3 Assemblies (Fully Adhered)]]
+
<ol>
 +
<li>[[TPO Conventionally Insulated System (Typical)| Conventionally Insulated System (Typical)]]
 +
<li>[[TPO Conventionally Insulated System (Alternate) | Conventionally Insulated System (Alternate)]]
 +
<li>[[TPO Protected Roof Assembly (Typical) | Protected Roof Assembly (Typical)]]
 +
</li></ol>
  
:[[TPO Details:D3.7.2-1 Parapets & Copings (High - Wall Supported)|D3.7.2-1 Parapets & Copings (High - Wall Supported)'''(Under Construction)''']]
+
===Part 6 - Air and Vapour Controls===
:[[TPO Details:D3.7.2-2 Parapets & Copings (Parapet - Wall Transition)|D3.7.2-2 Parapets & Copings (Parapet - Wall Transition)'''(Under Construction)''']]
+
====='''Continuity and Support''' ([[TPO_Roof_Systems_Standard#6.3.2.1._Continuity_and_Support | Article 6.3.2.1.]])=====
 +
<ol>
 +
<li>[[TPO Air and Vapour Controls (Field) | {{hilite | Air and Vapour Controls (Field)|| 2021-February-7 }}]]
 +
</li></ol>
  
:[[TPO Details:D3.7.3-1 Edges & Fascia (Cant Edge)|D3.7.3-1 Edges & Fascia (Cant Edge)'''(Under Construction)''']]
 
:[[TPO Details:D3.7.3-2 Edges & Fascia (Gravel Stop)|D3.7.3-2 Edges & Fascia (Gravel Stop)'''(Under Construction)''']]
 
:[[TPO Details:D3.7.3-3 Edges & Fascia (Roof Edge)|D3.7.3-3 Edges & Fascia (Roof Edge)]]
 
  
:[[TPO Details:D3.7.4-1 Counter-flashings & Reglets (Deck - Wall Supported)|D3.7.4-1 Counter-flashings & Reglets (Deck - Wall Supported)'''(Under Construction''')]]
 
:[[TPO Details:D3.7.4-2 Counter-flashings & Reglets (Deck - Unsupported by Wall)|D3.7.4-2 Counter-flashings & Reglets (Deck - Unsupported by Wall)'''(Under Construction)''']]
 
:[[TPO Details:D3.7.4-3 Counter-flashings & Reglets (Stucco Wall: Re-roofing)|D3.7.4-3 Counter-flashings & Reglets (Stucco Wall: Re-roofing)'''(Under Construction)''']]
 
:[[TPO Details:D3.7.4-4 Counter-flashings & Reglets (Stucco Wall: New)|D3.7.4-4 Counter-flashings & Reglets (Stucco Wall: New)'''(Under Construction''')]]
 
:[[TPO Details:D3.7.4-5 Counter-flashings & Reglets (Double Surface Reglet)|D3.7.4-5 Counter-flashings & Reglets (Double Surface Reglet)'''(Under Construction)''']]
 
:[[TPO Details:D3.7.4-6 Counter-flashings & Reglets (Low Door Sill)|D3.7.4-6 Counter-flashings & Reglets (Low Door Sill)'''(Under Construction)''']]
 
:[[TPO Details:D3.7.4-7 Counter-flashings & Reglets (Window Curb)|D3.7.4-7 Counter-flashings & Reglets (Window Curb)'''(Under Construction''')]]
 
 
</div>
 
</div>
 
<div class="col-md-4">
 
<div class="col-md-4">
 
<hr>
 
<hr>
:[[TPO Details:D3.7.5-1 Roof-Wall Transitions (Expansion Joint)|D3.7.5-1 Roof-Wall Transitions (Expansion Joint)'''(Under Construction''')]]
 
:[[TPO Details:D3.7.5-2 Roof-Wall Transitions (Divider/Joint)|D3.7.5-2 Roof-Wall Transitions (Divider/Joint)'''(Under Construction)''']]
 
:[[TPO Details:D3.7.5-3 Roof-Wall Transitions (Fire Separation Joint)|D3.7.5-3 Roof-Wall Transitions (Fire Separation Joint)'''(Under Construction)''']]
 
:[[TPO Details:D3.7.5-4 Roof-Wall Transitions (Fire Separation Wall)|D3.7.5-4 Roof-Wall Transitions (Fire Separation Wall)'''(Under Construction)''']]
 
  
:[[TPO Details:D3.7.6-1 Curbs & Sleepers (Equipment Sleeper)|D3.7.6-1 Curbs & Sleepers (Equipment Sleeper)'''(Under Construction)''']]
+
===Part 10 - Perimeters and Walls===
:[[TPO Details:D3.7.6-2 Curbs & Sleepers (Multiple Roof Penetrations)|D3.7.6-2 Curbs & Sleepers (Multiple Roof Penetrations)'''(Under Construction''')]]
+
====='''General Application''' ([[TPO_Roof_Systems_Standard#10.3.2.3._General_Application_Requirements_for_Perimeters_and_Walls | Article 10.3.2.3.]])=====
:[[TPO Details:D3.7.6-3 Curbs & Sleepers (Basic Curb)|D3.7.6-3 Curbs & Sleepers (Basic Curb)]]
+
<ol>
:[[TPO Details:D3.7.6-4 Curbs & Sleepers (Mechanical Opening)|D3.7.6-4 Curbs & Sleepers (Mechanical Opening)]]
+
<li>[[TPO Membrane Termination A | Membrane Termination A]]
 +
<li>[[TPO Membrane Termination B | Membrane Termination B]]
 +
<li>[[TPO Membrane Termination C | Membrane Termination C]]
 +
<li>[[TPO Membrane Termination D | Membrane Termination D]]
 +
<li>[[TPO Membrane Termination E | Membrane Termination E]]
 +
<li>[[TPO Membrane Termination F | Membrane Termination F]]
 +
</li></ol>
 +
 
 +
====='''Low-profile Edges''' ([[TPO_Roof_Systems_Standard#10.3.4.2._Low_Profile_Edges | Article 10.3.4.2.]])=====
 +
<ol>
 +
<li>[[TPO Metal Edge Termination | Metal Edge Termination]]
 +
</li></ol>
 +
 
 +
===Part 11 - Drainage===
  
:[[TPO Details:D3.7.7-1 Strip-in Flashings (Metal Plumbing)|D3.7.7-1 Strip-in Flashings (Metal Plumbing)'''(Under Construction)''']]
 
:[[TPO Details:D3.7.7-2 Strip-in Flashings (Two-part Cable)|D3.7.7-2 Strip-in Flashings (Two-part Cable)]]
 
:[[TPO Details:D3.7.7-3 Strip-in Flashings (Pourable Sealer Pocket)|D3.7.7-3 Strip-in Flashings (Pourable Sealer  Pocket)'''(Under Construction)''']]
 
 
</div>
 
</div>
 
<div class="col-md-4">
 
<div class="col-md-4">
 
<hr>
 
<hr>
:[[TPO Details:D3.7.8-1 Water & Drainage (Cast Iron Drain)|D3.7.8-1 Water & Drainage (Cast Iron Drain)'''(Under Construction)''']]
 
:[[TPO Details:D3.7.8-2 Water & Drainage (Spun Copper Drain)|D3.7.8-2 Water & Drainage (Spun Copper Drain)'''(Under Construction)''']]
 
:[[TPO Details:D3.7.8-3 Water & Drainage (Clamping Spun Copper Drain)|D3.7.8-3 Water & Drainage (Clamping Spun Copper Drain)]]
 
:[[TPO Details:D3.7.8-4 Water & Drainage (Open Wall Scupper)|D3.7.8-4 Water & Drainage (Open Wall Scupper)'''(Under Construction)''']]
 
:[[TPO Details:D3.7.8-5 Water & Drainage (Through-wall Scupper)|D3.7.8-5 Water & Drainage (Through-wall Scupper)'''(Under Construction)''']]
 
  
:[[TPO Details:D3.7.9-1 Miscellaneous Penetrations (Roof Anchor)|D3.7.9-1 Miscellaneous Penetrations (Roof Anchor)'''(Under Construction)''']]
+
===Part 12 - Penetrations and Curbs===
:[[TPO Details:D3.7.9-2 Miscellaneous Penetrations (Wall Anchor - Conventional Roof Assy)|D3.7.9-2 Miscellaneous Penetrations (Wall Anchor - Conventional Roof Assy)'''(Under Construction)''']]
+
 
:[[TPO Details:D2.7.9-3 Miscellaneous Penetrations (Wall Anchor - Protected Roof Assy)|D3.7.9-3 Miscellaneous Penetrations (Wall Anchor - Protected Roof Assy)'''(Under Construction)''']]
+
===Part 13 - Linear Metal Flashing===
 +
:See the separate page, [[Linear_Metal_Flashing_Details | Construction Details for Linear Metal Flashings]].
 +
 
 +
===Part 14 - The Roof as a Platform===
 +
 
 
</div>
 
</div>
 +
 
<div class="col-md-12">
 
<div class="col-md-12">
 +
<hr>
  
 +
[[TPO Roof Systems Standard|<i class="fa fa-chevron-circle-left" ></i> ''Standard for TPO Membrane Roof Systems'']]
  
 
+
[[Main Page | <i class="fa fa-home fa"></i> Home]]
[[TPO/PVC (Thermoplastic Membranes) Roof Systems|<i class="fa fa-chevron-circle-left" ></i> Back to ''TPO/PVC Roof Systems'']]
+
{{Template:RPM Page Footer with Copyright and Current Date}}
 
 
[[Construction Details|<i class="fa fa-chevron-circle-left" ></i> Back to ''Construction Details Section'']]
 
 
</div>
 
</div>

Latest revision as of 16:39, 26 February 2024



Division D - Construction Details

Construction Details for TPO Membrane Roof Systems
TPO project (courtesy Carlisle Syntec).jpg
The drawings linked on this page are intended to represent a variety of TPO Membrane roof system applications while remaining generic with regards to manufacturers’ specific application specifications. They do not represent all possible manufacturer application roof system designs. Consult each manufacturer's specifications and the RoofStar Guarantee Standards to develop a system acceptable to both the manufacturer and the RoofStar Guarantee Program.
For further information about TPO Membrane System designs and requirements, see the Standard for TPO Membrane Roof Systems.

Part 12 - Penetrations and Curbs

Part 13 - Linear Metal Flashing

See the separate page, Construction Details for Linear Metal Flashings.

Part 14 - The Roof as a Platform


Standard for TPO Membrane Roof Systems

Home

© RCABC 2024
RoofStarTM is a registered Trademark of the RCABC.
No reproduction of this material, in whole or in part, is lawful without the expressed permission of the RCABC Guarantee Corp.