Difference between revisions of "Template:All systems - ROOF DECKS"

Jump to: navigation, search

Difference between revisions of "Template:All systems - ROOF DECKS"

(Wood Board Decks)
 
(60 intermediate revisions by the same user not shown)
Line 1: Line 1:
<b>Concrete</b>
+
__NOTOC__
:* Concrete decks, curbs and equipment pads must be clean, dry, and smooth prior to commencement of roofing.  
+
=== General ===
:* Poured concrete or lightweight concrete decks are not to be roofed for a minimum of 28 days after pouring unless expressly instructed in writing by the Project Structural Engineer.
+
The roof deck must be designed to serve two major functions:
:* All concrete decks to receive adhered asphaltic roofing shall be primed.  
+
* As a structural component to transfer the weight of live and dead loads to supporting members. Live loads include construction equipment and workers, rain, snow, and ice. Dead loads include the deck itself, the roofing system, HVAC units and, possibly, landscaping. Most decks must also act as a diaphragm, transmitting wind or seismic lateral forces to the buildings structural framework.
:* A vented base sheet is required under all asphalt-adhered (adhesive, mopped or torched) roofing membranes that are adhered directly to concrete decks unless insulation is installed directly above or over the membrane.
+
* As a suitable substrate to which the roof membrane or roof system is attached.  
 +
<br>
 +
Prior to the application of the roof system, the deck must be smooth, straight, and free of "humps" or depressions.  These can counteract any sloped insulation systems installed by the roofing contractor and cause ponding.  On new construction projects, this is usually provided by the general contractor with review by the design authority and/or the building authority having jurisdiction.
  
:Pre-cast panels, post-stressed beams, or “T” and cavity decks <del>shall</del> '''''must''''' have a separation layer such as fibre board, gypsum board, plywood, proprietary overlay board etc. applied over the deck prior to the application of the roof membrane. Where a difference exists in the levels of adjacent surfaces, the general contractor or others shall install grouting. This grouting shall be feathered on the lower surface a minimum distance of twelve times the amount of the vertical differential.
+
The use of EPDM membranes in loose laid ballasted or loose laid protected membrane assemblies over concrete decks is '''not''' permitted '''unless''' a membrane underlay (recommended in writing by the membrane manufacturer) is installed.  
  
<b>Steel</b>
+
In addition, the roof deck must comply with several guiding principles, to be acceptable for a '''''RoofStar Guarantee''''':
  
When a membrane is specified for application directly over a steel deck, the RoofStar Guarantee Standards require a steel deck overlay of gypsum with fibreglass facers and a silicone treated gypsum core (see min. standards below), or plywood having a minimum thickness of 12.7 mm (1/2"). Where an underlay is used as a thermal barrier, it must conform to the applicable code and insurance requirements for the roof assembly.
+
* <span class="principles">For low slope (membrane roof or waterproofing systems) it should provide positive slope to drain (required for a '''''RoofStar 5-Year Roofing Guarantee''''', '''''RoofStar 10-Year Roofing Guarantee''''', or a '''''RoofStar 5-Year Waterproofing Guarantee''''' for new construction and for organic felt membrane systems when re-roofing). Positive slope to drain is attained when no standing water remains on the deck within a reasonable amount of time after rainfall stops during days with conditions that permit evaporation. Where required, crickets and saddles should be provided to assist drainage. Slope can be provided by sloping the deck, or using tapered insulation boards or insulating fill (insulating fill is rarely used in B.C.). Tapered slope insulation products can only be used to provide slope if any differences from level in the roof deck are less than the percentage of slope provided by the insulation.</span>  <span class="recommended">A minimum slope of 1:50 (1/4" in 12") is strongly recommended. The exception is often drain wells that are designed to collect water and provide a flat surface for the installation of roof drains.</span>  <span class="principles">Therefore, standing water may remain in drain wells for a longer period of time after a rainfall stops</span>.
 +
* <span class="principles">It should be dimensionally stable and capable of accommodating roof system component movement.</span>
 +
* <p class="principles">Deck deflections should be limited to 1/240 of the total span, but must conform to the Building Code. For plywood decks, the '''''RoofStar Guarantee Program Standards''''' limit the allowable deck deflection to 1/360 of the total span to prevent differential edge movement. Concentrated, non-uniform construction loads should be considered during design. Drains should be located at points of maximum deflection whenever possible, not over columns or bearing walls.  Building settlement can often cause slopes to change and low spots to appear on the roof surface.</p>
  
:.1 <u>Gypsum Board on Steel Decks</u>
+
<p class="principles">Prior to the commencement of roofing, any curbs, cants and blocking that are to be installed by others, should be in place.</p>
Gypsum boards installed over steel decks as substrates for primary roof membranes <b><u>must</u></b> be a minimum thickness of 12.7 mm (1/2") RGC accepted overlay boards. All edges of the gypsum board are to be fully or intermittently supported by the deck and end joints to be staggered (offset) 300 mm (12") from adjacent board rows. A minus offset tolerance of 50 mm (2") maximum will be permitted to compensate for variance in the manufacturers&rsquo; tolerance of differing board widths and lengths.
 
  
:.2 <u>Gypsum Board Attachment on Steel Decks</u>
+
===Deck Types===
When gypsum board is required on steel decks as a substrate overlay, {{hilite | the gypsum board can be fully mechanically fastened to the deck or adhered with proprietary polyurethane foam adhesives acceptable to the primary roof system manufacturer. Attachment must meet or exceed the CSA A123.21-14 requirements for the building dimensions and geographical location. || 2015-12-9 }}
+
==== Wood Decks ====
 +
Wood is a common construction material that has been used for many years because of its economy, ease of fabrication, lighter construction, and ready availability. Acceptable wood roof decks may include wood board decks, plywood decks, and, subject to restrictions, non-veneered wood decks (oriented strand board, waferboard, etc.). <span class="principles">All types of wood decks should be roofed promptly after installation.</span>
  
RGC maximum deck flute width and minimum fastener requirements for gypsum board in a deck overlay application are as follows:<table border="1" cellspacing="0" cellpadding="0" width="90%">
+
All wood decks shall be properly fastened to BC Building Code requirements. With the exception of standard insulated roof systems, all knots or cracks shall be covered with metal prior to acceptance of deck surface.  This work is to be done by others.  <span class="principles">Non-veneer (O.S.B. or wafer board) panels are acceptable sheathing for decks with low-slope roofing applications, provided the roofing membrane is not fully adhered directly to the panels.</span> The minimum plywood or non-veneer (O.S.B or wafer board) deck thickness for low-slope roofing (i.e., membrane roofing) shall be a minimum 12.7 mm (½") and as indicated in the applicable Building Code.
<tr>
 
<td align=center>
 
Gypsum Board <u>Thickness</u>
 
</td>
 
<td align=center>
 
<u>Deck Flute Width</u>
 
</td>
 
<td align=center>
 
<u>Gypsum Board Size</u>
 
</td>
 
<td align=center>
 
Screws &amp; Metal or <u>Plastic Stress Plates</u>
 
</td>
 
<td align=center>
 
Bugle Head <u>Drywall Screws</u>
 
</td>
 
</tr>
 
<tr>
 
<td align=center>
 
12.7mm (&frac12;")</td>
 
<td align=center>
 
up to 125mm (5")
 
</td>
 
<td align=center>
 
1200 mm x 2400 mm (4' x 8&rsquo;)
 
</td>
 
<td align=center>
 
12
 
</td>
 
<td align=center>
 
32
 
</td>
 
</tr>
 
<tr>
 
<td align=center>
 
15.9mm (5/8")
 
</td>
 
<td align=center>
 
up to 200mm (8")
 
</td>
 
<td align=center>1200 mm x 2400 mm (4&rsquo; x 8&rsquo;)
 
</td>
 
<td align=center>
 
12
 
</td>
 
<td align=center>
 
32
 
</td>
 
</tr>
 
</table>
 
  
When gypsum board is used under mechanically fastened insulation, the gypsum board must be fastened independently from the insulation. The minimum number of fasteners(screws or screws and plate) is four (4) per sheet.  {{hilite | Adhesive systems must meet or exceed the CSA A123.21-14 requirements for the building dimensions and geographical location. || 2015-12-9 }}
+
<p class="principles">All types of wood decks should be roofed promptly after installation.</p>
</div>
 
  
<b>Wood</b>
+
Differential edge movements or deflection in excess of 1/360 of the span in plywood or non-veneer decks in low slope roofing must be prevented by:
All wood decks shall be properly fastened to B.C.Building Code requirements. With the exception of standard insulated roof systems, all knots or cracks shall be covered with metal prior to acceptance of deck surface.This work is to be done by others.  <span class="principles">Non-veneer (O.S.B. or wafer board) panels are acceptable sheathing for decks with low-slope roofing applications, provided the roofing membrane is not fully adhered directly to the panels.</span> The minimum plywood or non-veneer (O.S.B or wafer board) deck thickness for low-slope roofing (i.e., membrane roofing) shall be a minimum 12.7 mm (1/2")and as indicated in the applicable Building Code.
+
* solid blocking under non-supported edges, and /or
 +
* use of tongue-and-groove plywood with non-grooved edges supported by joists or solid blocking, and / or
 +
* when rigid insulation is over the deck, properly sized and installed H-clips must be used on the unsupported edges.
 +
 
 +
===== '''Wood Board Decks''' =====
 +
<p class="reference">Wood board decks include tongue-and-groove, shiplapped, or splined boards or planks usually ranging from 19 mm to 89 mm (nominal 1" to 4") thickness.  Also 38 mm (nominal 2") by various width boards, placed on end, can be spiked together to form a &#8220;mill deck&#8221;. The thickness of the boards is determined by the anticipated loads and spacing of roof joists or trusses (consult Building Code).</p>
 +
 
 +
<p class="principles">Wood board decks should be of sound seasoned lumber, properly secured to supporting structure. The deck should form a firm smooth surface, free from knotholes, cracks, projections, depressions and other defects. Prior to the roofing contractor's acceptance of the deck, minor knotholes and cracks should be covered with securely nailed sheet metal (performed by others).</p>
 +
 
 +
<span class="principles">Wood board decks, especially mill decks, often have so many surface defects that a plywood overlay is desirable (9.5 mm (⅜") plywood is often acceptable).</span>  Where a plywood overlay is not required, a mechanically fastened base sheet or separator sheet is required for built-up roofs or fully-adhered bituminous or modified bituminous flexible roofing membranes. For non-bituminous flexible membranes (elastomeric or plastomeric membranes such as EPDM or PVC), a slip sheet or separator sheet should be installed according to membrane manufacturer's recommendations. Separation sheets, slip sheets, and mechanically fastened base sheets are installed to help relieve stresses in the membrane due to movement of the deck.
 +
 
 +
===== '''Plywood Decks''' =====
 +
<span class="reference">Plywood roof decks consist of exterior type plywood mechanically fastened to the roof framing.</span> <span class="principles">The plywood panels should conform to CSA 0121, &#8220;Douglas Fir Plywood&#8221;, CSA 0151, &#8220;Canadian Softwood Plywood&#8221;, or CSA 0153, &#8220;Poplar Plywood&#8221;, as per Building Code requirements.</span>
 +
 
 +
These thickness / span ratios will minimize deck deflection, especially with construction loads, and will provide a better surface for nailing as the bouncing effect of thin plywood&#8217;s is reduced.
 +
 
 +
For low slope roofing (e.g. BUR), plywood must be minimum 12.7 mm (1/2") thick unless mechanically attached rigid insulation is installed prior to the roofing membrane. The minimum centres for supporting members are:
 +
:* 400 mm (16") for 12.7 mm (1/2") plywood sheathing
 +
:* 600 mm (24") for 15.9 mm (5/8") plywood sheathing
 +
For low-slope roofing, differential edge movement and deflection in excess of 1/360 of the span must be prevented by:
 +
 
 +
:* solid blocking under non-supported edges, and / or
 +
:* use of tongue-and-groove plywood with non-grooved edges supported by joists or solid blocking, and / or
 +
:* when rigid insulation is over the deck, properly sized and installed H-clips should be used on the unsupported edges.
 +
 
 +
Plywood roof sheathing should be installed with the surface grain at right angles to the roof framing, with end joints staggered.
 +
 
 +
<span class="principles">Plywood decks receiving roofing directly applied to the deck should be attached using wood screws or nails which are especially resistant to pull-out or nail popping, particularly when using a single-ply membrane (i.e., use ring-type or ardox; smooth common nails are not acceptable).</span> <span class="reference">Nail popping is usually caused by a combination of thermal and structural movement and is especially critical where the membrane is directly adhered to the deck.</span> <span class="principles">All fasteners should have a corrosion-resistant coating (such as galvanizing). The structural suitability of the fastener is the responsibility of the design authority.</span>
 +
 
 +
===== '''Non-veneer Wood Decks''' =====
 +
<p class="reference">Non-veneer panels are identified as waferboard or oriented strand board (OSB) panels, as opposed to plywood or veneered panels.</p>
 +
 
 +
Non-veneer (O.S.B. or waferboard) panels are acceptable decks on low-slope roofing applications when an approved separation sheet or rigid insulation is mechanically attached before fully adhered roofing membrane is applied.
 +
 
 +
==== Concrete Decks ====
 +
<p class="reference">Concrete roof decks include decks that are cast-in-place or pre-cast, and structural or non-structural in nature. Although this roof deck category includes numerous variations (discussed later), many of the precautions involved with roofing over them are similar.</p>
 +
 
 +
<p class="principles">The finished surface of the deck should be smooth, level, and free of moisture or frost. All ridges or projections should be removed; and curbs, cants, blocking, and nailing strips should be installed where required prior to the roofing contractor's acceptance of the deck. With cast-in-place decks, special care must be taken to ensure that the deck is cured for 28 days and that the surface is dry. (A simple test for determining whether the deck is dry enough for roofing is to apply hot asphalt to the deck; if it foams or is easily peeled off after it cools, the deck is too wet.) Pre-cast decks may require joints to be &#8220;taped&#8221; or stripped-in with felts, and the joints, weld plates, and elevation differences to be feathered with grout.</p>
 +
 
 +
Concrete decks, curbs and equipment pads must be clean, dry, and smooth prior to commencement of roofing.
 +
 
 +
Poured concrete or lightweight concrete decks are not to be roofed for a minimum of 28 days after pouring unless expressly instructed in writing by the Project Structural Engineer.
 +
 
 +
<p class="reference">Although some concrete decks are considered &#8220;nailable&#8221;, insulation is most commonly attached by using proprietary adhesives, or by applying hot asphalt over a primed deck. In the latter case, the asphalt is mopped to the deck and allowed to cool to the point where the insulation is not melted, but is still sufficiently bonded to the deck.</p>
 +
 
 +
<p class="principles">Built-up roof membranes can be directly adhered to both cast-in-place decks and, provided precautions are taken, to pre-cast decks. Vented base sheets may be used to provide semi-adherence to the roof deck.</p>
 +
 
 +
<span class="reference">Concrete roof decks include:</span>
 +
* <span class="reference">Cast-in-place reinforced concrete</span>
 +
* <span class="reference">Pre-cast concrete panels</span>
 +
* <span class="reference">Pre-stressed concrete</span>
 +
* <span class="reference">Lightweight insulating concrete</span>
 +
* <p class="reference">Poured gypsum concrete</p>
 +
 
 +
<p class="reference">A cast-in-place reinforced concrete roof deck is produced by pouring concrete into formwork containing reinforcing steel bars or welded steel mesh. The surface of deck should be screeded and trowelled to provide a smooth, level surface. Caution should be exercised when using certain curing agents and techniques. Curing agents may not be compatible with roofing materials and some curing techniques do not allow the deck to dry sufficiently.</p>
 +
 
 +
<p class="reference">Pre-cast concrete-panel roof decks consist of manufactured panels designed to span between beams or load-bearing walls. They are available in the following cross-sectional shapes: single &#8220;T&#8221;, double &#8220;T&#8221;, solid slabs, hollow-core slabs, inverted channels, and tongue-and-groove planks. Metal plates may be installed to provide a welded structural connection and lateral bracing.</p>
 +
 
 +
<p class="reference">Pre-stressed concrete roof decks consist of concrete (usually pre-cast panels) that is pre-stressed using integral steel tendon reinforcement. The unit is compressed to counteract flexural tensile stresses which usually result in a cambered unit (a slight curve that results in the centre of the unit being higher than the supporting ends). The camber will usually flatten once the structure is loaded.</p>
 +
 
 +
<p class="reference">Lightweight insulating concrete roof decks and fills consist of concrete mixtures that have vermiculite or perlite as insulating aggregates, or they may also be produced by mixing pre-generated foam with Portland cement and water. This type of deck is usually designed for application over steel decks, corrugated metal forms, or bulb-tee or formboard systems. The concrete mixture is placed and screeded on site. Usually these mixes use a very high water / cement ratio and may require a lengthy cure time and a vented base sheet because of high moisture content. Vented base sheets provide a path for moisture vapour to vent to an appropriate point where the vapour may be released.</p>
 +
 
 +
<p class="reference">Poured gypsum concrete roof decks consist of a mixture of gypsum concrete, wood fibres or mineral aggregate, and water. The mixture is poured into formboards that contain welded or woven galvanized wire fabric. The formboards are left in place and may provide the finished interior surface.</p>
 +
 
 +
==== Steel Decks ====
 +
<p class="reference">Steel roof decks are constructed of light gauge (usually 22, 20, or 18 gauge) cold-rolled steel sections (panels) that are usually galvanized. In cross-section the panels are ribbed, with the ribs usually spaced at 150 mm (6") on centre. The ribs provide the strength and rigidity of the panels. Steel decks are generally supported by open-web steel joist framing and are welded or mechanically-fastened to the framework. Steel deck panels must be properly aligned, squarely intersect walls, and provide a smooth level surface for roofing.</p>
 +
 
 +
<span class="principles">For insulated roof assemblies, a thermal barrier may be required to conform with Building Code or fire insurance-rated assemblies. This is usually required where the insulation is classified as combustible.</span> Uninsulated systems require a leveling underlay for the membrane. Gypsum board may serve both purposes (thermal barrier & level surface).
 +
 
 +
<span class="principles">Minimum thickness of insulations should be checked carefully to ensure that the material can safely span the flutes.</span> The insulation or insulation overlay must be mechanically-fastened to the deck, unless it is a ballasted system.
 +
 
 +
'''<u>Corrosion Protection For New Steel Roof Decks</u>'''
 +
 
 +
<p class="recommended">When steel roof decks are specified, the '''''RoofStar Guarantee Program''''' recommends that the design authority specify the decking be factory-galvanized or factory-coated with aluminum zinc alloy for corrosion protection.</p>
 +
 
 +
<p class="principles">When specifying galvanized protection (in the section of the specifications addressing metal decking), the design authority should specify a coating that complies with ASTM A 525 Class G-60 or Class G-90. A G-90 coating provides greater corrosion protection than a G-60 coating (the ASTM specification previously identified G-60 as &#8220;light commercial&#8221; and G-90 as &#8220;commercial&#8221;).</p>
 +
 
 +
<p class="principles">When specifying aluminium zinc alloy protection (in the section of the specification addressing metal decking), the design authority should specify a coating that complies with ASTM A 792. An aluminum zinc alloy coating provides greater corrosion protection than a G-90 galvanized coating.</p>
  
An RGC approved separation sheet, minimum#40 asphalt coated fibre glass base sheet conforming to CAN/ CSA A123.16 - M88 (R1996), Type II or manufacturer’s accepted base sheet of equal or greater weight and reinforcement, or RGC accepted rigid insulation / overlay board mechanically attached or semi-adhered membrane (spot or strips) is required over non-veneer panels before fully adhered roofing membrane is applied.
+
<p class="principles">'''NOTE''':  The above recommendation applies to most buildings. However, in highly corrosive or chemical atmospheres, special care in specifying protective finishes should be taken, and individual deck manufacturers should be contacted.</p>
  
<p class="principles">Direct torch (open flame) membrane applications to wood decks and wood surfaces is NOT permitted. For further development of this policy, refer to SBS Application & Safety: Best Practices.</p>
+
=== Roof Expansion Joints ===
 +
(See '''[[Section:G. Construction Details|Construction Details]]''' to view the illustrated application of '''''RoofStar Guarantee Standards''''' for various membrane assemblies)
  
Differential edge movements or deflection in excess of1/360 of the span in plywood or non-veneer decks in low slope roofing must be prevented by:  
+
<p class="reference">Roof expansion joints are designed to prevent membrane splitting and ridging (caused by either movement of the building, or movement of the roof assembly due to thermal expansion and contraction).</p>
* solid blocking under non-supported edges, and /or
+
 
* use of tongue-and-groove plywood with non-grooved edges supported by joists or solid blocking, and / or  
+
<span class="principles">Roof expansion joints should be considered wherever:</span>
* when rigid insulation is over the deck, properly sized and installed H-clips must be used on the unsupported edges.
+
* <span class="principles">the type of deck changes</span>
 +
* <span class="principles">additions connect to existing buildings</span>
 +
* <span class="principles">expansion and control joints exist in the structural system</span>
 +
* <span class="principles">separate wings of a building join (e.g. &#8220;L&#8221; or &#8220;T&#8221; configurations)</span>
 +
* <span class="principles">interior heating conditions change</span>
 +
* <p class="principles">differential movement may occur (e.g. parapet detail where the deck is not supported by the wall)</p>
 +
 
 +
The location of roof expansion joints must be clearly indicated on the drawings and in the specifications, as the installation of wood blocking and cants is the responsibility of &#8220;others&#8221; and must be in place prior to the roofing contractor's acceptance of the deck.
 +
 
 +
=== Roof Divider / Control Joints ===
 +
(See '''[[Section:G. Construction Details|Construction Details]]''' to view the illustrated application of '''''RoofStar Guarantee Standards''''' for various membrane assemblies)
 +
 
 +
<p class="reference">Roof dividers (sometimes referred to as control joints or area dividers) are built on-site. They are designed to help control thermal expansion and contraction stresses in the roof system where no structural expansion joint has been provided in the building design. Roof dividers are especially useful for controlling stress concentration in the membrane, and should be considered (and may be required) on all fully-adhered roof membrane systems.</p>
 +
 
 +
<span class="reference">A roof divider is usually designed as two raised wood members attached to a wood base-plate that is securely anchored to the roof deck and then properly flashed with membrane and metal.</span>  Roof dividers should divide the roof into approximately equal, regularly-shaped areas. Ideally, roof dividers should be located at the high points of the roof, with drainage away from the divider on both sides, but DRAINAGE MUST NOT BE IMPEDED BY THE ROOF DIVIDER.
 +
 
 +
'''''RoofStar Guarantee Standards''''' for a '''''RoofStar 5-Year Roofing Guarantee''''' or '''''RoofStar 10-Year Roofing Guarantee''''' for built-up roof membrane requires roof dividers / control joints &#8220;to divide roofs into areas approximately 45 m x 45 m (150' x 150'), at changes of deck material and decking direction, at re-entrant corners, and at junctions or additions to existing structure.
 +
 
 +
The location of roof dividers must be clearly indicated on the drawings and in the specifications, as the installation of wood blocking and cants is the responsibility of others and must be in place prior to the roofing contractor's acceptance of the deck.
 +
 
 +
<b>NOTE</b> that the requirement for roof divider / control joints for flexible membranes differs, and must be evaluated on a product performance basis.
 +
 
 +
===Special Circumstances: Electrical Conduit===
 +
 
 +
Conduit, EMT, cable and/or piping applied on the top of roof deck surfaces shall not be acceptable on new construction projects.
  
Fully adhering modified bituminous membranes directly to wood decks is not permitted.
+
If conduit is present on decks in re-roofing projects, the deck must be made smooth and even to the satisfaction of the accepted roof inspection firm. The upper layer of insulation must cover the conduit, EMT, cable and/or piping.  Detailed as-built drawings should be made to prevent conduit damage and safety risks to roofers, should the roof require replacement at a future date.
  
<b>SPECIAL CIRCUMSTANCES</b>
 
('''''Electrical Conduit''''')
 
<div class="principles">Conduit, EMT, cable and/or piping applied on the top of roof deck surfaces shall not be acceptable on new construction projects.
 
  
If conduit is present on decks in re-roofing projects, the deck must be made smooth and even to the satisfaction of the accepted roof inspection firm. The upper layer of insulation must cover the conduit, EMT, cable and/or piping.</div>
+
For more about this topic, see the published '''Safety Bulletin''' in the November 10, 2015 [http://www.rcabc.org/technical/technical-updates/ '''Technical Update'''].
 +
<div id="EPDMWIND"></div>
 +
<div id="TPOWIND"></div>
 +
<div id="EPDM4"></div>
 +
<div id="TPO4"></div>

Latest revision as of 15:18, 15 January 2019

1 General

The roof deck must be designed to serve two major functions:

  • As a structural component to transfer the weight of live and dead loads to supporting members. Live loads include construction equipment and workers, rain, snow, and ice. Dead loads include the deck itself, the roofing system, HVAC units and, possibly, landscaping. Most decks must also act as a diaphragm, transmitting wind or seismic lateral forces to the buildings structural framework.
  • As a suitable substrate to which the roof membrane or roof system is attached.


Prior to the application of the roof system, the deck must be smooth, straight, and free of "humps" or depressions. These can counteract any sloped insulation systems installed by the roofing contractor and cause ponding. On new construction projects, this is usually provided by the general contractor with review by the design authority and/or the building authority having jurisdiction.

The use of EPDM membranes in loose laid ballasted or loose laid protected membrane assemblies over concrete decks is not permitted unless a membrane underlay (recommended in writing by the membrane manufacturer) is installed.

In addition, the roof deck must comply with several guiding principles, to be acceptable for a RoofStar Guarantee:

  • For low slope (membrane roof or waterproofing systems) it should provide positive slope to drain (required for a RoofStar 5-Year Roofing Guarantee, RoofStar 10-Year Roofing Guarantee, or a RoofStar 5-Year Waterproofing Guarantee for new construction and for organic felt membrane systems when re-roofing). Positive slope to drain is attained when no standing water remains on the deck within a reasonable amount of time after rainfall stops during days with conditions that permit evaporation. Where required, crickets and saddles should be provided to assist drainage. Slope can be provided by sloping the deck, or using tapered insulation boards or insulating fill (insulating fill is rarely used in B.C.). Tapered slope insulation products can only be used to provide slope if any differences from level in the roof deck are less than the percentage of slope provided by the insulation. A minimum slope of 1:50 (1/4" in 12") is strongly recommended. The exception is often drain wells that are designed to collect water and provide a flat surface for the installation of roof drains. Therefore, standing water may remain in drain wells for a longer period of time after a rainfall stops.
  • It should be dimensionally stable and capable of accommodating roof system component movement.
  • Deck deflections should be limited to 1/240 of the total span, but must conform to the Building Code. For plywood decks, the RoofStar Guarantee Program Standards limit the allowable deck deflection to 1/360 of the total span to prevent differential edge movement. Concentrated, non-uniform construction loads should be considered during design. Drains should be located at points of maximum deflection whenever possible, not over columns or bearing walls. Building settlement can often cause slopes to change and low spots to appear on the roof surface.

Prior to the commencement of roofing, any curbs, cants and blocking that are to be installed by others, should be in place.

2 Deck Types

2.1 Wood Decks

Wood is a common construction material that has been used for many years because of its economy, ease of fabrication, lighter construction, and ready availability. Acceptable wood roof decks may include wood board decks, plywood decks, and, subject to restrictions, non-veneered wood decks (oriented strand board, waferboard, etc.). All types of wood decks should be roofed promptly after installation.

All wood decks shall be properly fastened to BC Building Code requirements. With the exception of standard insulated roof systems, all knots or cracks shall be covered with metal prior to acceptance of deck surface. This work is to be done by others. Non-veneer (O.S.B. or wafer board) panels are acceptable sheathing for decks with low-slope roofing applications, provided the roofing membrane is not fully adhered directly to the panels. The minimum plywood or non-veneer (O.S.B or wafer board) deck thickness for low-slope roofing (i.e., membrane roofing) shall be a minimum 12.7 mm (½") and as indicated in the applicable Building Code.

All types of wood decks should be roofed promptly after installation.

Differential edge movements or deflection in excess of 1/360 of the span in plywood or non-veneer decks in low slope roofing must be prevented by:

  • solid blocking under non-supported edges, and /or
  • use of tongue-and-groove plywood with non-grooved edges supported by joists or solid blocking, and / or
  • when rigid insulation is over the deck, properly sized and installed H-clips must be used on the unsupported edges.
2.1.1 Wood Board Decks

Wood board decks include tongue-and-groove, shiplapped, or splined boards or planks usually ranging from 19 mm to 89 mm (nominal 1" to 4") thickness. Also 38 mm (nominal 2") by various width boards, placed on end, can be spiked together to form a “mill deck”. The thickness of the boards is determined by the anticipated loads and spacing of roof joists or trusses (consult Building Code).

Wood board decks should be of sound seasoned lumber, properly secured to supporting structure. The deck should form a firm smooth surface, free from knotholes, cracks, projections, depressions and other defects. Prior to the roofing contractor's acceptance of the deck, minor knotholes and cracks should be covered with securely nailed sheet metal (performed by others).

Wood board decks, especially mill decks, often have so many surface defects that a plywood overlay is desirable (9.5 mm (⅜") plywood is often acceptable). Where a plywood overlay is not required, a mechanically fastened base sheet or separator sheet is required for built-up roofs or fully-adhered bituminous or modified bituminous flexible roofing membranes. For non-bituminous flexible membranes (elastomeric or plastomeric membranes such as EPDM or PVC), a slip sheet or separator sheet should be installed according to membrane manufacturer's recommendations. Separation sheets, slip sheets, and mechanically fastened base sheets are installed to help relieve stresses in the membrane due to movement of the deck.

2.1.2 Plywood Decks

Plywood roof decks consist of exterior type plywood mechanically fastened to the roof framing. The plywood panels should conform to CSA 0121, “Douglas Fir Plywood”, CSA 0151, “Canadian Softwood Plywood”, or CSA 0153, “Poplar Plywood”, as per Building Code requirements.

These thickness / span ratios will minimize deck deflection, especially with construction loads, and will provide a better surface for nailing as the bouncing effect of thin plywood’s is reduced.

For low slope roofing (e.g. BUR), plywood must be minimum 12.7 mm (1/2") thick unless mechanically attached rigid insulation is installed prior to the roofing membrane. The minimum centres for supporting members are:

  • 400 mm (16") for 12.7 mm (1/2") plywood sheathing
  • 600 mm (24") for 15.9 mm (5/8") plywood sheathing

For low-slope roofing, differential edge movement and deflection in excess of 1/360 of the span must be prevented by:

  • solid blocking under non-supported edges, and / or
  • use of tongue-and-groove plywood with non-grooved edges supported by joists or solid blocking, and / or
  • when rigid insulation is over the deck, properly sized and installed H-clips should be used on the unsupported edges.

Plywood roof sheathing should be installed with the surface grain at right angles to the roof framing, with end joints staggered.

Plywood decks receiving roofing directly applied to the deck should be attached using wood screws or nails which are especially resistant to pull-out or nail popping, particularly when using a single-ply membrane (i.e., use ring-type or ardox; smooth common nails are not acceptable). Nail popping is usually caused by a combination of thermal and structural movement and is especially critical where the membrane is directly adhered to the deck. All fasteners should have a corrosion-resistant coating (such as galvanizing). The structural suitability of the fastener is the responsibility of the design authority.

2.1.3 Non-veneer Wood Decks

Non-veneer panels are identified as waferboard or oriented strand board (OSB) panels, as opposed to plywood or veneered panels.

Non-veneer (O.S.B. or waferboard) panels are acceptable decks on low-slope roofing applications when an approved separation sheet or rigid insulation is mechanically attached before fully adhered roofing membrane is applied.

2.2 Concrete Decks

Concrete roof decks include decks that are cast-in-place or pre-cast, and structural or non-structural in nature. Although this roof deck category includes numerous variations (discussed later), many of the precautions involved with roofing over them are similar.

The finished surface of the deck should be smooth, level, and free of moisture or frost. All ridges or projections should be removed; and curbs, cants, blocking, and nailing strips should be installed where required prior to the roofing contractor's acceptance of the deck. With cast-in-place decks, special care must be taken to ensure that the deck is cured for 28 days and that the surface is dry. (A simple test for determining whether the deck is dry enough for roofing is to apply hot asphalt to the deck; if it foams or is easily peeled off after it cools, the deck is too wet.) Pre-cast decks may require joints to be “taped” or stripped-in with felts, and the joints, weld plates, and elevation differences to be feathered with grout.

Concrete decks, curbs and equipment pads must be clean, dry, and smooth prior to commencement of roofing.

Poured concrete or lightweight concrete decks are not to be roofed for a minimum of 28 days after pouring unless expressly instructed in writing by the Project Structural Engineer.

Although some concrete decks are considered “nailable”, insulation is most commonly attached by using proprietary adhesives, or by applying hot asphalt over a primed deck. In the latter case, the asphalt is mopped to the deck and allowed to cool to the point where the insulation is not melted, but is still sufficiently bonded to the deck.

Built-up roof membranes can be directly adhered to both cast-in-place decks and, provided precautions are taken, to pre-cast decks. Vented base sheets may be used to provide semi-adherence to the roof deck.

Concrete roof decks include:

  • Cast-in-place reinforced concrete
  • Pre-cast concrete panels
  • Pre-stressed concrete
  • Lightweight insulating concrete
  • Poured gypsum concrete

A cast-in-place reinforced concrete roof deck is produced by pouring concrete into formwork containing reinforcing steel bars or welded steel mesh. The surface of deck should be screeded and trowelled to provide a smooth, level surface. Caution should be exercised when using certain curing agents and techniques. Curing agents may not be compatible with roofing materials and some curing techniques do not allow the deck to dry sufficiently.

Pre-cast concrete-panel roof decks consist of manufactured panels designed to span between beams or load-bearing walls. They are available in the following cross-sectional shapes: single “T”, double “T”, solid slabs, hollow-core slabs, inverted channels, and tongue-and-groove planks. Metal plates may be installed to provide a welded structural connection and lateral bracing.

Pre-stressed concrete roof decks consist of concrete (usually pre-cast panels) that is pre-stressed using integral steel tendon reinforcement. The unit is compressed to counteract flexural tensile stresses which usually result in a cambered unit (a slight curve that results in the centre of the unit being higher than the supporting ends). The camber will usually flatten once the structure is loaded.

Lightweight insulating concrete roof decks and fills consist of concrete mixtures that have vermiculite or perlite as insulating aggregates, or they may also be produced by mixing pre-generated foam with Portland cement and water. This type of deck is usually designed for application over steel decks, corrugated metal forms, or bulb-tee or formboard systems. The concrete mixture is placed and screeded on site. Usually these mixes use a very high water / cement ratio and may require a lengthy cure time and a vented base sheet because of high moisture content. Vented base sheets provide a path for moisture vapour to vent to an appropriate point where the vapour may be released.

Poured gypsum concrete roof decks consist of a mixture of gypsum concrete, wood fibres or mineral aggregate, and water. The mixture is poured into formboards that contain welded or woven galvanized wire fabric. The formboards are left in place and may provide the finished interior surface.

2.3 Steel Decks

Steel roof decks are constructed of light gauge (usually 22, 20, or 18 gauge) cold-rolled steel sections (panels) that are usually galvanized. In cross-section the panels are ribbed, with the ribs usually spaced at 150 mm (6") on centre. The ribs provide the strength and rigidity of the panels. Steel decks are generally supported by open-web steel joist framing and are welded or mechanically-fastened to the framework. Steel deck panels must be properly aligned, squarely intersect walls, and provide a smooth level surface for roofing.

For insulated roof assemblies, a thermal barrier may be required to conform with Building Code or fire insurance-rated assemblies. This is usually required where the insulation is classified as combustible. Uninsulated systems require a leveling underlay for the membrane. Gypsum board may serve both purposes (thermal barrier & level surface).

Minimum thickness of insulations should be checked carefully to ensure that the material can safely span the flutes. The insulation or insulation overlay must be mechanically-fastened to the deck, unless it is a ballasted system.

Corrosion Protection For New Steel Roof Decks

When specifying galvanized protection (in the section of the specifications addressing metal decking), the design authority should specify a coating that complies with ASTM A 525 Class G-60 or Class G-90. A G-90 coating provides greater corrosion protection than a G-60 coating (the ASTM specification previously identified G-60 as “light commercial” and G-90 as “commercial”).

When specifying aluminium zinc alloy protection (in the section of the specification addressing metal decking), the design authority should specify a coating that complies with ASTM A 792. An aluminum zinc alloy coating provides greater corrosion protection than a G-90 galvanized coating.

NOTE: The above recommendation applies to most buildings. However, in highly corrosive or chemical atmospheres, special care in specifying protective finishes should be taken, and individual deck manufacturers should be contacted.

3 Roof Expansion Joints

(See Construction Details to view the illustrated application of RoofStar Guarantee Standards for various membrane assemblies)

Roof expansion joints are designed to prevent membrane splitting and ridging (caused by either movement of the building, or movement of the roof assembly due to thermal expansion and contraction).

Roof expansion joints should be considered wherever:

  • the type of deck changes
  • additions connect to existing buildings
  • expansion and control joints exist in the structural system
  • separate wings of a building join (e.g. “L” or “T” configurations)
  • interior heating conditions change
  • differential movement may occur (e.g. parapet detail where the deck is not supported by the wall)

The location of roof expansion joints must be clearly indicated on the drawings and in the specifications, as the installation of wood blocking and cants is the responsibility of “others” and must be in place prior to the roofing contractor's acceptance of the deck.

4 Roof Divider / Control Joints

(See Construction Details to view the illustrated application of RoofStar Guarantee Standards for various membrane assemblies)

Roof dividers (sometimes referred to as control joints or area dividers) are built on-site. They are designed to help control thermal expansion and contraction stresses in the roof system where no structural expansion joint has been provided in the building design. Roof dividers are especially useful for controlling stress concentration in the membrane, and should be considered (and may be required) on all fully-adhered roof membrane systems.

A roof divider is usually designed as two raised wood members attached to a wood base-plate that is securely anchored to the roof deck and then properly flashed with membrane and metal. Roof dividers should divide the roof into approximately equal, regularly-shaped areas. Ideally, roof dividers should be located at the high points of the roof, with drainage away from the divider on both sides, but DRAINAGE MUST NOT BE IMPEDED BY THE ROOF DIVIDER.

RoofStar Guarantee Standards for a RoofStar 5-Year Roofing Guarantee or RoofStar 10-Year Roofing Guarantee for built-up roof membrane requires roof dividers / control joints “to divide roofs into areas approximately 45 m x 45 m (150' x 150'), at changes of deck material and decking direction, at re-entrant corners, and at junctions or additions to existing structure.

The location of roof dividers must be clearly indicated on the drawings and in the specifications, as the installation of wood blocking and cants is the responsibility of others and must be in place prior to the roofing contractor's acceptance of the deck.

NOTE that the requirement for roof divider / control joints for flexible membranes differs, and must be evaluated on a product performance basis.

5 Special Circumstances: Electrical Conduit

Conduit, EMT, cable and/or piping applied on the top of roof deck surfaces shall not be acceptable on new construction projects.

If conduit is present on decks in re-roofing projects, the deck must be made smooth and even to the satisfaction of the accepted roof inspection firm. The upper layer of insulation must cover the conduit, EMT, cable and/or piping. Detailed as-built drawings should be made to prevent conduit damage and safety risks to roofers, should the roof require replacement at a future date.


For more about this topic, see the published Safety Bulletin in the November 10, 2015 Technical Update.