Difference between revisions of "Template:ROOFTOP GARDENS, PLANTERS & WALKWAYS (SBS)"
Difference between revisions of "Template:ROOFTOP GARDENS, PLANTERS & WALKWAYS (SBS)"
(→Planters) |
(→Planters) |
||
Line 42: | Line 42: | ||
====Planters==== | ====Planters==== | ||
− | <p class="principles">Structural planters that incorporate pre-curb or start-up curbs for walls that are completely sealed with membrane and are a minimum of 100 mm (4") in height, as detailed in [[ | + | <p class="principles">Structural planters that incorporate pre-curb or start-up curbs for walls that are completely sealed with membrane and are a minimum of 100 mm (4") in height, as detailed in Construction Detail [[SBS Details:D1.7.6-5 Curbs & Sleepers (Pre-curb for Planters)|'''D1.7.6-5 Curbs & Sleepers (Pre-curb for Planters)''']], qualify for '''''RoofStar Guarantee''''' coverage. Waterproofing liners in planters with structural walls, concrete curb or other materials, that do not incorporate pre-curbs shall be isolated and separated from the guaranteed roofing membrane and are specifically not accepted under the '''''RoofStar Guarantee'''''.</p> |
<span class="recommended">Non-structural planters placed over landscaped deck and roofing membranes, with an appropriate protection layer, are strongly recommended whenever practical.</span> Structural planters that incorporate pre-curb or start-up curbs for walls that are completely sealed with membrane and are a minimum of 100 mm (4") in height, as detailed in the [[Construction Details|'''Construction Details''']] section, qualify for '''''RoofStar Guarantee''''' coverage. | <span class="recommended">Non-structural planters placed over landscaped deck and roofing membranes, with an appropriate protection layer, are strongly recommended whenever practical.</span> Structural planters that incorporate pre-curb or start-up curbs for walls that are completely sealed with membrane and are a minimum of 100 mm (4") in height, as detailed in the [[Construction Details|'''Construction Details''']] section, qualify for '''''RoofStar Guarantee''''' coverage. |
Revision as of 15:47, 24 October 2016
1 General
SBS Modified Bituminous membranes used on Landscaped and Vegetated roofing systems shall consist of two plies and the top ply (cap) must be a minimum thickness of 3.7 mm on the selvedge edge, with a minimum 180g / meters squared polyester or equal strength combination reinforcement. Thermoset and Thermo Plastic (EPDM, TPO, PVC) single ply membranes used for Landscaped and Vegetated roofing systems shall be fully adhered and a minimum thickness of 1.5mm (0.060").
2 Membrane Protection
Protection for roofing membranes is required during the installation and maintenance of landscaping, extensive and intensive vegetated (green) roofing installations. The minimum membrane protection must be installed by the roofing or waterproofing contractor and shall be 3 mm (⅛") asphalt core protection board or 25 mm (1") minimum extruded polystyrene insulation plus filter mat, root intrusion barrier, and drainage layer. Tightly butt all protection and insulation boards, overlap all filter mat seams and seal all laps of roof intrusion barriers to RoofStar Guarantee Standards and manufacturer’s installation instructions.
Only RoofStar-accepted SBS Modified Bituminous, Thermoset and Thermoplastic roofing membranes that are specifically accepted by the membrane manufacturer for use on Landscaped and Vegetated (green) roof systems qualify for coverage under the RoofStar Guarantee Program.
The Membrane Manufacturer and RoofStar Guarantee Program must confirm acceptance of other alternative protection systems or components in writing. Damage to membranes and flashings that results from the use of plants with aggressive root structures, (Bamboo, Willow etc.) for landscaped and green (vegetated) roof systems, is not the responsibility of the RoofStar Guarantee Program and is specifically not covered under the RoofStar Guarantee. For additional information refer to the latest addition of the British Columbia Landscape Standard, Green Roof Section.
Conventionally insulated roof assemblies are required to have a minimum 12.5mm (½") adhered approved RoofStar-accepted gypsum overlay board, and insulation boards with a minimum compressive strength of 20 psi, under the roof membrane for extensive vegetated systems (less than 200 mm, 8" in depth). Intensive vegetated systems (200 mm, 8" or more in depth) are not permitted over conventionally insulated roof systems.
2.1 Root Barriers & Separation Zones
Proprietary root intrusion barriers must be acceptable to the roof membrane manufacturer and appropriate for the vegetation system installed. Polyethylene or polypropylene sheeting used as a root barrier shall be a minimum thickness of .2mm (8mils). Root Barriers shall be sheets or boards installed in a continuous plane above the roof membrane, carried up the inside of soil retention perimeters (separation zones), and must be installed with sealed laps and seams as per manufacturer's instructions.
Separation Zones that are free of growing medium and vegetation are required around all roof perimeters, up-stands, drains, penetrations, mechanical equipment, expansion joints, etc. Zones must be a minimum of 300 mm (12”) wide and constructed with curbs or other physical barriers that separate and facilitate drainage. Physical barriers must be placed above the membrane protection layers and must not be attached through or penetrate the roof membrane.
2.2 Drainage
A drainage layer is required. Specialized proprietary drainage products must be acceptable to the membrane manufacturer.
3 Planter Design & Waterproofing
4 CSA A123.24 and Wind Uplift
All vegetative roof systems using a modular system are required to meet CSA A123.24 “Standard test method for wind resistance of modular vegetated roof assembly” (latest edition).
5 Flood Testing
6 Overburdens
6.1 Extensive Vegetative Roof Assemblies
Where Extensive Vegetative Roof Assemblies are installed as part of the roofing specification and / or contract (Extensive Vegetative Roof Assemblies are defined as roof top gardens having minimal plant species diversity, irrigated only to establish plants, and typically having a soil depth of less than 150 mm or 6 inches) the costs for removal and replacement of soil to access the membrane, to investigate or repair leaks in the membrane, are included in the RoofStar Guarantee coverage. However, the removal and replacement of plants, irrigation lines and or equipment, electrical lines, landscape and decorative features such as concrete pads, statues, planters, large rocks, etc., to investigate or repair leaks in the membrane, is not included, and is the responsibility of others. Subsequently, such access shall be provided and/or paid for by others.
6.2 Intensive Vegetative Roof Assemblies
Where Intensive Vegetative Roof Assemblies are installed as part of the roofing specification and/or contract (Intensive Vegetative Roof Assemblies are defined as roof top gardens with diverse plant species, irrigated for maintenance and typically having a soil depth equal to or more than 150 mm or 6 inches), and where the soil thickness of Intensive Vegetative Roof Assemblies exceeds 200 mm (8″), the removal and replacement of soil and plants to access the membrane to investigate or repair leaks in the membrane is the responsibility of others, and such access shall be paid by others. In addition, the removal and replacement of plants, irrigation lines or equipment, electrical lines, landscape and decorative features such as concrete pads, statues, planters, large rocks, etc., to investigate or repair leaks in the membrane is also the responsibility of others, and such access shall be provided and or paid for by others.
6.3 Planters
Structural planters that incorporate pre-curb or start-up curbs for walls that are completely sealed with membrane and are a minimum of 100 mm (4") in height, as detailed in Construction Detail D1.7.6-5 Curbs & Sleepers (Pre-curb for Planters), qualify for RoofStar Guarantee coverage. Waterproofing liners in planters with structural walls, concrete curb or other materials, that do not incorporate pre-curbs shall be isolated and separated from the guaranteed roofing membrane and are specifically not accepted under the RoofStar Guarantee.
Non-structural planters placed over landscaped deck and roofing membranes, with an appropriate protection layer, are strongly recommended whenever practical. Structural planters that incorporate pre-curb or start-up curbs for walls that are completely sealed with membrane and are a minimum of 100 mm (4") in height, as detailed in the Construction Details section, qualify for RoofStar Guarantee coverage.
Waterproofing liners in planters with structural walls, concrete curb or other materials, that do not incorporate pre-curbs shall be isolated and separated from the guaranteed roofing membrane and are specifically not accepted under the RoofStar Guarantee. Conventionally insulated roof assemblies are required to have a minimum 12.5mm (½") adhered approved RoofStar-accepted gypsum overlay board, and insulation boards with a minimum compressive strength of 20 psi, under the roof membrane for extensive vegetated systems (less than 200 mm, 8" in depth). Intensive Vegetative Roof Assemblies in excess of 200 mm (8") or more in depth are not permitted over conventionally insulated roof systems.
7 Walkways and Warning Zones
When primary roof membranes of contrasting colour are used for warning zones, membrane end lap off sets and ply side lap directions must be maintained. Staggered membrane end lap offsets may be positioned below primary roof membranes that are used for warning zones.
Where walkways are employed, they must be designed to facilitate drainage of water. To promote drainage, use accepted concrete-topped XPS insulation panels, or pavers located on purpose-made XPS insulation panels. When pavers are used as the walkway material, they must be spaced no closer than 3mm (1/8″) and must be supported by non-abrasive pads or proprietary pedestals providing a minimum of 12.5 mm (1/2″) of vertical separation layer for airflow and levelling. The choice of pedestal or drainage layer type is the responsibility of the design authority. Pedestals provide airflow for drying surfaces and assist in leveling. They should not impede the flow of water or air, and should uniformly distribute the dead load of pavers and predicted live loads.
A design authority or membrane manufacturer may specify a proprietary walkway protection system or warning zone membrane over the primary roof membrane. Walkway and warning zone materials are not part of the roofing membrane assembly but are typically accessory products that are placed over completed roof membranes. Subsequently the type and performance of any walkway or warning zone material is specifically excluded from coverage under the RoofStar Guarantee, as is any detrimental effect the materials may have on the roof system.