| style="color: black; background-color: #ffffcc; width: 100%;text-align:center" | Images used in a Construction Detail are representative and <u>not intended in their representation of an assembly to be prescriptive</u>. Nor are they necessarily drawn to scale. Rather, they are provided to visually convey the Standards, Guiding Principles and Recommendations of the '''RoofStar Guarantee Standards''' for a Waterproofing or Water-shedding System. Actual design with respect to dimensions, the selection of materials and their application remains the responsibility of the ''Design Authority''.<br><br>The full text of applicable '''''RoofStar Guarantee Standards''''' may be read by using the <span style="color:#6495ed">'''blue hyperlinks'''</span>
+
<big><big>Division D - Construction Details</big></big>
|}
+
<hr>
 +
<big><big><big><big><big>SBS | Canted Edge ([[SBS_Roof_Systems_Standard#10.3.4.2._Low_Profile_Edges | Article 10.3.4.2.]])</big></big></big></big></big>
 +
{{Template:Construction Details Header}}
 
<div class="panel panel-success">
 
<div class="panel panel-success">
 
<div class="panel-heading"><big>'''SBS Details'''</big></div>
 
<div class="panel-heading"><big>'''SBS Details'''</big></div>
Line 15: Line 17:
 
[[File:SBS 10.3.5.3 Cant Edge (2).jpg|class=img-responsive | link=http://rpm.rcabc.org/images/9/91/SBS_10.3.5.3_Cant_Edge_%282%29.jpg]]
 
[[File:SBS 10.3.5.3 Cant Edge (2).jpg|class=img-responsive | link=http://rpm.rcabc.org/images/9/91/SBS_10.3.5.3_Cant_Edge_%282%29.jpg]]
 
</div>
 
</div>
 
 
 
::Click below for a printable version of this page (under development)
 
 
<div style="width:150px; text-align: left;">
 
:[[File:Pdf.png|100 px|link=http://rpm.rcabc.org/images/4/4c/D1.7.3-1_Print_Sheet.pdf|'''Print Sheet''']]
 
</div>
 
 
  
 
</div><!-- COL-MD-6 -->
 
</div><!-- COL-MD-6 -->
Line 29: Line 22:
 
<div class="col-md-6">
 
<div class="col-md-6">
 
=== WORK INCLUDED ===
 
=== WORK INCLUDED ===
;(1) [[RoofStar Guarantee Standards for SBS Modified Bitumen Membrane Systems#SBSAIRVAPOUR|'''Air or Vapour Control Layer''']]: Installed following the requirements of '''Part 6''' in this Standard.  Tie in the control layers with membranes installed by other trades, to preserve continuity of the building enclosure ('''1a''').
+
;(1) [[SBS Roof Systems Standard#PART_6|'''Air or Vapour Control Layer''']]: Installed following the requirements of '''Part 6''' in this Standard.  Tie in the control layers with membranes installed by other trades, to preserve continuity of the building enclosure ('''1a''').
;(2) [[RoofStar Guarantee Standards for SBS Modified Bitumen Membrane Systems#SBSINSULATIONAPPLICATION|'''Insulation''']]: Installed in staggered and offset layers (not illustrated), and secured in accordance with the design of the system, which is based on the British Columbia Building Code, Part 4 and Part 5, and on '''Part 3''' of the '''''RoofStar Guarantee Standards''''' for the membrane system type.
+
;(2) [[SBS Roof Systems Standard#PART_7|'''Insulation''']]: Installed in staggered and offset layers (not illustrated), and secured in accordance with the design of the system, which is based on the British Columbia Building Code, Part 4 and Part 5, and on '''Part 3''' of the '''''RoofStar Guarantee''''' Standard for the membrane system type.
;(3) [[RoofStar Guarantee Standards for SBS Modified Bitumen Membrane Systems#SBSINSULATIONOVERLAY|'''Insulation Overlay''']]: Subject to the requirements of '''Part 8''' in the '''''RoofStar Guarantee Standards''''' for the membrane system type.
+
;(3) [[SBS Roof Systems Standard#PART_8|'''Insulation Overlay''']]: Subject to the requirements of Part 8 in the Standard.
;(4) [[RoofStar Guarantee Standards for SBS Modified Bitumen Membrane Systems#SBSMEMBRANES|'''Base Membrane (field)''']]: Mechanically attached, torch-applied, adhered or self-adhered.  See Tables '''9.1''' and '''9.2''' for acceptable membrane types and securement options.  See '''9.3''' for application requirements.
+
;(4) [[SBS Roof Systems Standard#PART_9|'''Base Membrane (field)''']]: Mechanically attached, torch-applied, adhered or self-adhered.  See Table 9.1. in [[SBS Roof Systems Standard#9.2.1.1. Membrane Composition, Thickness, and Selection | Article 9.2.1.1.]] for acceptable membrane types and securement options.  See [[SBS Roof Systems Standard#10.3.4.2._Low_Profile_Edges | Article 10.3.4.2.]] for application requirements.
;(5) [[RoofStar Guarantee Standards for SBS Modified Bitumen Membrane Systems#SBSPERIMETERS|'''Base Membrane (flashing)''']]: Carried vertically up a wall or parapet at least 200 mm (8”), and onto the roof field at least 100 mm (4”) (greater if required by the membrane manufacturer).  Prime substrate, as required by the membrane manufacturer.
+
;(5) [[SBS Roof Systems Standard#PART_10|'''Base Membrane (flashing)''']]: Carried over the canted edge and down the outside face at least 50.8 mm (2").  Prime substrate, as required by the membrane manufacturer.
;(6) [[RoofStar Guarantee Standards for SBS Modified Bitumen Membrane Systems#SBSMEMBRANES|'''Cap Membrane (field)''']]: Granule-surfaced membrane.  See Tables '''9.1''' and '''9.2''' for acceptable cap membrane types and their securement options.  See '''9.3''' for application requirements.
+
;(6) [[SBS Roof Systems Standard#PART_9|'''Cap Membrane (field)''']]: Granule-surfaced membrane.
;(7) [[RoofStar Guarantee Standards for SBS Modified Bitumen Membrane Systems#SBSPERIMETERS|'''Cap Membrane (flashing)''']]: Extended vertically past the termination of the base membrane flashing, to provide a positive seal at the top edge.
+
;(7) [[SBS Roof Systems Standard#PART_10|'''Cap Membrane (flashing)''']]: Extended vertically past the termination of the base membrane flashing, to provide a positive seal at the top edge.
;(8) [[RoofStar Guarantee Standards for SBS Modified Bitumen Membrane Systems#SBSMETALCANT|'''Metal Cant Flashing''']]: Secure metal flashings with appropriate fasteners set at least 87 mm (3 ½”) above the finished roof surface.  Alternatively, secure flashing from the outside face (illustrated).  See '''13.3.7 Cant Edges''' for metal flashing securement requirements.
+
;(8) [[SBS Roof Systems Standard#PART_13|'''Metal Cant Flashing''']]: Secure metal flashings with appropriate fasteners set at least 87 mm (3 ½”) above the finished roof surface.  Alternatively, secure flashing from the outside face (illustrated).
  
 
<hr>
 
<hr>
  
 
=== RELATED WORK BY OTHERS ===
 
=== RELATED WORK BY OTHERS ===
;(A) [[RoofStar Guarantee Standards for SBS Modified Bitumen Membrane Systems#SBSDECKS|'''Acceptable Deck''']]
+
;(A) [[SBS Roof Systems Standard#PART_2|'''Acceptable Deck''']]
 
;(B) '''Cant and Fascia Woodwork'''
 
;(B) '''Cant and Fascia Woodwork'''
 
</div><!-- COL-6-MD -->
 
</div><!-- COL-6-MD -->
Line 47: Line 40:
 
</div><!-- PANEL -->
 
</div><!-- PANEL -->
  
'''NOTE''': Refer to '''''RoofStar Guarantee Standards''''' for additional requirements.
+
'''NOTE''': See the [[SBS Roof Systems Standard | '''Standard''']] for additional requirements.
  
 
<hr>
 
<hr>
  
[[RoofStar Guarantee Standards for SBS Modified Bitumen Roof Assemblies |<i class="fa fa-chevron-circle-left fa" ></i> Back to ''RoofStar Guarantee Standards for SBS Modified Bitumen Roof Assemblies'']]
+
[[SBS Roof System Details|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''"SBS" Roof System Details'']]
  
[[SBS Modified Bitumen Construction Details|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''SBS Modified Bitumen Construction Details'']]
+
[[Main Page | <i class="fa fa-home fa"></i> Home]]
  
[[Construction Details|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''Construction Details'']]
+
{{Tempate:RPM Page Footer with Copyright and Current Date}}

Latest revision as of 18:03, 25 July 2024



Division D - Construction Details


SBS | Canted Edge ( Article 10.3.4.2.)

Notice to Reader
Images used in a Construction Detail are representative and not prescriptive, and are not necessarily drawn to scale. They are intended to support the related Standard (Ref. Division A, Article 2.2.1.2.).

The reader may link to the related Article in the detail title, or link to the Standard as it relates to a specific element in the detail. All hyperlinks are displayed blue text.

SBS Details

SBS 10.3.5.3 Cant Edge (1).jpg

SBS 10.3.5.3 Cant Edge (2).jpg

1 WORK INCLUDED

(1) Air or Vapour Control Layer
Installed following the requirements of Part 6 in this Standard. Tie in the control layers with membranes installed by other trades, to preserve continuity of the building enclosure (1a).
(2) Insulation
Installed in staggered and offset layers (not illustrated), and secured in accordance with the design of the system, which is based on the British Columbia Building Code, Part 4 and Part 5, and on Part 3 of the RoofStar Guarantee Standard for the membrane system type.
(3) Insulation Overlay
Subject to the requirements of Part 8 in the Standard.
(4) Base Membrane (field)
Mechanically attached, torch-applied, adhered or self-adhered. See Table 9.1. in Article 9.2.1.1. for acceptable membrane types and securement options. See Article 10.3.4.2. for application requirements.
(5) Base Membrane (flashing)
Carried over the canted edge and down the outside face at least 50.8 mm (2"). Prime substrate, as required by the membrane manufacturer.
(6) Cap Membrane (field)
Granule-surfaced membrane.
(7) Cap Membrane (flashing)
Extended vertically past the termination of the base membrane flashing, to provide a positive seal at the top edge.
(8) Metal Cant Flashing
Secure metal flashings with appropriate fasteners set at least 87 mm (3 ½”) above the finished roof surface. Alternatively, secure flashing from the outside face (illustrated).

2 RELATED WORK BY OTHERS

(A) Acceptable Deck
(B) Cant and Fascia Woodwork

NOTE: See the Standard for additional requirements.


Back to "SBS" Roof System Details